Plan Review Details - Permit 22110423
Plan Review Stops For Permit 22110423
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-02-28 Cont ID  
Sent By jwitmer Date 2023-02-28 Time 11:44 Rev Time 0.00
Received By jwitmer Date 2023-02-28 Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-12-28 Cont ID  
Sent By jwitmer Date 2022-12-28 Time 13:02 Rev Time 0.00
Received By jwitmer Date 2022-12-28 Time 10:11 Sent To  
Notes
2022-12-28 13:02:07COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2023-05-03 Cont ID  
Sent By pvalenti Date 2023-05-03 Time 09:24 Rev Time 0.00
Received By pvalenti Date 2023-05-03 Time 09:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-04-26 Cont ID  
Sent By pvalenti Date 2023-04-26 Time 16:38 Rev Time 0.00
Received By pvalenti Date 2023-04-26 Time 14:58 Sent To  
Notes
2023-04-26 16:44:17PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE CLARIFY THE DIFFERENCE IN WIDTH
 FOR THE DRINKING FOUNTAIN NICHE. PLAN SHEETS A-1 & A-2
 INDICATE AN INSIDE MEASUREMENT BETWEEN NEW WALLS OF
 3'3" AND PLAN SHEET A-4 INDICATES THAT THERE MUST BE A
 48" DIMENSION OF THIS SPACE. PLEASE CORRECT THE
 DIFFERENCE AND RE-SUBMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-04-24 Cont ID  
Sent By shill Date 2023-04-24 Time 11:14 Rev Time 0.00
Received By shill Date 2023-04-24 Time 11:14 Sent To  
Notes
2023-04-24 11:15:10PROVISO - ISSUED AT APPLICANT'S RISK - CONFLICT WITH
 OTHER PAGES. COMPLIANCE WITH FBC ACCESSIBLITY
 PROTRUDING OBJECTS 307.2 REQUIRED (DRINKING FOUNTAIN).
 SEE PAGE A-1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-04-17 Cont ID  
Sent By jwitmer Date 2023-04-17 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2023-04-17 Time 10:14 Sent To  
Notes
2023-04-17 10:32:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110423
 ADD: 2617 N AUSTRALIAN AVE.
 CONT: MASTER CONTRACTORS
 TEL: 561-712-8898
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW.
 DATE: MON. APRIL 17TH/ 20232
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3A-3J. COMPLIED.
  
 3K) 4TH REQUEST, SEMI-COMPLIED. SHEET A-1 SHOWS THE
 RECESSED DRINKING FOUNTAINS, BUT ALL OTHER FLOOR PLANS
 WERE NOT UPDATED, DISCREPANCY IN PLANS. LIFE SAFETY,
 P-1 AND E-1.
 3RD REQUEST. DRINKING FOUNTAINS STICK OUT PAST THE WALL
 MORE THAN 4 INCHES REQUIRES WING WALLS ON BOTH SIDES OF
 THE DRINKING FOUNTAINS.
 DRINKING FOUNTAINS PROTRUDING OBJECTS 307.2 PROTRUSION
 LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 3L-3M) COMPLIED.
  
 4-5) COMPLIED.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 14:20 Sent To  
Notes
2023-04-03 14:47:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110423
 ADD: 2617 N AUSTRALIAN AVE.
 CONT: MASTER CONTRACTORS
 TEL: 561-712-8898
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. APRIL 03RD/ 20232
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) COMPLIED.
  
 1B) 3RD REQUEST, SEMI-COMPLIED. THE RESPONSE STATES NO
 ROOF WORK, I AGREE BUT YOU THE DESIGNER OF RECORD
 LISTED WORST CASE ALL OPENINGS, IF WORST CASE WOULD BE
 WALL ZONE 5 AT 10 SQ. FT. OUR TABLES CALCULATE FOR D
 EXPOSURE AT A MEAN ROOF HEIGHT OF 15 FEET, +46.0/
 -61.6.
  
 2) COMPLIED.
  
 3A-3J. COMPLIED.
  
 3K) 3RD REQUEST. DRINKING FOUNTAINS STICK OUT PAST THE
 WALL MORE THAN 4 INCHES REQUIRES WING WALLS ON BOTH
 SIDES OF THE DRINKING FOUNTAINS.
 DRINKING FOUNTAINS PROTRUDING OBJECTS 307.2 PROTRUSION
 LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 3L-3M) COMPLIED.
  
