Plan Review Details - Permit 22110427
Plan Review Stops For Permit 22110427
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-11-19 Cont ID  
Sent By cpuell Date 2022-11-19 Time 09:12 Rev Time 0.00
Received By cpuell Date 2022-11-19 Time 09:12 Sent To  
Notes
2022-11-19 09:12:37ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-01-18 Cont ID  
Sent By lmarchan Date 2023-01-18 Time 11:01 Rev Time 0.00
Received By lmarchan Date 2023-01-18 Time 11:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 06:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-17 06:56:13COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By jwitmer Date 2022-12-14 Time 08:24 Rev Time 0.00
Received By jwitmer Date 2022-12-13 Time 16:29 Sent To  
Notes
2022-12-14 08:24:10TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 06:54 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-17 06:54:44PROVISO: REVISION REQUIRED.
 AUTTOMATIC & POWER ASSISTED DOOR TO SHOW
 LOCATION OF PUSH BUTTON WALL SWITCHES IN
 AN ACCESSIBLE LOCATION FOR BOTH THE EXTERIOR
 AND INTERIOR LOCATIONS BEFORE ROUGH INSPECTIONS.
 J WITMER PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By jwitmer Date 2022-12-14 Time 09:52 Rev Time 0.00
Received By jwitmer Date 2022-12-13 Time 16:29 Sent To  
Notes
2022-12-14 09:52:34WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110427
 ADD: 931 VILLAGE BLVD # 904
 CONT: LANDMARK CONTRACTING
 TEL: 407-264-0100
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 14/2022
 ACTION: DENIED
 1) SHEET A-1 FLOOR & CEILING PLAN:
  
 1A) FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS ($80,000.00 X 0.20=
 $16,000.00 DOLLARS) LISTED FOR EACH ELEMENT WHERE THE
 FUNDS ARE BEING SPENT AND IN THE ORDER LISTED IN
 SECTION 202.4.1 DISPROPORTIONATE COST OF THE 2020
 ACCESSIBILITY CODE.
  
 1B) FRONT ENTRY MAYBE EXISTING BUT IS NOT ACCESSIBLE.
 THE FIRST ITEM ON THE DISPROPORTIONATE COST LIST IS AN
 ACCESSIBLE ENTRANCE. 202.4.1. DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COST THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COST ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUT TO THE
 ALTERED AREA; (II) COST ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS ENLARGING DOOR OPENINGS,
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 1C) PLEAS REVIEW IN THE 2020FBC-ACCESSIBILITY CODE
 SECTIONS 404.3 AUTOMATIC AND POWER-ASSISTED DOORS AND
 404.3.2. NOTE STANDBY POWER WILL NEED TO OCCUR OR
 OTHERWISE COMPLY WITH 404.2.4 MANEUVERING CLEARANCES.
 PLEASE ALSO REVIEW THE REQUIRED CONTROLS IN 404.3.5.
  
 1D) THE BUSINESS MANAGERS DESK MAYBE BY TENANT BUT WILL
 NEED TO MEET THE ACCESSIBILITY REQUIREMENTS FOUND IN
 SECTIONS:
 1D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1D)(2) 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE
 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 1E) THE DESK IN OFFICE # 2 , THE OFFICE AND BOOTH DOES
 NOT PROVIDE THE EIGHT OF THE DESK NOR COMPLIANCE WITH
 909.2 NOR 909.3.
  
 1F) THE BOOTH DOOR IS MISSING FROM THE DOOR SCHEDULE ON
 SHEET A-2. STATES BY MANUFACTURER. 2020 FBC-B 1010.1.1.
 SIZE OF DOORS. CLEAR WIDTH. DOOR OPENINGS SHALL PROVIDE
 A CLEAR WIDTH OF 32 INCHES MINIMUM. CLEAR OPENINGS OF
 DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN
 AT 90 DEGREES.
  
 1G) PLEASE PROVIDE THE INTERIOR FINISHED MEASUREMENTS
 OF THE BOOTH AND THE REQUIRED TURNING SPACE IN
 COMPLIANCE WITH 304.3.
  
 1H) THE BOOTH DOES NOT PROVIDE IF THERE IS A BASE
 WITHIN THE BOOTH MAKING THE BOOTH FINISH FLOOR HIGHER
 THAN THE FLOOR LEVEL OF THE TENANT SPACE. PLEASE REFER
 TO RAMPS FOUND IN SECTION 405.2 FOR SLOPE.
  
