Plan Review Details - Permit 22110628
Plan Review Stops For Permit 22110628
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-03-29 Cont ID  
Sent By cpuell Date 2023-03-29 Time 12:46 Rev Time 0.00
Received By cpuell Date 2023-03-29 Time 12:46 Sent To  
Notes
2023-03-29 12:47:22ADDRESS FOR THE PROJECT HAS BEEN AGREED AS 2484
 PINEWOOD AVE UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2023-02-28 Time   Rev Time 0.00
Received By cpuell Date 2023-02-28 Time 15:11 Sent To  
Notes
2023-02-28 15:16:04AN ADDRESS NEEDS TO BE ASSIGNED TO THIS PROJECT,
 2.12.22 I EMAIL BERNARDO VANEGAS THE FOLLOWING
 ADDRESSES FOR THE PROJECT: 615 23RD ST (IF BROADWAY IS
 GOING TO BE EXTENDED THEN THIS SHOULD BE CHANGED TO A
 BROADWAY ADDRESS)
 629 23RD ST
 635 23RD ST
 637 23RD ST
 641 23RD ST
  
 590 NORTHWOOD RD
 620 NORTHWOOD RD
 634 NORTHWOOD RD
 650 NORTHWOOD RD
 662 NORTHWOOD RD
 672 NORTHWOOD RD
  
 585 NORTHWOOD RD
 645 NORTHWOOD RD
 659 NORTHWOOD RD
 679 NORTHWOOD RD
  
 580 24TH ST
 636 24TH ST
 654 24TH ST
 680 24TH ST
  
 641 24TH ST
 655 24TH ST
 667 24TH ST
 681 24TH ST
  
 612 25TH ST
 624 25TH ST
  
 2461 PINEWOOD AVE
 2471 PINEWOOD AVE
 2515 PINEWOOD AVE
 2525 PINEWOOD AVE
 2541 PINEWOOD AVE
 2555 PINEWOOD AVE
 2575 PINEWOOD AVE
  
 2462 PINEWOOD AVE
 2464 PINEWOOD AVE
 2476 PINEWOOD AVE
 2484 PINEWOOD AVE
 2556 PINEWOOD AVE
 2576 PINEWOOD AVE
  
 2419 BROADWAY
 2435 BROADWAY
 2451 BROADWAY
 2471 BROADWAY
 2527 BROADWAY
 2541 BROADWAY
 2561 BROADWAY
 2571 BROADWAY
  
 2426 BROADWAY
 2436 BROADWAY
 2458 BROADWAY
 2470 BROADWAY
  
 THEN BRYAN BENHAMOU WAS SENT THE LIST OF PROPOSED
 ADDRESSES ON 12.16.22, THANK ME FOR MY EMAIL STATED
 THAT THEY WOULD DISCUSS INTERNALLY AND HAVE NOT HEARD
 FROM ANYONE. PLEASE CONTACT [email protected] OR
 CALL 561-805-6659 TO DISCUSS ADDRESSING. FOR THE
 FOUNDATION PERMIT WE ONLY NEED TO START WITH THE
 PRIMARY ADDRESS FOR THE PROJECT. ALSO THE PARCEL WILL
 NEED TO BE REPLATTED SO THAT THERE IS ONLY ONE PARCEL,
 WHERE ARE YOU IN THAT STAGE, PLEASE EMAIL ME THE
 PRELIMINARY PCN LETTER FROM THE PROPERTY APPRAISERS.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2023-05-22 Cont ID  
Sent By swelter Date 2023-05-22 Time 10:50 Rev Time 0.00
Received By swelter Date 2023-05-22 Time 11:28 Sent To  
Notes
2023-05-22 11:28:23MISSING ART ASSESSMENT APPLICATION AND ESCROW OF FUNDS
 OR CONTRIBUTION INTO THE FUNDS.
  
 ALLL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $500,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS PUBLIC ART REQUIREMENT, EVEN
 IF THE BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED
 IN PHASES
  
 OPTION 1: INSTALL AND ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
  
 IF INSTALLING ARTWORK OPTION 1, SUBMIT AN ART
 ASSESSMENT APPLICATION, WHICH INCLUDES ALL DOCUMENTS
 INCLUDING EVIDENCE OF ESCROW. THE ART APPLICATION SHALL
 BE SUBMITTED WITH THE APPLICATION FOR A BUILDING
 PERMIT.
  
 OF NOTE ARTWORK SHALL BE CLEARLY DEMONSTRATED ON ALL
 SITE-PLANS SUBMITTED FOR CITY APPROVALS.
  
 ART ASSESSMENT IS DUE NOW ESCROW OR DIRECT DEPOSIT DUE
 NOW.
  
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-07-25 Cont ID  
Sent By rmcphers Date 2023-07-25 Time 14:52 Rev Time 0.00
Received By rmcphers Date 2023-07-25 Time 14:37 Sent To  
Notes
2023-07-25 14:52:05FOUNDATION AND STRUCTURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE ADDED DRAWING A301.5 SHOWS EV CHARGING STATIONS
 - PLEASE SHOW THAT AT LEAST 1 OF THE CHARGING STATIONS
 IS AN ACCESSIBLE PARKING SPACE, ACCESS AISLE, SIGNAGE
 ETC. PER FBC A 502
 FBC 406.1.7 ELECTRIC VEHICLE CHARGING STATIONS.
 ACCESSIBILITY TO ELECTRIC VEHICLE CHARGING STATIONS
 SHALL BE PROVIDED IN ACCORDANCE WITH CHAPTER 11.
  
 2) PLEASE SHOW THE STORM WATER DRAINAGE - SITE OR CIVIL
 PLAN SHOULD SHOW ALL OF THE FOLLOWING FBC WPB 107.2.5
 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH
 THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A
 SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-11 Cont ID  
Sent By rmcphers Date 2023-05-11 Time 14:15 Rev Time 0.00
Received By rmcphers Date 2023-05-11 Time 13:26 Sent To  
Notes
2023-05-11 14:15:30FOUNDATION AND STRUCTURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER
 THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 A) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 2) PLEASE SHOW THE BUILDING SETBACKS FROM THE PROPERTY
 LINES AND OTHER BUILDINGS. THE SITE PLAN OR CIVIL PLAN
 NEEDS TO SHOW ALL OF THE FOLLOWING INFORMATION - FBC
 WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-20 Cont ID  
Sent By rmcphers Date 2023-03-20 Time 09:38 Rev Time 0.00
Received By rmcphers Date 2023-03-16 Time 15:50 Sent To  
Notes
2023-03-20 09:38:06FOUNDATION AND STRUCTURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S-1.0A SHOWS THE 2014 FBC - SHOULD BE 2020
 FBC
  
 2) PLEASE PROVIDE THE LIFE SAFETY PLANS FOR EACH FLOOR.
  
 3) EACH SEPARATE BUILDING REQUIRES A SEPARATE PERMIT
 WITH ITS OWN PLANS - PLEASE REMOVE THE DRAWINGS IN THIS
 PERMIT FOR BUILDINGS "B" AND "C"
  
 4) PLEASE SHOW THE ACCESSIBLE VAN PARKING HEIGHT AND
 LOCATION - 502.5 VERTICAL CLEARANCE.
 PARKING SPACES FOR VANS AND ACCESS AISLES AND VEHICULAR
 ROUTES SERVING THEM SHALL PROVIDE A VERTICAL CLEARANCE
 OF 98 INCHES (2490 MM) MINIMUM.
  
 5) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER
 THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 A) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 6) DRAWINGS S-8.1, S-8.2, S-8.3, S-8.4, S-8.5, S-8.6 DO
 NOT SHOW THE WIND PRESSURES AS STATED ON THOSE
 DRAWINGS.
  
 7) PLEASE PROVIDE A STORM WATER DRAINAGE PLAN. FBC WPB
 107.2.5

Review Stop E ELECTRICAL
Rev No 3 Status   Date 2023-07-26 Cont ID  
Sent By mpeterso Date 2023-07-26 Time 14:49 Rev Time 0.00
Received By mpeterso Date 2023-07-26 Time 14:47 Sent To  
Notes
2023-07-26 14:52:54EMAILED THE APPLICANT TO PROVIDE A MISSING NARRITIVE
 RESPONSE. THEY EMAILED BACK WITH A RESPONSE. I WILL
 CONTINUE THE REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-05-17 Cont ID  
Sent By mpeterso Date 2023-05-17 Time 15:57 Rev Time 0.00
Received By mpeterso Date 2023-05-17 Time 08:59 Sent To  
Notes
2023-05-17 16:00:41ELECTRIC REVIEW FAILED 2ND CYCLE
  
 1) SUBMITTAL DOES NOT INCLUDE ALL DRAWINGS INDICATED ON
 PLAN INDEX SHEET CS001. MISSING DRAWINGS INCLUDE ALL
 ELECTRICAL DRAWINGS E202.1 -E202.8 . THESE DRAWINGS ARE
 ALSO REFERENCED ON SHEET E200.
  