 4-5) COMPLIED.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-28 Cont ID  
Sent By jwitmer Date 2023-02-28 Time 11:46 Rev Time 0.00
Received By jwitmer Date 2023-02-28 Time   Sent To  
Notes
2023-02-28 11:46:43WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110423
 ADD: 2617 N AUSTRALIAN AVE.
 CONT: MASTER CONTRACTORS
 TEL: 561-712-8898
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 28TH/ 2022
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) COMPLIED.
 1B) SEMI-COMPLIED. CHANGED TO EXPOSURE D BUT DID NOT
 CHANGE PRESSURES ROOF AND WALL COMPONENTS AND CLADDING
 ( AS PLAN STATEMENT WORST CASE ALL OPENINGS) WALL ZONE
 5 AND ROOF ZONES 1, 2, & 3.
  
 2) COMPLIED.
 3) SHEET A-1 CONSTRUCTION FLOOR PLAN. SHOWS NEW
 EXTERIOR DOOR OPENINGS AND DOORS.
 3A)SEMI-COMPLIED, MISSING THE PRODUCT APPROVAL FOR THE
 NEW OPENING EAST SIDE, DOOR SIDELIGHTS (WINDOWS &
 VERTICAL MULLION, BETWEEN WINDOW & DOOR JAMB NEW DOUBLE
 GLASS DOOR SYSTEM. )
 1ST ROUND OF COMMENTS. COMPONENTS & CLADDING. PLEASE
 SUBMIT THE COMPONENTS AND CLADDING PRODUCT APPROVALS.
 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS
 (B) DOOR SIDELIGHT WINDOWS
  
 3B) SEMI-COMPLIED, NEED WINDOW AND MULLION REPORTS. W.
 P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE 61G20
 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP DRAWING
 STAMP OF APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3C) SEMI-COMPLIED. NEED WINDOW AND MULLION REPORTS.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER???S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 3D)(1) SEMI-COMPLIED. PLEASE PROVIDE THE WIDTH OF THE
 EXISTING SIDEWALK. EXISTING ADA RAMP DOOR TO HOTEL
 STAFF ENTRANCE ONLY NEEDS TO SHOW COMPLIANCE WITH
 2020-ACCESSIBILITY CODE FIGURE 404.2.1 FIGURE
 ( E ).
  
 3D)(2) NEW COMMENT. EXISTING DOOR WEST SIDE OF BUILDING
 AT EXISTING ADA RAMP TO STAFF TRAINING ROOM IS MISSING
 THE REQUIRED MANEUVERING CLEARANCE LETCH SIDE OF DOOR.
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
 FIGURE 404.2.1(A)
  
 1ST ROUND OF COMMENTS. THE FLOOR PLAN SHOWS FROM THE
 NEW LOBBY THERE IS A SERIES OF EXISTING STAIRS THAT
 EITHER DROP OR ARE RAISED TO THE HOTEL AERA. THE FLOOR
 PLAN DOES NOT SHOW COMPLIANCE WITH VERTICAL
 ACCESSIBILITY REQUIREMENTS. PLEASE REVIEW SECTION
 201.1.1 VERTICAL ACCESSIBILITY & SECTION 408 FOR LULA
 LIFT, LIMITED USE LIMITED APPLICATION.
  
 3E) COMPLIED. BREAKROOM DOOR.
  
 3F) COMPLIED. INFILL HOTEL & STAFF TRAINING ROOM.
  
 3G)(1) COMPLIED. THE NEW BREAK ROOM SINK AND CABINETS .
 3G)(2) COMPLIED. 606.2 CLEAR FLOOR SPACE
  
 3H) COMPLIED DOOR.
  
 3I) COMPLIED. THE LOBBY RECEPTION DESK.
  
 3J) COMPLIED. DRINKING FOUNTAIN. NO FEWER THAN TWO
 DRINKING FOUNTAINS.
  