 1I) THE FLOOR PLAN DOES SHOW A DOUBLE DRINKING FOUNTAIN
 ON THE FLOOR PLAN. SHEET A003 ONLY SHOWS THE LOW
 DRINKING FOUNTAIN DETAIL (WHEELCHAIR), IT DOES NOT SHOW
 THE HEIGHT FOR THE STANDING PERSON IN COMPLIANCE WITH
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 1J) THE ACCESSIBLE RESTROOM ON SHEET A-1 NOR SHEET A-2
 NEITHER SHOW 30 X 48 INCH CLEAR FLOOR SPACE BEYOND THE
 ARC OF THE INSWING DOOR. PLEASE REVIEW 603.2.3 AND
 EXCEPTION 2. WHERE TOILET ROOMS ARE FOR INDIVIDUAL USE
 AND A CLEAR FLOORS SPACE COMPLYING WITH 305.3 IS
 PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR
 SWING. WHAT IS MISSING IS THE REQUIRED 30X48 INCH CLEAR
 FLOOR SPACE BEYOND THE ARC OF THE DOOR. USUALLY AT A
 45% ANGLE TO THE DOOR ENTRANCE.
  
 2) SHEET A2 RESTROOM ELEVATIONS DOES NOT SHOW THE
 FINISH WALL MATERIAL. 2020 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS,
 RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 2A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2B) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER???S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM (MR BOARD) SHALL NOT BE USED FOR
 SHOWER & TUB ENCLOSURES BUT CAN BE USED FOR BACKING
 BOARD FOR A BASE FOR TILE IN WATER CLOSET COMPARTMENT
 WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840 AND THE MANUFACTURE???S RECOMMENDATIONS.
  
 3) SHEET A-2 SHOWS A DETAIL FOR A PRODUCT SPECIFICATION
 DRAWING FOR QUICK STAND #30 SWHP-WM WALL MOUNTED
 EQUIPMENT PLATFORM BUT DOES NOT PROVIDE WHAT TYPE OF
 WALL IS TO SUPPORT THIS UNIT NOR THE ANCHORS TO SUPPORT
 THE 30-GALLON FILLED WATER HEATER AND STAND. INTERIOR
 NON-LOAD BEARING METAL STUDS SEE SECTION 1607.14.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-11 Cont ID  
Sent By mpeterso Date 2023-01-11 Time 14:58 Rev Time 0.00
Received By mpeterso Date 2023-01-11 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-06 Cont ID  
Sent By mpeterso Date 2022-12-06 Time 11:56 Rev Time 0.00
Received By mpeterso Date 2022-12-06 Time 11:48 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-03-27 Cont ID  
Sent By jleahy Date 2023-03-27 Time 11:26 Rev Time 0.00
Received By jleahy Date 2023-03-27 Time 11:26 Sent To  
Notes
2023-03-27 11:27:05VOICE AND DATA PER PLANS JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-09 Cont ID  
Sent By cwalker Date 2023-01-09 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-01-09 09:52:12FIRE PROVISO COMMENTS:
  
 (1) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION. ANY IMPAIRMENT TO ANY LIFE
 SAFETY SYSTEM IN EXCESS OF 4 CONTINUOUS HOURS IN
 DURATION WILL REQUIRE THE IMPLEMENTATION OF A FIRE
 WATCH.
  
 (2) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE PROTECTED FROM DAMAGE INCLUDE PAINTING
 DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION.
  
  
 (3) ANY AND ALL WORK ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-11-16 Cont ID  
Sent By cwalker Date 2022-11-16 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-11-16 11:01:54FIRE PROVISO COMMENTS:
  
 (1) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION. ANY IMPAIRMENT TO ANY LIFE
 SAFETY SYSTEM IN EXCESS OF 4 CONTINUOUS HOURS WILL
 REQUIRE THE IMPLEMENTATION OF A FIRE WATCH.
  
 (2) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE PROTECTED FROM DAMAGE INCLUDING
 PAINTING DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
  
 (3) ANY AND ALL WORK ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-18 Cont ID  
Sent By jesmith Date 2023-01-18 Time 08:31 Rev Time 0.00
Received By jesmith Date 2023-01-18 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-12-14 Time   Rev Time 0.00
Received By cdecoeur Date 2022-11-15 Time 10:10 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-12-13 Cont ID  
Sent By jwitmer Date 2022-12-13 Time 16:29 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 14:08 Rev Time 0.00
Received By medwards Date 2023-01-11 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-23 Cont ID  
Sent By medwards Date 2022-11-23 Time 06:02 Rev Time 0.00
Received By medwards Date 2022-11-23 Time 06:02 Sent To  
Notes
2022-11-23 06:02:451ST REVIEW FMC
 PERMIT: 22110427
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENERGY CALCULATIONS- PAGE 2 OF 24: THE ADDRESS OF
 THIS PROJECT IS 2140 58TH AVENUE VERO BEACH. OUR
 RECORDS INDICATE THE ADDRESS IS 931 VILLAGE BLVD. UNIT
 904. PLEASE SUBMIT THE ENERGY CALCULATIONS AND
 MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THIS
 PROJECT. FBC 107.3.5
  