 2) PLEASE PROVIDE SHEETS LABELED E200.1 AND E200.3
 (SECTIONS OF BUILDING A). FBC 107.2
  
 3) SHEET E501B, CORRECTLY LABELED, ELECTRICAL RISER
 DIAGRAM BUILDING A, AND IS AGAIN LABELED BELOW THE
 DIAGRAM AS BUILDING B. IN ADDITION THE SUBMITTAL NAME
 IS CALLED OUT INCORRECTLY AS RISER B. PLEASE CORRECT AS
 APPLICABLE. FBC 107.2
  
 4) PLEASE CORRECT LABELING FOR SHEET E502A SUBMITTAL
 NAME INDICATES RISE INSTEAD OF CORRECTLY NAMING
 ELECTRIC CALCS AND RISER NOTES
  
 5) PLEASE ENSURE ALL SHEET NAMES ARE CORRECTLY LABELED
 ON SHEETS AND SUBMITTAL NAMING. FBC 107.2
  
 6) PLEASE PROVIDE ELECTRIC RISER DIAGRAM FOR BUILDING
 C. FBC 107.2
  
 7) PLEASE PROVIDE INDICATIONS THAT ALL OVERCURRENT
 PROTECTION RATED 1200 AMPS AND ABOVE CONTAIN ARC ENERGY
 REDUCTION METHOD IN ACCORDANCE WITH NEC 240.87 (A) AND
 (B)
  
 8) PLEASE PROVIDE INDICATIONS THAT ALL FEEDER
 DISCONNECTS RATED 1000 AMPS AND ABOVE, FOR SYSTEMS OF
 MORE THAN 150 VOLTS TO GROUND ARE PROVIDED WITH GROUND
 FAULT PROTECTION. NEC 215.10 NEC
  
 9) PLEASE PROVIDE FLOOR PLANS FOR BOTH ELECTRIC ROOMS
 IN BUILDING A, B AND C LOCATING ALL ELECTRICAL
 EQUIPMENT AND INDICATING ALL CLEARANCES REQUIRED IN
 ACCORDANCE WITH NEC 110.26 ARE MET. FBC 107.2
  
 10) PLEASE PROVIDE FLOOR PLANS FOR FIRE PUMP ROOM IN
 BUILDING A LOCATING ALL EQUIPMENT AND INDICATING ALL
 REQUIREMENTS OF NEC ARTICLE 695 ARE MET. FBC 107.2
  
 11) PLEASE PROVIDE FLOOR PLANS FOR GENERATOR ROOM IN
 BUILDING A LOCATING ALL EQUIPMENT AND INDICATING ALL
 REQUIREMENTS OF NEC ARTICLE 700, 445 AND CLEARANCES IN
 ACCORDANCE TO NEC 110.26. FBC 107.2
  
 12) PLEASE PROVIDE A NOTE STATING ALL LOW VOLTAGE
 WIRING SYSTEMS INCLUDING BUT NOT LIMITED TO FIRE ALARM,
 VOICE, DATA TELEPHONE, TV, SATELLITE, SECURITY AND BDA,
 DAS, CELL PHONE ENHANCEMENT SYSTEMS REQUIRE A SEPARATE
 PERMIT. IN ADDITION, SITE LIGHTING AND SIGNS WILL BE
 REQUIRED TO BE SEPARATE PERMITS
  
 13) PLEASE PROVIDE A FEEDER SCHEDULE FOR ALL RISER
 DIAGRAMS. NEC 215.5
  
 14) SUBMITTAL CONTAINS SOME ELECTRIC SHEETS THAT HAVE A
 RED X ON THEM. IF THESE SHEETS ARE NOT INCLUDED WITH
 THE SUBMITTAL PLEASE HAVE THEM REMOVED. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-07 Cont ID  
Sent By mpeterso Date 2023-03-07 Time 10:21 Rev Time 0.00
Received By mpeterso Date 2023-03-06 Time 10:20 Sent To  
Notes
2023-03-07 10:22:12ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL ON SHEET E400A COMPLIANCE WITH NEC
 695.14(E), PROTECTION OF FIRE PUMP GENERATOR CONTROL
 WIRING
 2) PLEASE DETAIL COMPLIANCE WITH NEC 230.95, GROUND
 FAULT PROTECTION FOR 480V/2000A MDP-RS AND 480/2500A
 MDP-RN
 3) PLEASE DETAIL COMPLIANCE WITH NEC 695.39(B) FOR
 BUILDINGS B AND C, ALTERNATE SOURCE OF POWER, AS THE
 AHJ DOES NOT REGARD FPL UTILITY POWER AS A RELIABLE
 SOURCE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2023-07-18 Cont ID  
Sent By cseifer Date 2023-07-18 Time 15:24 Rev Time 0.00
Received By cseifer Date 2023-07-18 Time 15:24 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-06-07 Cont ID  
Sent By lquinone Date 2023-05-09 Time 14:05 Rev Time 0.00
Received By lquinone Date 2023-06-07 Time 10:46 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-02-21 Cont ID  
Sent By rrossano Date 2023-02-21 Time   Rev Time  
Received By rrossano Date 2023-02-21 Time   Sent To  
Notes
2023-02-21 11:24:45UNDER FORMAL ENGINEERING SUBMITTAL REVIEW (E22120042).

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-07-17 Cont ID  
Sent By pleduc Date 2023-07-17 Time   Rev Time 0.00
Received By pleduc Date 2023-07-17 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-08 Cont ID  
Sent By pleduc Date 2023-05-08 Time   Rev Time 0.00
Received By pleduc Date 2023-05-08 Time 14:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-02-23 Cont ID  
Sent By pleduc Date 2023-02-23 Time   Rev Time 0.00
Received By pleduc Date 2023-02-22 Time 11:05 Sent To  
Notes
2023-02-22 12:37:12FIRE COMMENT:
  
 ANY FIRE LINE UNDERGROUND THAT MAY BE INSTALLED UNDER
 THIS PERMIT SHALL BE SUBMITTED UNDER SEPARATE PERMIT &
 SHOP
 DRAWING PER NFPA 24 AND MANUFACTURES SPECIFICATIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-14 Time 09:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-05 Cont ID  
Sent By aoliver Date 2023-06-05 Time 07:24 Rev Time 0.00
Received By aoliver Date 2023-05-05 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-04 Cont ID  
Sent By lmarchan Date 2023-04-04 Time 15:08 Rev Time 0.00
Received By lmarchan Date 2023-02-16 Time 10:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-03-20 Cont ID  
Sent By rmcphers Date 2023-03-20 Time 09:38 Rev Time 0.00
Received By rmcphers Date 2023-03-20 Time 09:38 Sent To  
Notes
2023-03-20 09:38:50PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-07-19 Cont ID  
Sent By ccole Date 2023-07-19 Time 15:00 Rev Time 0.00
Received By ccole Date 2023-07-19 Time 08:31 Sent To  
Notes
2023-07-19 15:02:463RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22110628
 7/19/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE NOTE A COMPLETE
 REVIEW OF THE PLUMBING SYSTEMS WAS NOT PERFORMED UNDER
 THIS FOUNDATION PERMIT, AND ADDITIONAL COMMENTS
 IMPACTING THE UNDERGROUND PIPING SYSTEMS MAY OCCUR
 UNDER THE MAIN PERMIT REVIEW.
  
 1) SHEET P200.1, P200.3, P200.5, P402A: BASED ON THE
 SCHIER SI & GI SPECIFICATIONS SHOWN ON THE DERM SHEETS
 THE GREASE INTERCEPTOR INLET AND OUTLET PIPINGS SHALL
 BE 4-INCH- SEC. 1003.3.5.1 FBC P. THE PLANS SHOW 3-INCH
 FOR FOG SYSTEMS #1 & 3.
  
 2) BUILDING A GROUND FLOOR SHEETS P200.1, .2, .3, .4,
 .5, .6: AS PREVIOUSLY REQUESTED IN THE 1ST AND 2ND
 REVIEWS PLEASE SHOW THE FOLLOWING ITEMS.
  
 A) DFU'S FOR SANITARY PIPING AT RISERS, BRANCHES AND
 MAIN BUILDING DRAINS- TABLE 710.1(1) FBC P.
  
 B) STORM DRAINAGE FLOW IN GPM FOR EACH STORM DRAIN
 BRANCH AND MAIN- TABLE 1106.2 FBC P.
  
 C) AC CONDENSATE AND WATER HEATER DISCHARGE VERTICAL
 RISER LOCATIONS AND HORIZONTAL UNDERGROUND PIPING RUNS
 AND TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1,
 504.7.2 FBC P.
  
 D) EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
  
 3) 2ND REQUEST FOR GREASE INTERCEPTOR PERMIT
 APPLICATIONS.
  
 PLEASE NOTE DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO APPROVAL OF THIS PLUMBING REVIEW. YOU CAN SUBMIT
 APPLICATIONS TBD (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 A) SHEET P402A: 2ND REQUEST TO SHOW VENTING FOR THE
 INTERCEPTORS- SEC. 1003.9 FBC P.
  