 3K) 2ND REQUEST. DRINKING FOUNTAINS PROTRUDING OBJECTS
 307.2 PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES
 ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 3L) COMPLIED. DRINKING FOUNTAIN 602.2 CLEAR FLOOR SPACE
  
 3M) COMPLIED. POUT OUTLETS/ DRINKING FOUNTAINS
  
  
  
 4)COMPLIED. SHEET A-3 BATHROOM ACCESSIBILITY DETAILS:
  
 5) CMPLIED.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-28 Cont ID  
Sent By jwitmer Date 2022-12-28 Time 13:03 Rev Time 0.00
Received By jwitmer Date 2022-12-28 Time 10:11 Sent To  
Notes
2022-12-28 13:03:38WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110423
 ADD: 2617 N AUSTRALIAN AVE.
 CONT: MASTER CONTRACTORS
 TEL: 561-712-8898
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 28TH/ 2022
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) OCCUPANT LOAD IS TAKEN AS 5,600 SQ. FT. @ 150= 37.3
 ROUNDED DOWN TO 37. WHEN THERE IS A DECIMAL PORTION OF
 AN OCCUPANT IT IS ALWAYS ROUNDED UP THERE ARE NO PARTS
 OF A OCCUPANT. TABLE 1004.1.2 OF THE 2017 FBC-BUILDING,
 INTERPRETATION FROM THE BUILDING OFFICIALS OF FLORIDA
 INFORMAL INTERPRETATIONS.
  
 1B) DESIGN WIND PRESSURES DOES NOT PROVIDE ALL OF THE
 WIND DESIGN CRITERIA, MISSING INFO:
 1B)(1)IS THE DESIGN WIND PRESSURE IN VULT OR VASD
 1B(2) RISK CATEGORY
 1B)( C ) WIND EXPOSURE- 2020 FBC-BUILDING 1609.4.3.
 EXPOSURE CATEGORIES, EXPOSURE D.
 EXPOSURE D SHALL APPLY WHERE THE GROUND SURFACE
 ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS
 D, PREVAILS IN THE UPWARD DIRECTION FOR A DISTANCE OF
 AT LEAST 5,000 FEET OR 20 TIMES THE HEIGHT
 OF THE BUILDING, WHICHEVER IS GREATER. EXPOSURE SHALL
 ALSO APPLY WHERE THE GROUND SURFACE
 ROUGHNESS IMMEDIATELY UPWIND OF THE SITE IS B OR C ,
 AND THE SITE IS WITHIN A DISTANCE OF 600
 FEET OR 20 TIMES THE BUILDING HEIGHT, WHICHEVER IS
 GREATER, FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
  
 2) SHEET SP-2 PROPOSED SITE PLAN.
 2A) INDICATES 53 PARKING SPACES. PLEASE REVIEW THE 2020
 FBC-BUILDING CODE TABLE 208.2 BETWEEN 51 TO 75 SPACES
 REQUIRING 3 ACCESSIBLE PARKING SPACES.
  
 2B) THE ACCESSIBLE PARKING SPACES DOESN???T INDICATE
 THE NEED TO COMPLY WITH: 502.4 ACCESS AISLE & PARKING
 SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND SURFACES.
 PARKING SPACES AND THE ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 3) SHEET A-1 CONSTRUCTION FLOOR PLAN. SHOWS NEW
 EXTERIOR DOOR OPENINGS AND DOORS.
 3A) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,
 (B) DOOR SIDELIGHT WINDOWS
  
 3B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER???S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 3D) THE FLOOR PLAN SHOWS FROM THE NEW LOBBY THERE IS A
 SERIES OF EXISTING STAIRS THAT EITHER DROP OR ARE
 RAISED TO THE HOTEL AERA. THE FLOOR PLAN DOES NOT SHOW
 COMPLIANCE WITH VERTICAL ACCESSIBILITY REQUIREMENTS.
 PLEASE REVIEW SECTION 201.1.1 VERTICAL ACCESSIBILITY &
 SECTION 408 FOR LULA LIFT, LIMITED USE LIMITED
 APPLICATION.
  
 3E) WHEN LEAVING THE LOBBY AREA THE DOOR THAT LEADS
 INTO THE BREAKROOM DOES NOT HAVE MANEUVERING
 CLEARANCES. ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
  
 3F) THE DOOR BETWEEN THE HOTEL AREA AND STAFF TRAINING
 ROOM IS ALSO MISSING THE MANEUVERING CLEARANCES. THIS
 SAME DOOR IS INSET ONE FOOT WITHIN THE FACE OF THE
 WALL. PLEASE REVIEW 404.2.4.3 RECESSED DOORS AND FIGURE
 404.2.4.3.
  