 2) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH
 USE OF SPACE IN THIS TENANT SPACE. FMC 403.3.1.1
  
 3) THE BATH EXHAUST FANS ARE CONTROLLED BY A SWITCH ON
 THE WALL. PLEASE SHOW THE REQUIRED 70 CFM???S OF
 EXHAUST PER WATER CLOSET. FMC TABLE 403.3.1.1 FOOTNOTE
 E
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-01-18 Cont ID  
Sent By jesmith Date 2023-01-18 Time 08:28 Rev Time 0.00
Received By jesmith Date 2023-01-18 Time 08:04 Sent To  
Notes
2023-01-18 08:14:2922110427 931 VILLAGE BLVD # 904
  
 PLUMBING COMMENTS: REVIEWED FOR COMPLIANCE IN
 ACCORDANCE WITH WPB FBC 107.3.5.1.3
  
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO: PROVIDE A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1017 AT THE WATER HEATER. FPC
 607.1.1, 613.1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By jesmith Date 2022-11-16 Time 13:57 Rev Time 0.00
Received By jesmith Date 2022-11-16 Time 09:12 Sent To  
Notes
2022-11-16 13:48:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22110427 931 VILLAGE BLVD # 904
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
  
 1. A003-A2/TYPICAL RESTROOM PLAN: SPACE BETWEEN SIDE
 WALL AND REAR GRAB BAR AT WATER CLOSET SHALL BE 6
 INCHES, NOT 8 INCHES. FBC ACC 604.5.2
  
 2. A003-A2/ACCESSIBILITY NOTE 7: PER FBC ACC 606.5,
 AMEND NOTE TO READ "WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT PER FBC
 ACCESSIBILITY CODE 606.5".
  
 3. A003-A2: FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
  
 4. A003-A2: PLEASE INDICATE THE DIMENSION IS TO THE
 BOTTOM EDGE OF THE "REFLECTING" SURFACE OF THE BATHROOM
 MIRROR. FBC ACC 603.3
  
 5. DRINKING FOUNTAIN: PLEASE PROVIDE ELEVATION DETAIL
 OF DRINKING FOUNTAIN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 ***A) FBC ACC 306 KNEE AND TOE CLEARANCE
 ***B) FBC ACC 602.4 SPOUT HEIGHT
 ***C) FBC ACC 602.5 SPOUT LOCATION
 ***D) FBC ACC 602.7 SPOUT HEIGHT FOR STANDING PERSONS
  
 6. DRINKING FOUNTAIN: OBJECTS WITH LEADING EDGES MORE
 THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE
 FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH. FBC ACC 307.2
 PROTRUSION LIMITS. PLEASE NOTE, THIS CAN BE CORRECTED
 BY SPECIFYING A CANE APRON FOR THE HIGHER DRINKING
 FOUNTAIN ON THE PLUMBING FIXTURE SCHEDULE
  
 7. A002-A1: PROVIDE CLEAR FLOOR SPACE FOR BREAK ROOM
 SINK. FBC ACC 606.2, 305.3, 305.5
  
 8. PER FBC 1210.2.2, FBC PL 310.3, PROVIDE A SMOOTH,
 HARD, NON-ABSORBENT WALL SURFACE TO A HEIGHT NOT LESS
 THAN 4 FEET ABOVE THE FLOOR WITHIN 2 FEET OF SERVICE
 SINK. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE
 "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS (INCLUDING EPOXY PAINT), DOES NOT
 MEET THE INTENT OF SECTION 1210.2.2. THE TYPICAL
 MATERIALS USED FOR THIS APPLICATION ARE CERAMIC TILE,
 FIBERGLASS REINFORCED PLASTIC (FRP) PANELS, PHENOLIC
 PANELS, LAMINATED PLASTIC PANELS, PAINTED STEEL AND
 STAINLESS STEEL
  
 9. P001-P1/SANITARY RISER: MAXILINE SERIES 725 SERIES
 WATER TEMP LIMITING DEVICE. IS THIS A SYMMONS
 (7-225-CK-F) MAXLINE THERMOSTATIC WATER TEMPERATURE
 LIMITING DEVICE AND ASSE 1017/1070 COMPLIANT?
 PER WPB FBC 107.2.1, PLEASE CLARIFY ON THE PLANS.
 PROVIDE DETAIL.
  