 B) P9.00- P905 DERM SHEETS: 2ND REQUEST TO PROVIDE
 HEAVY DUTY LIDS FOR THE INTERCEPTOR CLEANOUTS. PLEASE
 PROVIDE MANUFACTURER AND MODEL NUMBER OF THE LIDS- SEC.
 305.7 FBC P.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-05-10 Cont ID  
Sent By ccole Date 2023-05-10 Time 11:15 Rev Time 0.00
Received By ccole Date 2023-05-09 Time 16:58 Sent To  
Notes
2023-05-10 17:05:242ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22110628
 5/10/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS MANY OF THE KEY PLUMBING DRAWINGS
 INCLUDING P200.1- P.200.6 WHICH ARE THE UNDERGROUND
 DRAINAGE PIPING PLANS FOR BUILDING A HAVE NOT BEEN
 CORRECTED AND RESUBMITTED (SEE 1ST REVIEW COMMENT #4
 COPIED BELOW). RESUBMITTED IN THEIR PLACES ARE
 P.200.1A- P200.6A WHICH ARE WATER AND GAS PLANS. PLEASE
 RESUBMIT THE PLANS WITH THE REQUESTED CORRECTIONS PER
 COMMENT #4.
  
 4) P200.1- P200.6 BUILDING A GROUND LEVEL PLANS:
 A) SANITARY AND STORM DRAIN PIPE SIZES MISSING- TABLES
 710.1(1), 710.1(2), 1106.2 FBC P.
 B) DFU'S FOR SANITARY PIPING NOT SHOWN- TABLE 710.1(1).
 C) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH
 STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P.
 D) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION
 LOCATIONS- SEC. 1108.2 FBC P.
 E) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE
 VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND
 TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2
 FBC P.
 F) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE
 PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC.
 712.3.5 FBC P.
 G) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
  
 2) 2ND REQUEST FOR POTABLE WATER BACKFLOW PERMIT
 APPLICATIONS. SHEET SP200: THE PLAN SHOWS MULTIPLE RPZ
 BACKFLOW PREVENTERS FOR THE POTABLE WATER AND FIRE
 SERVICE LINES FOR BUILDINGS WHICH WILL REQUIRE SEPARATE
 PERMIT SUBMITTALS FOR EACH ONE. CONCERNING THE RPZ'S
 FOR THE POTABLE WATER PLEASE NOTE DUE TO A CHANGE IN
 PROCESS, THE BACKFLOW PERMITS ARE REQUIRED TO BE
 SUBMITTED PRIOR TO APPROVAL OF THIS PLUMBING REVIEW.
 YOU CAN SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 A) PLEASE NOTE THAT THE SEPARATE PERMIT SUBMITTALS FOR
 THE BACKFLOW PREVENTERS SHALL INCLUDE A MANUFACTURER'S
 SPECIFICATION SHEET SHOWING THE MAKE, MODEL AND SIZE OF
 THE DEVICE, AND WHICH STATES THE DEVICE IS LEAD-FREE
 AND IS ON THE APPROVED DEVICE LIST PUBLISHED BY THE
 UNIVERSITY OF SOUTHERN CALIFORNIA (USC). ALSO REQUIRED
 IS A SITE OR CIVIL SHOWING THE LOCATION OF THE BACKFLOW
 PREVENTER- SEC. 107.2.1 WPB.
  
 3) P200.7 & P.200.8: 2ND REQUEST TO PROVIDE THE STORM
 DRAINAGE FLOW IN GPM FOR EACH STORM DRAIN BRANCH AND
 MAIN- TABLE 1106.2 FBC P.
  
 4) P402A: SHOW THE LOCATION OF THE GREASE AND SOLIDS
 INTERCEPTORS ON THE SANITARY DRAINAGE FLOOR PLANS- SEE
 COMMENT #1 ABOVE.
 PLEASE NOTE DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO APPROVAL OF THIS PLUMBING REVIEW. YOU CAN SUBMIT
 APPLICATIONS TBD (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
 GREASE INTERCEPTOR PLAN REVIEW REQUIREMENTS.
  
 A) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND
 CAPACITY OF THE UNIT.
 B) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
 C) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND
 SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL
 VENTS, AND SAMPLING PORTS.
 D) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF
 RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P.
 E) ACCESS LID DETAILS INDICATING THE LIDS WILL BE HEAVY
 DUTY TRAFFIC RATED AND WILL BE EQUIPPED WITH ACCESS
 RESTRICTORS. HEAVY DUTY LIDS ARE ALSO REQUIRED FOR
 CLEANOUTS, AND SAMPLING PORTS (IF INSTALLED).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-21 Cont ID  
Sent By ccole Date 2023-02-21 Time 17:11 Rev Time 0.00
Received By ccole Date 2023-02-17 Time 16:50 Sent To  
Notes
2023-02-21 17:19:371ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22110628
 2/21/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET SP200: THE PLAN SHOWS MULTIPLE RPZ BACKFLOW
 PREVENTERS FOR THE POTABLE WATER AND FIRE SERVICE LINES
 FOR BUILDINGS WHICH WILL REQUIRE SEPARATE PERMIT
 SUBMITTALS FOR EACH ONE. CONCERNING THE RPZ'S FOR THE
 POTABLE WATER PLEASE NOTE DUE TO A CHANGE IN PROCESS,
 THE BACKFLOW PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO APPROVAL OF THIS PLUMBING REVIEW. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 A) PLEASE NOTE THAT THE SEPARATE PERMIT SUBMITTALS FOR
 THE BACKFLOW PREVENTERS SHALL INCLUDE A MANUFACTURER'S
 SPECIFICATION SHEET SHOWING THE MAKE, MODEL AND SIZE OF
 THE DEVICE, AND WHICH STATES THE DEVICE IS LEAD-FREE
 AND IS ON THE APPROVED DEVICE LIST PUBLISHED BY THE
 UNIVERSITY OF SOUTHERN CALIFORNIA (USC). ALSO REQUIRED
 IS A SITE OR CIVIL SHOWING THE LOCATION OF THE BACKFLOW
 PREVENTER- SEC. 107.2.1 WPB.
  
