Plan Review Details - Permit 22110486
Plan Review Stops For Permit 22110486
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-02-07 Cont ID  
Sent By pleduc Date 2023-02-07 Time   Rev Time 0.00
Received By pleduc Date 2023-02-07 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2023-01-17 Cont ID  
Sent By pleduc Date 2023-01-17 Time   Rev Time 0.00
Received By pleduc Date 2023-01-17 Time 10:02 Sent To  
Notes
2023-01-17 10:05:19THERE DOES NOT APPEAR TO BE ANY NEW DOCUMENTS NOR
 INFORMATION PROVIDED THAT ADDRESS THE PERVIOUS FIRE
 COMMENTS.
  
 THE PREVIOUS FIRE COMMENTS ARE RESUBMITTED BELOW.
  
 PLEASE ADDRESS AS APPLICABLE.
  
 *******************************************************
 *******************************************************
 **************************
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS A SITE PLAN PROVIDED. HOWEVER, THIS IS NO
 SPECIFIC LOCATION INDICATED FOR THE PROPOSED DDCV.
  
 THE LOCATION IS REQUIRED TO COMPLY WITH NFPA 24.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A HIGHLIGHTED
 LOCATION FOR THE PROPOSED DDCV.
  
  
 1A) IS THIS PROPOSED DDCV FOR A FIRE LINE OR DOMESTIC
 LINE, OR IS IT FOR BOTH?
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
 1B) THERE ARE NO MANUFACTURES SPECIFICATION SHEETS FOR
 THE PROPOSED DDCV THAT INDICATES COMPLIANCE WITH NFPA.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-01-11 Cont ID  
Sent By pleduc Date 2023-01-11 Time   Rev Time 0.00
Received By pleduc Date 2023-01-11 Time 11:08 Sent To  
Notes
2023-01-11 11:17:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS A SITE PLAN PROVIDED. HOWEVER, THIS IS NO
 SPECIFIC LOCATION INDICATED FOR THE PROPOSED DDCV.
  
 THE LOCATION IS REQUIRED TO COMPLY WITH NFPA 24.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A HIGHLIGHTED
 LOCATION FOR THE PROPOSED DDCV.
  
  
 1A) IS THIS PROPOSED DDCV FOR A FIRE LINE OR DOMESTIC
 LINE, OR IS IT FOR BOTH?
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
 1B) THERE ARE NO MANUFACTURES SPECIFICATION SHEETS FOR
 THE PROPOSED DDCV THAT INDICATES COMPLIANCE WITH NFPA.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-08 Cont ID  
Sent By aoliver Date 2023-02-08 Time 10:22 Rev Time 0.00
Received By aoliver Date 2023-02-06 Time 11:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-20 Cont ID  
Sent By lmarchan Date 2023-01-20 Time 08:29 Rev Time 0.00
Received By lmarchan Date 2023-01-10 Time 09:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-02-07 Cont ID  
Sent By ccole Date 2023-02-07 Time 10:46 Rev Time 0.00
Received By ccole Date 2023-02-07 Time 09:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-12 Cont ID  
Sent By ccole Date 2023-01-12 Time 11:06 Rev Time 0.00
Received By ccole Date 2023-01-12 Time 10:20 Sent To  
Notes
2023-01-12 11:07:211ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22110486
 1/12/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPLICATION IS FOR A DCDA BACKFLOW PREVENTER
 ASSEMBLY APPARENTLY FOR THE FIRE LINE. PLEASE NOTE
 SUBMITTED PLAN SHEET C6.01 CALLS OUT AN 8-INCH VERTICAL
 ASSEMBLY PLEASE SUBMIT A SPEC SHEET FOR THE DCDA WITH
 APPROVAL STAMP BY THE DESIGN PROFESSIONAL OF RECORD-
 SEC. 107.2.1 WPB.
  
 2) THE SUBMITTED CIVIL PLAN SHEETS IN THE SIGNATURE
 FILE ARE NOT DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER OF RECORD- FL. STATUTE 471.025, AND SECTION
 61G15-23.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status N Date 2022-11-19 Cont ID  
Sent By shill Date 2022-11-19 Time 09:46 Rev Time 0.00
Received By shill Date 2022-11-19 Time 09:46 Sent To  
Notes
2022-11-19 09:46:36CITY PLAN REVIEW, CITY INSPECTIONS
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 2023-02-08 Cont ID  
Sent By aoliver Date 2023-02-08 Time 10:22 Rev Time 0.00
Received By aoliver Date 2023-02-08 Time 10:22 Sent To  
Notes
2023-02-08 10:22:29APPROVED BY RONALD JENKINS

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 2023-01-20 Cont ID  
Sent By lmarchan Date 2023-01-20 Time 08:29 Rev Time 0.00
Received By lmarchan Date 2023-01-20 Time 08:29 Sent To  
Notes
2023-01-20 08:29:30PER RJENKINS - NO SPECS PROVIDED.