| 2023-01-11 11:49:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS A SITE PLAN PROVIDED. HOWEVER, THIS IS NO |
| | SPECIFIC LOCATION INDICATED FOR THE PROPOSED FIRE LINE. |
| | |
| | FOR THE OFFICIAL RECORD AND CLARIFICATIONS, PLEASE |
| | PROVIDE A HIGHLIGHTED LOCATION FOR THE PROPOSED FIRE |
| | LINE. |
| | |
| | |
| | 1A) THERE ARE NO INDICATIONS OF COMPLIANCE WITH NFPA |
| | 24. |
| | |
| | THE PROPOSED SHALL BE INSTALLED, INSPECTED AND TESTED |
| | PER NFPA AND MANUFACTURES SPECIFICATIONS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE |
| | OF ACKNOWLEDGMENT ON THE PLAN SHEETS. |
| | |
| | |
| | 1B) THERE ARE NO MANUFACTURES SPECIFICATION SHEETS FOR |
| | THE PROPOSED FIRE LINE THAT INDICATES COMPLIANCE WITH |
| | NFPA. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS. |
| | |
| | |
| | 1C) ENSURE THE APPLICABLE JOINT RESTRAINTS ARE |
| | INSTALLED AND TORQUED PER MANUFACTURES SPECS AND JOINTS |
| | SHALL NOT BE COVERED OVER PRIOR TO FIRE INSPECTION. |
| | |
| | A TORQUE WRENCH SHALL BE ON SITE WITH THE INSTALLING |
| | CONTRACTOR FOR CONFIRMATION AND VERIFICATION AT THE |
| | TIME OF FIRE INSPECTION. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE |
| | OF ACKNOWLEDGMENT ON THE PLAN SHEETS. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |