Plan Review Details - Permit 22110492
Plan Review Stops For Permit 22110492
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-11-19 Cont ID  
Sent By cpuell Date 2022-11-19 Time 08:41 Rev Time 0.00
Received By cpuell Date 2022-11-19 Time 08:41 Sent To  
Notes
2022-11-19 08:41:28ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-12-06 Cont ID  
Sent By pvalenti Date 2022-12-06 Time 14:04 Rev Time 0.00
Received By pvalenti Date 2022-12-06 Time 14:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-05 Cont ID  
Sent By pvalenti Date 2023-01-05 Time 07:40 Rev Time 0.00
Received By pvalenti Date 2023-01-05 Time 07:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-20 Cont ID  
Sent By pvalenti Date 2022-12-20 Time 11:30 Rev Time 0.00
Received By pvalenti Date 2022-12-20 Time 11:23 Sent To  
Notes
2022-12-20 11:35:22PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 3. WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 IT APPEARS THAT FOR THE WATERING DOWN METHOD, YOUR
 INTENTION IS TO USE THE NEIGHBORS WATER. IN USING THE
 NEIGHBORS WATER, YOU STILL WILL NEED TO HAVE A BACKFLOW
 PREVENTER DEVICE PERMIT AND APPROVED FINAL INSPECTION
 BY THE CITY OF WPB BUILDING(PLUMBING) DEPARTMENT AND
 THE PUBLIC UTILITIES DEPARTMENT.
  
 IF THERE IS AN EXISTING BACKFLOW PREVENTER DEVICE, A
 CURRENT/UP TO DATE CERTIFICATION OF THE DEVICE WILL BE
 REQUIRED FROM A STATE LICENSED CONTRACTOR WHO IS
 LICENSED FOR BACKFLOW DEVICE CERTIFICATION. THAT
 CERTIFICATION OF THE DEVICE WILL HAVE TO BE APPROVED BY
 THE WPB PUBLIC UTILITIES DEPARTMENT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-06 Cont ID  
Sent By pvalenti Date 2022-12-06 Time 14:05 Rev Time 0.00
Received By pvalenti Date 2022-12-06 Time 14:05 Sent To  
Notes
2022-12-06 14:08:09THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
  
 3. WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED,
 FBC 107.
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2022-12-13 Cont ID  
Sent By rrossano Date 2022-12-13 Time   Rev Time 0.00
Received By rrossano Date 2022-12-13 Time   Sent To  
Notes
2022-12-13 14:44:22PASSED WITH PROVISO: THERE ARE WATER AND SEWER LINES IN
 THE VICINITY OF THIS PROJECT. PER CHAPTER 556 OF THE
 FLORIDA STATE STATUTES, YOU MUST CALL 811 FOR UTILITY
 LOCATES AT LEAST TWO FULL BUSINESS DAYS IN ADVANCE OF
 ANY CONSTRUCTION OR DEMOLITION WORK. INFORMATION CAN BE
 FOUND HERE: HTTP://WWW.SUNSHINE811.COM/
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-11-21 Cont ID  
Sent By rrossano Date 2022-11-21 Time   Rev Time  
Received By rrossano Date 2022-11-21 Time   Sent To  
Notes
2022-11-21 10:59:16SHOW WATER SOURCE FOR DEMO.
 PROVIDE SWPPP SHOWING SILT FENCE.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By fmittner Date 2022-11-21 Time 16:03 Rev Time 0.00
Received By fmittner Date 2022-11-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-05 Cont ID  
Sent By pvalenti Date 2023-01-05 Time 07:40 Rev Time 0.00
Received By pvalenti Date 2023-01-04 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-03 Cont ID  
Sent By aoliver Date 2023-01-03 Time 09:46 Rev Time 0.00
Received By aoliver Date 2022-12-07 Time 06:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-06 Cont ID  
Sent By pvalenti Date 2022-12-06 Time 14:08 Rev Time 0.00
Received By pvalenti Date 2022-11-18 Time 06:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-12-06 Cont ID  
Sent By pvalenti Date 2022-12-06 Time 14:08 Rev Time 0.00
Received By pvalenti Date 2022-12-06 Time 14:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-12-30 Cont ID  
Sent By fmittner Date 2022-12-30 Time 10:55 Rev Time 0.00
Received By fmittner Date 2022-12-30 Time 10:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By fmittner Date 2022-11-21 Time 16:03 Rev Time 0.00
Received By fmittner Date 2022-11-21 Time 16:03 Sent To  
Notes
***NONE***