| 2022-12-21 11:24:09 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22110655 |
| | ADD: 700 S ROSEMARY SUITE; ??? |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | 1) PERMIT APPLICATION, THE SUITE # B8 DOES NOT MEET THE |
| | CITY STANDARD FOR ADDRESSING. 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. 2020 FBC-B 501.2 ADDRESS |
| | IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE |
| | PROVIDED WITH APPROVED ADDRESS IDENTIFICATION. PLEASE |
| | IDENTIFY LOCATION OF UNIT. |
| | 2) TITLEBLOCK TO CORRECT THE TENANT IMPROVEMENT ADDRESS |
| | TENANT SPACE IN THE TITLE BLOCK ONCE THE CITY OF WEST |
| | PALM BEACH PROVIDES AN APPROVED ADDRESS. SEE NOTES |
| | UNDER THE ADDRESS PLAN REVIEW FOR COMMENTS. FL. |
| | ADMINISTRATIVE CODE 61G1-16.004. |
| | 3) COVERSHEET: UNDER THE HEADING 7 JURISDICTION WRONG |
| | STREET ADDRESS, THAT GIVEN IS FOR PALM BEACH COUNTY |
| | BUILDING DEPARTMENT NOT THE CITY OF WEST PALM BEACH. |
| | 4) SHEET LIFE SAFETY PLAN: NEW STORE FRONT GLAZING AND |
| | RECESSED DOUBLE DOOR ENTRY. NOTE AT ENTRY IS TAKING THE |
| | EGRESS CAPACITY FACTOR OF 0.15 INCHES. TO TAKE THIS |
| | FACTOR THE LIFE SAFETY PLAN SHOULD ALSO INCLUDE ALL |
| | FACTORS INVOLVED UNDER THE 2020 FBC-BUILDING CODE |
| | 1005.3.2 EXCEPTION # 1.THE BUILDING IS TO BE COMPLETELY |
| | SPRINKLERED IN ACCORDANCE WITH 903.3.1.1 OR 903.3.1.2 |
| | AND THE BUILDING SHALL HAVE AN EMERGENCY VOICE/ ALARM |
| | COMMUNICATION SYSTEM IN ACCORDANCE WITH SECTION |
| | 907.5.2.2. |
| | 5) SHEET A201 TOILET ROOM ELEVATIONS THE TOILET TISSUE |
| | DISPENSER IS MEASURED HORIZONTALLY FROM THE REAR |
| | RESTROOM WALL. PLEASE REFER TO THE 2020 |
| | FBC-ACCESSIBILITY CODE SECTION. 604.7. THE TOILET PAPER |
| | DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES |
| | MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. |
| | 6) AE100 EXISTING CONDITIONS, KEY NOTE # 3 STATES THE |
| | LANDLORD HAS REMOVED THE EXISTING STOREFRONT, PLEASE |
| | PROVIDE THE DEMO-PERMIT FOR THIS WORK. FOR THE ADDRESS |
| | 700 S. ROSEMARY THERE WAS ONLY ONE DEMO PERMIT PULLED |
| | FOR THE 700 BLOCK OF SOUTH ROSEMARY 22100811 FOR UNIT # |
| | 124. |
| | |
| | 7) SHEET S00 WIND DESIGN LOADS THE SHOW 170 MPH VULT, |
| | IMPORTANCE FACTOR IS GIVEN AS 1.0 AND EXPOSURE AS C BUT |
| | THE PLANS STATE DESIGN PRESSURES ON COMPONENTS AND |
| | CLADDING IN ACCORDANCE WITH ASCE 7-16 CHAPTER 30 BUT |
| | THERE ARE NO WIND DESIGN PRESSURES GIVEN. PLEASE ALSO |
| | CONSIDER THE HEIGHT FACTOR AND MULTIPLIERS. PLEASE ALSO |
| | PROVIDE THE COMPONENT & CLADDING PRESSURES IN VASD |
| | SINCE ALL PRODUCT APPROVALS ARE IN VASD. |
| | 8) SHEET A301 SHOWS A CUT AWAY SECTION OF THE NEW |
| | STOREFRONT SYSTEM. THE QUESTION IS ON SHEET A-300 & |
| | A-302 DETAIL 1 SHOWS THE NEW STOREFRONT WALL IN THE |
| | SAME LOCATION WITH FOOTER. THE NEW RECESSED AREA OF |
| | WALL DETAIL 4 ALSO SHOWS A RECESSED FOOTER, THIS WAS |
| | FORMALLY INTERIOR FLOOR SPACE, IS THERE A MONOLITHIC |
| | FOOTER FOR THE NEW STEEL 4X4 COLUMNS? 2020 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1. 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | 9) NEITHER A301 OR S100 DETAIL B SHOW IF THE NEW STEEL |
| | COLUMNS ARE TO CONTINUE TO THE DECK ABOVE AND ANCHOR |
| | INTO THE FLOOR/ CEILING DECK ABOVE? SHEET S300 DETAIL 2 |
| | DOES NOT DESIGNATE IF THIS IS STEEL COLUMN OR METAL |
| | STUD INFILL. THE PLANS ARE ALSO SILENT IF THE STEEL |
| | STUD INFILL ARE ARCHITECTURAL OR STRUCTURAL. THERE IS A |
| | NOTE STOREFRONT SYSTEM BY DELEGATE ENGINEER. PLEASE |
| | PROVIDE ADDITIONAL INFORMATION. 107.2.1. CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | 10) WELDED OR BOLTED CONNECTIONS. THIS BUILDING |
| | CONTAINS EITHER BOLTED AND OR WELDED CONNECTIONS. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD |
| | BRUNELLE AT 561-805-6670. |
| | 11) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS |
| | AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, |
| | 12) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| | OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | 13) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | 14) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | 15) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | 16) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |