| Plan Review Stops For Permit 22110439 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2023-01-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-01-03 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2023-01-03 |
Time |
18:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-01-18 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-01-18 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-01-18 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-01-10 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-01-10 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2023-01-10 14:20:23 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. | | | NEC 220. | | | NOTE: - DRAWINGS SHOW ON PAGE 2 OF 3 SECTION POOL | | | EQUIPMENT SCHEDULE LISTING AS PART OF THE EQUIPMET A | | | POOL HEATER GULFSTREAM HI150-R-A. | | | BY THE SPECS MINIMUM CIRCUIT AMPACITY 40, MAIN TIME | | | DELAY BREAKER 50 AMPS, AVERAGE RUNNING AMPS 32.8. | | | - DRAWINGS SHOW ON PAGE 3 OF 3 SECTION ELECTRIC RISER A | | | PROPOSED POOL PANEL WITH A 2P30 BREAKER FOR ELECTRIC | | | HEATER. | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-11-29 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2022-11-29 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2022-11-29 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2022-11-29 14:55:26 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | | | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. | | | NEC 215.2, 220, 408.30 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-01-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-27 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-01-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-13 |
Time |
09:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-01-11 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-01-04 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-01-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-01-03 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-11-23 |
Time |
09:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-30 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-30 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-19 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-19 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2023-01-19 09:08:42 | 2ND REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22110439 | | | 1/18/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE RESUBMITTED S2 PLAN SHEET DOES NOT HAVE A | | | VERIFIABLE DIGTAL SIGNATURE AND SEAL BY THE ENGINEER OF | | | RECORD AS REQUIRED BY FL. STATUTE 471.025, AND SECTION | | | 61G15-23.005 FAC. THE PLAN APPEARS TO BE A SCANNED COPY | | | OF THE ORIGINAL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-09 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-09 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-12-02 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-12-02 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2022-12-02 10:50:06 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22110439 | | | 12/2/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET 2: REFER TO SEC. R4501.6 FBC RES AND PROVIDE | | | NOTES ON THE PLAN INDICATING THE POOL DESIGN, | | | CONSTRUCTION AND WORKMANSHIP SHALL BE IN CONFORMITY | | | WITH THE REQUIREMENTS OF ANSI/APSP/ICC3; ANSI/APSP/ICC | | | 4; ANSI/ APSP/ICC 5; ANSI/APSP/ICC 6; AND ANSI/APSP/ICC | | | 7. | | | | | | 2) SHEET 2: PROVIDE AN EQUIPMENT SCHEDULE LISTING THE | | | MAKES AND MODELS OF THE PUMP, FILTER, CHLORINATOR, POOL | | | HEATER, AND THE MAIN DRAIN ASSEMBLIES- SEC. R4501.6.2 | | | FBC RES. THE PLAN DOES NOT INDICATE ELECTRIC HEAT PUMP | | | OR GAS-FIRED POOL HEATER. PLEASE NOTE GAS POOL HEATERS | | | SHALL BE INSTALLED UNDER A SEPARATE PERMIT- SEC. 105.1 | | | & 107.2.1 WPB. | | | | | | 3) SHEET 2: THE 285 SQUARE FOOTAGE CALCULATION FOR THE | | | MAIN POOL APPEARS INCORRECT BASED ON THE DIMENSIONS | | | SHOWN ON THE PLAN, AND ALSO DOES NOT ACCOUNT FOR THE | | | SQUARE FOOTAGE OF THE SPA THAT IS DRAINING IN TO THE | | | POOL- SEC. R4501.6.1 & R4501.7.2 FBC RES. | | | | | | 4) SHEET 2: THE 4-INCH SUCTION LINES FROM THE SPA TO | | | THE POOL INCLUDING THE FLOW VELOCITIES OF THE PIPES ARE | | | NOT ACCOUNTED FOR IN THE TDH CALCULATIONS- SEC. 4.4.9 | | | ANSI/APSP/ICC-7. | | | | | | A) WHAT TYPE OF TERMINATION FITTING WILL BE USED FOR | | | THE 4-INCH LINES AT THE POOL WALL- R4501.21.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-30 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-30 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-19 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-19 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2023-01-19 09:09:34 | DIGITAL SIGNATURE REVIEW | | | PERMIT- 22110439 | | | 1/18/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE RESUBMITTED S2 PLAN SHEET DOES NOT HAVE A | | | VERIFIABLE DIGTAL SIGNATURE AND SEAL BY THE ENGINEER OF | | | RECORD AS REQUIRED BY FL. STATUTE 471.025, AND SECTION | | | 61G15-23.005 FAC. THE PLAN APPEARS TO BE A SCANNED COPY | | | OF THE ORIGINAL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-09 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-09 |
Time |
09:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-12-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-12-02 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-12-02 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-12-07 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-12-07 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-12-07 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|