 10. WATER HEATER DETAIL:
 ***A) SPECIFY AND PROVIDE THERMAL EXPANSION CONTROL
 DEVICE IN THE COLD WATER SUPPLY BETWEEN ANY CHECK
 VALVES, BACKFLOW PREVENTERS AND PRESSURE REDUCING
 VALVES. FBC PL 607.3
 ***B) NOTE SIZES CORRECT TERMINATIONS OF T&P RELIEF
 DISCHARGE PIPE AND AUXILLARY PAN DRAIN. FBC PL 504.6,
 504.7.1, 504.7.2
  
 11. WATER HEATER IS EXISTING AND RELOCATED. PER PER WPB
 FBC 107.3.5.1.3 (5) PLEASE PROVIDE STORAGE CAPACITY AND
 ENERGY EFFICIENCY SHOWING COMPLIANCE WITH FBC EC TABLE
 C404.2.
  
 12. INSULATION SPECIFICATION FOR HOT WATER INSULATION
 COMPLY WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10.
 INSULATION THICKNESS FOR PIPES SMALLER THAN 1 INCH
 DIAMETER SHALL BE 1 INCH.
  
 13. MAXIMUM ALLOWABLE LENGTH OF 3/4 INCH HOT WATER TO
 PUBLIC LAVATORY FAUCET FROM HOT WATER SOURCE IS 1/2
 FOOT. FBC EC C404.5.1, TABLE C404.5.1.
 REGARDING MAXIMUM LENGTHS AND VOLUME OF HOT WATER FROM
 SOURCE TO OUTLET IN GENERAL, PLEASE REFER TO TABLE
 C404.5.1.
 ***A) FOR A PUBLIC LAVATORY FAUCET, USE THE ???PUBLIC
 LAVATORY FAUCETS??? COLUMN IN TABLE C404.5.1.
 ***B) FOR ALL OTHER PLUMBING FIXTURES AND PLUMBING
 APPLIANCES, USE THE ???OTHER FIXTURES AND APPLIANCES???
 COLUMN IN TABLE C404.5.1.
  
 14. PER WPB FBC 107.3.5.1.3 (2) (3) (4), PROVIDE A
 FIXTURE PLUMBING CONNECTION SCHEDULE OF ALL FIXTURES,
 NEW AND RELOCATED INDICATING FIXTURE DRAIN CONNECTION
 SIZE, DFU, WATER CONNECTION SIZE(S) HOT & COLD, WATER
 FLOW RATE/FLUSHING CYCLE. FBC PL TABLE 604.4, TABLE
 709.1
  
 15. PROVIDE MATERIAL SPECIFICATION, SIZE, ROUTING AND
 TERMINATION OF A/C CONDENSATE DRAIN FOR AIR HANDLER
 UNIT AS WELL AS INSULATION SPECIFICATION. FBC PL 314.2,
 314.2.1, 314.2.2, TABLE 314.2.2, FBC EC TABLE 403.2.10
 ***A) PLEASE NOTE, PER WPB CODE OF ORDINANCE CHAPTER
 90, ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE
 (INTERPRET THIS AS ANY CONDENSATION FROM EVAPORATOR
 COILS) SHALL NOT DISCHARGE TO THE CITY UTILITIES
 SANITARY SEWAGE INFRASTRUCTURE WITHOUT PERMISSION FROM
 THE UTILITIES DEPARTMENT. YOU MAY CONTACT MR. RICK
 ROSSANO IN ENGINEERING AT 561-494-1098 FOR ADDITIONAL
 INFORMATION. MOVING FORWARD, DISCHARGE THE CONDENSATE
 TO AN EXTERIOR DRYWELL; PER WPB FBC 107.2.1, PROVIDE
 ROUTING AND DRYWELL DETAIL.
  
 16. P001-P1/PLUMBING FIXTURE SCHEDULE-MOP SINK: FAUCET
 WITH HOSE END SHALL BE PROVIDED WITH A VACUUM BREAKER.
 FBC PL 608.1
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ALL PLANS TO BE SIGNED AND SEALED BY
 THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-11 Cont ID  
Sent By mpeterso Date 2023-01-11 Time 15:00 Rev Time 0.00
Received By mpeterso Date 2023-01-11 Time 15:00 Sent To  
Notes
2023-01-11 15:00:43ALL PLANS PASSED SIGNATURE REVIEW
2023-01-11 14:08:56DIGITAL MECHANICAL SIGNATURES APPROVED ME
  
2023-01-11 10:19:25ELECTRONIC SIGNATURES FOR PLUMBING PLANS ARE VALID. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-23 Cont ID  
Sent By medwards Date 2022-11-23 Time 06:03 Rev Time 0.00
Received By medwards Date 2022-11-23 Time 06:03 Sent To  
Notes
2022-11-16 09:15:21ELECTRONIC SIGNATURES FOR PLUMBING ARE APPROVED. JS

Review Stop Z ZONING
Rev No 1 Status P Date 2022-12-01 Cont ID  
Sent By vbroglia Date 2022-12-01 Time 13:32 Rev Time 0.00
Received By vbroglia Date 2022-12-01 Time 13:32 Sent To  
Notes
***NONE***