| Plan Review Stops For Permit 22110486 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2023-02-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-02-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-02-07 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2023-01-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-01-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-01-17 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2023-01-17 10:05:19 | THERE DOES NOT APPEAR TO BE ANY NEW DOCUMENTS NOR | | | INFORMATION PROVIDED THAT ADDRESS THE PERVIOUS FIRE | | | COMMENTS. | | | | | | THE PREVIOUS FIRE COMMENTS ARE RESUBMITTED BELOW. | | | | | | PLEASE ADDRESS AS APPLICABLE. | | | | | | ******************************************************* | | | ******************************************************* | | | ************************** | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS A SITE PLAN PROVIDED. HOWEVER, THIS IS NO | | | SPECIFIC LOCATION INDICATED FOR THE PROPOSED DDCV. | | | | | | THE LOCATION IS REQUIRED TO COMPLY WITH NFPA 24. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A HIGHLIGHTED | | | LOCATION FOR THE PROPOSED DDCV. | | | | | | | | | 1A) IS THIS PROPOSED DDCV FOR A FIRE LINE OR DOMESTIC | | | LINE, OR IS IT FOR BOTH? | | | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | | 1B) THERE ARE NO MANUFACTURES SPECIFICATION SHEETS FOR | | | THE PROPOSED DDCV THAT INDICATES COMPLIANCE WITH NFPA. | | | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-01-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-01-11 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2023-01-11 11:17:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS A SITE PLAN PROVIDED. HOWEVER, THIS IS NO | | | SPECIFIC LOCATION INDICATED FOR THE PROPOSED DDCV. | | | | | | THE LOCATION IS REQUIRED TO COMPLY WITH NFPA 24. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A HIGHLIGHTED | | | LOCATION FOR THE PROPOSED DDCV. | | | | | | | | | 1A) IS THIS PROPOSED DDCV FOR A FIRE LINE OR DOMESTIC | | | LINE, OR IS IT FOR BOTH? | | | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | | 1B) THERE ARE NO MANUFACTURES SPECIFICATION SHEETS FOR | | | THE PROPOSED DDCV THAT INDICATES COMPLIANCE WITH NFPA. | | | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-02-08 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-08 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-02-06 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-01-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-01-20 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-10 |
Time |
09:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-02-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-07 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-07 |
Time |
09:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-01-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-12 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-12 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2023-01-12 11:07:21 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22110486 | | | 1/12/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE APPLICATION IS FOR A DCDA BACKFLOW PREVENTER | | | ASSEMBLY APPARENTLY FOR THE FIRE LINE. PLEASE NOTE | | | SUBMITTED PLAN SHEET C6.01 CALLS OUT AN 8-INCH VERTICAL | | | ASSEMBLY PLEASE SUBMIT A SPEC SHEET FOR THE DCDA WITH | | | APPROVAL STAMP BY THE DESIGN PROFESSIONAL OF RECORD- | | | SEC. 107.2.1 WPB. | | | | | | 2) THE SUBMITTED CIVIL PLAN SHEETS IN THE SIGNATURE | | | FILE ARE NOT DIGITALLY SIGNED AND SEALED BY THE | | | ENGINEER OF RECORD- FL. STATUTE 471.025, AND SECTION | | | 61G15-23.005 FAC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
N |
Date |
2022-11-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-11-19 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-11-19 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2022-11-19 09:46:36 | CITY PLAN REVIEW, CITY INSPECTIONS | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
2 |
Status |
P |
Date |
2023-02-08 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-08 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-02-08 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2023-02-08 10:22:29 | APPROVED BY RONALD JENKINS |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
2023-01-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-01-20 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-20 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2023-01-20 08:29:30 | PER RJENKINS - NO SPECS PROVIDED. |
|
|