 2) PROVIDE SANITARY DRAINAGE AND WATER RISER DRAWINGS
 FOR BUILDING A- SEC. 107.3.5.1.3 WPB.
  
 3) PROVIDE PRIMARY AND SECONDARY ROOF DRAINAGE RISER
 DRAWINGS- SEC. 107.3.5.1.3 WPB.
  
 4) P200.1- P200.6 BUILDING A GROUND LEVEL PLANS:
 A) SANITARY AND STORM DRAIN PIPE SIZES MISSING- TABLES
 710.1(1), 710.1(2), 1106.2 FBC P.
 B) DFU'S FOR SANITARY PIPING NOT SHOWN- TABLE 710.1(1).
 C) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH
 STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P.
 D) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION
 LOCATIONS- SEC. 1108.2 FBC P.
 E) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE
 VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND
 TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2
 FBC P.
 F) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE
 PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC.
 712.3.5 FBC P.
 G) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
  
 5) P200.7:
 A) LABEL THE WASTE AND SOIL STACK LOCATIONS USING THE
 LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1 WPB.
 B) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH
 STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P.
 C) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE
 VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND
 TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2
 FBC P.
 D) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE
 PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC.
 712.3.5 FBC P.
 E) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
 F) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION
 LOCATIONS- SEC. 1108.2 FBC P.
  
 6) P200.8:
 A) LABEL THE WASTE AND SOIL STACK LOCATIONS USING THE
 LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1 WPB.
 B) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH
 STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P.
 C) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE
 VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND
 TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2
 FBC P.
 D) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE
 PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC.
 712.3.5 FBC P.
 E) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
 F) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION
 LOCATIONS- SEC. 1108.2 FBC P.
  
 7) P300: THERE ARE TWO P300 PLAN SHEETS APPARENTLY ONE
 FOR BUILDING B AND ONE FOR BUILDING C HOWEVER THEY ARE
 NOT TITLED PROPERLY TO DISTINGUISH ONE FROM THE OTHER-
 SEC. 107.2.1 WPB.
  
 8) P300: THE WATER RISERS ARE INCORRECTLY LABELED AS
 RAIN WATER LEADER RISERS- SEC. 107.2.1 WPB.
  
 9) P301: THERE ARE TWO P301 PLAN SHEETS APPARENTLY ONE
 FOR BUILDING B AND ONE FOR BUILDING C HOWEVER THEY ARE
 NOT TITLED PROPERLY TO DISTINGUISH ONE FROM THE OTHER-
 SEC. 107.2.1 WPB.
 A) SAN. ISO: LABEL THE WASTE AND SOIL STACK LOCATIONS
 USING THE LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1
 WPB.
 B) STORM ISO: PROVIDE THE STORM DRAINAGE FLOW IN GPM
 FOR EACH STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC
 P.
  
 10) P500 DETAIL 6: PROVIDE THE MAKE AND MODEL OF THE
 CLEANOUT ASSEMBLY SHOWN IN THE DETAIL- SEC. 708.1.10.2
 FBC P.
  