 3G)(1) THE NEW BREAK ROOM SINK AND CABINETS WILL NEED
 TO SHOW COMPLIANCE WITH THE 2020 ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3G)(2) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
 3H) THE DOOR LEADING INTO THE OFFICE IS A 2-FOOT 8-INCH
 DOOR OR 32-INCHES. 2020 ACCESS. CODE 404.2.3. CLEAR
 WIDTH & SIZE OF DOORS, 2020 FBC-B 1010.1.1. WHERE THIS
 SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32-INCHES OR
 A 34-INCH DOOR MINIMUM. THE MINIMUM SIZE OF A SWING
 DOORS IS MEASURED CLEAR OPENING OF THE DOORWAY WITH THE
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 3I) THE LOBBY RECEPTION DESK DOES NOT PROVIDE DETAILS
 FOR ACCESSIBILITY CODE COMPLIANCE, SECTION:
 3I)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3I)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3J) THE PLANS DO NOT PROVIDE COMPLIANCE WITH DRINKING
 FOUNTAINS. 2020 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 3K) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 3L) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 3M) POUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
  
  
 4) SHEET A-3 BATHROOM ACCESSIBILITY DETAILS:
 4A) DETAIL 2 BACK GRAB BAR IS A GENERIC DETAIL BUT NOT
 ACCURATE WHEN THE SIDE WALL IS CONSIDERED. THE SIDE
 WALL IS TO THE RIGHT OF THE WATER CLOSET SO SHOWING THE
 DETAIL AS IS THE GRAB BAR COULD BE INSTALLED RIGHT IN
 THE CORNER OF THE ROOM, SECTION 604.5.2
  
 4B) DETAIL # 7 MIRROR. 2020 ACCESS. CODE 404.2.3. CLEAR
 WIDTH & SIZE OF DOORS, 2020 FBC-B 1010.1.1. WHERE THIS
 SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32-INCHES OR
 A 34-INCH DOOR MINIMUM. THE MINIMUM SIZE OF A SWING
 DOORS IS MEASURED CLEAR OPENING OF THE DOORWAY WITH THE
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 5) NEITHER SHEET A-3-BATHROOM DETAILS NOR A-4 DETAIL
 SHEET SHOW COMPLIANCE WITH BATHROOM WALL FINISHES. 2020
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
  
 5A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 5B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 5C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 5D) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER???S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM (MR BOARD) SHALL NOT BE USED FOR
 SHOWER & TUB ENCLOSURES BUT CAN BE USED FOR BACKING
 BOARD FOR A BASE FOR TILE IN WATER CLOSET COMPARTMENT
 WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840 AND THE MANUFACTURE???S RECOMMENDATIONS.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2022-12-28 10:13:36IN REVIEW. JW

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-05-03 Cont ID  
Sent By mpeterso Date 2023-05-03 Time 15:04 Rev Time 0.00
Received By mpeterso Date 2023-05-03 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-26 Cont ID  
Sent By mpeterso Date 2023-04-26 Time 13:09 Rev Time 0.00
Received By mpeterso Date 2023-04-26 Time 13:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-15 Cont ID  
Sent By fgiaquin Date 2022-12-15 Time 22:08 Rev Time 0.00
Received By fgiaquin Date 2022-12-15 Time 21:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2023-05-04 Cont ID  
Sent By pleduc Date 2023-05-04 Time   Rev Time 0.00
Received By pleduc Date 2023-05-04 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2023-04-26 Cont ID  
Sent By cwalker Date 2023-04-26 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-04-14 Cont ID  
Sent By pleduc Date 2023-04-14 Time   Rev Time 0.00
Received By pleduc Date 2023-04-14 Time 09:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-03-30 Cont ID  
Sent By cwalker Date 2023-03-30 Time   Rev Time 0.00
Received By cwalker Date 2023-03-30 Time   Sent To  
Notes
2023-03-30 10:32:41FIRE PROVISO COMMENTS:
  
 (1) DOOR LOCKS, 7.2.1.5 LOCKS, LATCHES, AND ALARM
 DEVICES
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IN
 OCCUPIED.
  
