Plan Review Details - Permit 22110661
Plan Review Stops For Permit 22110661
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-28 Cont ID  
Sent By rmcdouga Date 2023-04-28 Time 13:35 Rev Time 0.00
Received By rmcdouga Date 2023-04-28 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-14 Cont ID  
Sent By rmcdouga Date 2023-04-14 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2023-04-14 Time 09:05 Sent To  
Notes
2023-04-14 10:10:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A SURVEY. SHOW THE LOCATION OF THE GENERATOR
 AND SET BACKS FROM PROPERTY LINES AND BUILDINGS. FBC
 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. FBC-R303.5.1
 INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR
 INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS. THIS SHOULD BE
 NOTED ON THE SURVEY.
  
 3) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 PROPOSED 24 KW GENERATOR. FBC 107.2.1
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By rperdomo Date 2023-05-03 Time 15:23 Rev Time 0.00
Received By rperdomo Date 2023-05-03 Time 15:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-04-18 Cont ID  
Sent By rperdomo Date 2023-04-18 Time 09:30 Rev Time 0.00
Received By rperdomo Date 2023-04-18 Time 09:06 Sent To  
Notes
2023-04-18 09:32:49FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE MANUFACTURE' S SPECIFICATIONS FOR THE
 PROPOSED 24 KW GENERATOR. FBC 107.3.5
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-04 Cont ID  
Sent By aoliver Date 2023-05-04 Time 08:21 Rev Time 0.00
Received By aoliver Date 2023-04-21 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-19 Cont ID  
Sent By aoliver Date 2023-04-19 Time 07:15 Rev Time 0.00
Received By aoliver Date 2023-04-07 Time 13:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-14 Cont ID  
Sent By rmcdouga Date 2023-04-14 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2023-04-14 Time 09:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-28 Cont ID  
Sent By rmcdouga Date 2023-04-28 Time 13:35 Rev Time 0.00
Received By asangele Date 2023-04-28 Time 13:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-04-17 Cont ID  
Sent By ASangele Date 2023-04-17 Time 18:33 Rev Time 0.00
Received By asangele Date 2023-04-17 Time 18:33 Sent To  
Notes
2023-04-17 18:34:29FAILED
 4/17/2023
  
 PLEASE PROVIDE A SURVEY WITH APPLICATION AND INDATE
 WHERE THE GENERATOR WILL BE LOCATED.
  
 ARTICLE X SECTION 94-305
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK.
  
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]