 11) P502 DETAILS 5 & 11: THE POOL SHALL BE UNDER
 SEPARATE PERMIT HOWEVER CONCERNING POOL WASTE WATER
 DISPOSAL AS SHOWN IN THE DETAILS PLEASE NOTE THE
 FOLLOWING-
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-07-26 Cont ID  
Sent By rmcphers Date 2023-07-26 Time 07:42 Rev Time 0.00
Received By rmcphers Date 2023-07-26 Time 07:40 Sent To  
Notes
2023-07-26 07:42:14SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE EROSION CONTROL DRAWINGS AND THE BACK FLOW
 PREVENTER DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2023-07-19 15:05:38PLUMBING PLAN SIGNATURES PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-10 Cont ID  
Sent By ccole Date 2023-05-10 Time 10:59 Rev Time 0.00
Received By ccole Date 2023-05-10 Time 10:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-07 Cont ID  
Sent By mpeterso Date 2023-03-07 Time 14:12 Rev Time 0.00
Received By mpeterso Date 2023-03-07 Time 14:12 Sent To  
Notes
2023-03-07 14:12:47ALL PLANS PASSED SIGNATURE REVIEW. MP
2023-02-21 11:16:08PLUMBING (P) PLAN SHEETS APPROVED.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2023-07-25 Cont ID  
Sent By rmcphers Date 2023-07-25 Time 14:52 Rev Time 0.00
Received By rmcphers Date 2023-07-25 Time 14:52 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2023-05-11 Cont ID  
Sent By rmcphers Date 2023-05-11 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2023-05-11 Time 14:16 Sent To  
Notes
2023-05-11 14:16:28SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-06-02 Cont ID  
Sent By eschneid Date 2023-06-02 Time 16:44 Rev Time 6.00
Received By eschneid Date 2023-06-02 Time 16:44 Sent To  
Notes
2023-06-02 16:45:03FAILED
  
 1) THE STRUCTURAL SHEETS DO NOT MATCH SP200 SITE PLAN
 AND A301.5 LEVEL 1.5 OVERALL FLOOR PLAN (MINOR
 DIFFERENCES) SUBMITTED WITH THIS PERMIT NOR DO EITHER
 OF THESE PLANS MATCH THE LATEST ARCHITECTURAL PLANS
 (MAJOR DIFFERENCES) THAT HAVE BEEN SUBMITTED TO THE
 CITY AS PART OF THE FORMAL SITE PLAN REVIEW. STAFF HAS
 BEEN TOLD THAT THE STRUCTURAL SHEETS ARE THE
 CONSTRUCTION PLANS AND THAT THE ARCHITECTURAL PLANS
 WILL BE UPDATED TO MATCH THE STRUCTURAL SHEETS. STAFF
 IS UNABLE TO VERIFY THAT THE LAYOUT ON THE STRUCTURAL
 SHEETS COMPLIES WITH THE NORTHWOOD MIXED USE DISTRICT
 DEVELOPMENT REQUIREMENTS (OR THE WAIVERS TO THE
 REQUIREMENTS GRANTED BY THE APPROVED LEVEL III SPECIAL
 REVIEW) SINCE THE STRUCTURAL SHEETS DO NOT MATCH THE
 ARCHITECTURAL SETS, WHICH INCLUDE THE DATA TABLES. THE
 FORMAL SITE PLAN SUBMITTALS MUST BE UPDATED TO MATCH
 THE STRUCTURAL PLANS, PROVIDED THAT THE STRUCTURAL
 PLANS MET THE NMUD REQUIREMENTS. YOU MUST PROVIDE DATA
 TABLES THAT REFLECT CHANGES TO THE FOLLOWING AREAS OF
 THE PLANS AND VERIFY THAT THESE CHANGES COMPLY WITH THE
 NMUD REQUIREMENTS (OR THE APPROVED VARIANCES):
  
 A. TOWER FLOOR PLATES
 B. ACTIVE USE CALCULATIONS
 C. FENESTRATION CALCULATIONS
 D. PLANAR BREAK CALCULATIONS
 E. DWELLING UNIT SIZES
 F. SETBACKS
  
 2) PLEASE EXPLAIN HOW THE GROUND LEVEL OF BUILDING A
 ADDS 10,525 SQUARE FEET TO THE PREVIOUSLY REVIEWED
 ARCHITECTURAL PLANS. THIS NET INCREASE DOES NOT APPEAR
 TO BE A CONVERSION OF ONE USE (EX RETAIL OR LOBBY) TO
 ANOTHER, BUT RATHER NEW SQUARE FOOTAGE. IT IS NOT
 OBVIOUS WHERE THIS INCREASE OCCURS SINCE THE OUTER
 WALLS DO NOT APPEAR TO HAVE SHIFTED AND HOW THIS
 AFFECTS THE ACTIVE USE, FENESTRATION, ETC. CALCULATIONS
 REQUIRED BY COMMENT NUMBER 1.
  
 3) PLEASE EXPLAIN WHY/HOW/WHERE THE BUILDING C TOTAL
 SQUARE FOOTAGE INCREASE OCCURS BASED ON THE PREVIOUSLY
 REVIEWED ARCHITECTURAL PLANS. THE DATA TABLE SHOWS 50
 SQUARE FEET ON THE GROUND FLOOR, BUT IT IS NOT CLEAR
 WHERE THIS OCCURS AND HOW THIS AFFECTS THE ACTIVE USE,
 FENESTRATION, ETC. CALCULATIONS REQUIRED BY COMMENT
 NUMBER 1.
  