 7.7.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR THE
 OPERATION FROM THE EGRESS SIDE.
  
 (2) PORTABLE FIRE EXTINGUISHERS OF THE APPROPRIATE
 QUANTITY, SIZE, AND TYPE FOR THE HAZARD SHALL BE
 PROVIDED WITHIN 75 FT. OF TRAVEL DISTANCE FROM ANY
 POINT INSIDE THE BUILDING. NFPA 38.3.5
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-01 Cont ID  
Sent By cwalker Date 2023-03-01 Time   Rev Time 0.00
Received By cwalker Date 2023-03-01 Time   Sent To  
Notes
2023-03-01 09:39:13FIRE PROVISO COMMENTS:
  
 (1) DOOR LOCKS, 7.2.1.5 LOCKS, LATCHES, AND ALARM
 DEVICES
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 (2) PORTABLE FIRE EXTINGUISHERS OF THE APPROPRIATE
 QUANTITY, SIZE AND TYPE FOR THE HAZARD SHALL BE
 PROVIDED WITHIN 75 FT. OF TRAVEL DISTANCE FROM ANY
 POINT INSIDE THE BUILDING. NFPA 38.3.5
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-12-05 Cont ID  
Sent By cwalker Date 2022-12-05 Time   Rev Time  
Received By cwalker Date 2022-12-05 Time   Sent To  
Notes
2022-12-05 10:37:09FIRE PROVISO COMMENTS:
  
 (1) DOOR LOCKS, 7.2.1.5 LOCKS, LATCHES, AND ALARM
 DEVICES.
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
  
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 (2) PORTABLE FIRE EXTINGUISHERS OF THE APPROPRIATE
 QUANTITY, SIZE AND TYPE FOR THE HAZARD SHALL BE
 PROVIDED WITHIN 75 FT. OF TRAVEL DISTANCE FROM ANY
 POINT INSIDE THE BUILDING. NFPA 38.3.5
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-05-09 Cont ID  
Sent By jgomez Date 2023-05-09 Time 17:28 Rev Time 0.00
Received By jgomez Date 2023-05-03 Time 09:11 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-04-28 Cont ID  
Sent By aoliver Date 2023-04-28 Time 16:33 Rev Time 0.00
Received By aoliver Date 2023-04-25 Time 08:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-24 Cont ID  
Sent By medwards Date 2023-04-24 Time 12:24 Rev Time 0.00
Received By medwards Date 2023-04-13 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-06 Cont ID  
Sent By lmarchan Date 2023-04-06 Time 15:52 Rev Time 0.00
Received By lmarchan Date 2023-03-29 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-08 Cont ID  
Sent By lmarchan Date 2023-03-08 Time 10:16 Rev Time 0.00
Received By lmarchan Date 2023-02-27 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-11 Cont ID  
Sent By lmarchan Date 2023-01-11 Time 15:33 Rev Time 0.00
Received By lmarchan Date 2022-12-01 Time 09:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-12-28 Cont ID  
Sent By jwitmer Date 2022-12-28 Time 13:03 Rev Time 0.00
Received By jwitmer Date 2022-12-28 Time 10:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2023-05-03 Cont ID  
Sent By medwards Date 2023-05-03 Time 15:02 Rev Time 0.00
Received By medwards Date 2023-05-03 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2023-04-25 Cont ID  
Sent By medwards Date 2023-04-25 Time 10:27 Rev Time 0.00
Received By medwards Date 2023-04-25 Time 10:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-04-24 Cont ID  
Sent By medwards Date 2023-04-24 Time 12:23 Rev Time 0.00
Received By medwards Date 2023-04-24 Time 12:22 Sent To  
Notes
2023-04-24 12:23:27MECHANICAL DESIGN WAS NOT SUBMITTED IN THIS CYCLE. ME