 4) THE PARKING LAYOUT ON LEVELS 1.5 AND 2 HAVE CHANGED
 FROM THE PREVIOUSLY REVIEWED ARCHITECTURAL PLANS. THE
 PLANS UPLOADED WITH THE FOUNDATION/SHELL PERMIT DO NOT
 INCLUDE DIMENSIONS FOR THE PARKING SPACES, DRIVE
 AISLES, AND DISTANCE BETWEEN THE PARKING SPACES AND
 WALLS (MINIMUM ONE FOOT REQUIRED FOR DOOR SWING). ONCE
 THE DIMENSIONS ARE PROVIDED, STAFF CAN DETERMINE IF AND
 ADDITIONAL PARKING SPACES NEED TO BE DESIGNATED AS
 COMPACT SPACES. ADDITIONALLY, THE PARKING TABLES THAT
 WERE PREVIOUSLY INCLUDED ON THE A103 PARKING SPACE
 CALCULATION SHEETS NEED TO BE UPDATED AND INCLUDED SO
 THAT STAFF CAN VERIFY THERE IS SUFFICIENT PARKING BASED
 ON THE REVISED PARKING LAYOUT.
  
 5) THE BICYCLE STORAGE ROOMS HAVE CHANGED FROM THE
 PREVIOUSLY REVIEWED ARCHITECTURAL PLANS AND THERE IS NO
 INFORMATION PROVIDED FOR STAFF TO VERIFY COMPLIANCE
 WITH THE NMUD REQUIREMENTS. ADDITIONALLY, IT APPEARS
 THAT THE SHOWER AND CHANGING FACILITY HAS BEEN REMOVED,
 WHICH IS NOT PERMITTED.
  
 6) SP200 AND 300 PROVIDED WITH THE FOUNDATION PERMIT DO
 NOT ACCURATELY REFLECT THE MOST RECENT PARKING LAYOUT
 ALONG NEW PINEWOOD, BROADWAY AVENUE OR BROADWAY
 EXTENSION.
  
 7) THE PARKING TABLE INCLUDES THE PARKING SPACES WITHIN
 THE FDOT PORTION OF BROADWAY AS PROVIDED PARKING;
 HOWEVER, FDOT SPECIFICALLY PROHIBITED THIS IN THEIR
 PREDETERMINATION LETTER. THESE SPACES MUST BE REMOVED
 FROM THE PARKING TABLE.
  
 8) THE NEW PLANS SHOW STORAGE AREAS ON THE GARAGE
 LEVELS. PLEASE EXPLAIN WHO USES THESE STORAGE AREAS.
 PLEASE NOTE THAT ANY THAT ARE FOR A NON-RESIDENTIAL
 USER ARE CONSIDERED AS PART OF THE COMMERCIAL SQUARE
 FOOTAGE FOR THE PROJECT AND THUS WOULD NEED TO BE
 FACTORED INTO THE PARKING CALCULATIONS.
  
 9) SOUTH ELEVATION WIND PRESSURES DRAWING FOR BUILDING
 A SHOWS THE WESTERNMOST BANK OF WINDOWS INCORRECTLY.
 THEY START/END ONE FLOOR/PARAPET TO HIGH.
  
 10) THE PLANS SHALL CLEARLY SHOW THE SETBACK DIMENSIONS
 FROM THE BUILDING WALL TO THE PROPERTY LINE.
  
 11) ADDITIONAL COMMENTS MAY BE ISSUED WHEN CONSISTENT,
 ACCURATE PLANS ARE SUPPLIED.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By ESchneid Date 2023-04-04 Time 14:53 Rev Time 0.25
Received By eschneid Date 2023-04-04 Time 14:52 Sent To  
Notes
2023-04-04 14:58:55FAILED
  
 1) THE FORMAL SITE PLAN FOR THIS PROJECT HAS NOT BEEN
 APPROVED. ZONING WILL NOT APPROVE THIS PERMIT UNTIL THE
 SITE PLAN IS APPROVED.
  
 2) ZONING HAS IDENTIFIED THAT THE PLANS SUBMITTED WITH
 THE PERMIT DO NOT MATCH THE LATEST SET OF PLANS
 REVIEWED BY STAFF AS PART OF THE SITE PLAN REVIEW. THE
 PERMIT PLANS MUST BE INTERNALLY CONSISTENT AS WELL AS
 MATCH THE APPROVED SITE PLAN SET.
  
 3) ZONING WILL NOT DO A REVIEW UNTIL PLANS THAT MATCH
 THE APPROVED SITE PLAN ARE SUBMITTED.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]