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-04-04 Cont ID  
Sent By medwards Date 2023-04-04 Time 14:09 Rev Time 0.00
Received By medwards Date 2023-04-04 Time 14:09 Sent To  
Notes
2023-04-04 14:09:233RD REVIEW FMC
 PERMIT:
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS 5600 SQUARE FOOT PET RESORT WILL REQUIRE
 OUTDOOR AIR FOR 56 PEOPLE AND THE SPACE FOR A TOTAL OF
 1,428 CFM???S. IT WILL ALSO REQUIRE A TOTAL EXHAUST OF
 5,040 CFM???S BASED ON WHAT WAS SUBMITTED. SHEET M-2
 INDICATES IN THE EXHAUST FAN SCHEDULE THAT EACH EXHAUST
 FAN IS 110 CFM. THE DRAWING SEEMS TO INDICATE THAT EACH
 FAN IS 330 CFM. THE DRAWING AND SCHEDULE WILL NEED TO
 MATCH. FMC TABLE 403.3.1.1
  
 2) THE EXISTING RTUS INDICATE THAT 4 UNITS HAVE A
 SUPPLY AIR OF 2000 CFM???S AND 350 CFMS OF OUTDOOR AIR.
 THE ONE RTU HAS 1600 CFMS OF SUPPLY WITH 250 CFMS OF
 OUTDOOR AIR. THIS A TOTAL OF 1650 CFM???S OF OUTDOOR
 AIR ENTERING THE BUILDING WITH A TOTAL OF 5600CFM OF
 EXHAUST AIR INCLUDING THE BATHROOMS LEAVING THIS
 BUILDING. PLEASE SHOW HOW THIS DESIGN WILL BE BALANCED.
 FMC 403.3.1.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-03-02 Cont ID  
Sent By medwards Date 2023-03-02 Time 09:54 Rev Time 0.00
Received By medwards Date 2023-03-02 Time 09:54 Sent To  
Notes
2023-03-02 09:54:271ST REVIEW FMC
 PERMIT: 22110423
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2: PLEASE REMOVE THE OUTSIDE AIR
 CALCULATIONS REFERENCE TO ASHRAE 62.1 AS THE FLORIDA
 MECHANICAL CODE 2020 EDITION SHOULD BE USED FBC
 403.3.1.1 AND TABLE 403.3.1.1
  
 2) SHEET M-1: THE EXISTING MECHANICAL UNITS CAN BRING
 IN A COMBINED TOTAL OF 1,650 CFM???S OF OUTDOOR AIR
 THROUGH THE SYSTEMS. THIS OUTDOOR AIR IS CONDITIONED TO
 COOL AND REMOVE THE HUMIDITY SO THE OUTDOOR AIR BEING
 DELIVERED INSIDE THE BUILDING DOES NOT CAUSE HUMIDITY
 AND UNSAFE CONDITIONS INSIDE THIS BUILDING. BASED ON
 THE INFORMATION PROVIDED, IT IS REQUIRED, BASED ON THE
 OCCUPANTS AND OCCUPANCY CLASSIFICATION??? FOR THE
 OCCUPANTS AND THE SPACE, TO BRING IN A MINIMUM OF 739
 CFM???S. THIS LEAVES A TOTAL OF 911 CFM???S OF
 CONDITIONED OUTDOOR AIR. THE REQUIRED EXHAUST FOR THIS
 BUILDING, ACCORDING TO THE INFORMATION SUBMITTED, IS
 2,532 CFM???S FOR THE PET AREAS AND 140 CFM???S FOR THE
 BATHROOMS EXHAUST. THIS IS A TOTAL OF 2,672 OF REQUIRED
 EXHAUST FOR THIS BUILDING.
  
 SHEET M-2: EACH SPACE MUST EXHAUST THE MINIMUM REQUIRED
 FOR THAT SPACE. THE ANIMAL AREAS EXHAUST FAN SCHEDULE
 SPECIFIES AN EXHAUST FAN WITH 110 CFM???S. THERE ARE 8
 SHOWN ON THIS DRAWING. THIS WOULD BE A TOTAL OF 880
 CFM???S OF EXHAUST FOR THE PET AREAS. NOTE 1 ON SHEET
 M-2 INDICATES THE EXHAUST FANS AND THE SUPPLY FANS WILL
 BE CONTROLLED TO OPERATE SIMULTANEOUSLY. THIS COULD
 MEAN THAT THE SYSTEM WOULD BRING IN 1,792 CFM???S OF
 UNCONDITIONED AIR FROM THE OUTSIDE. PLEASE EXPLAIN HOW
 THIS DESIGN WILL PROVIDE AN AIR-CONDITIONING SYSTEM
 THAT MEETS THE DEFINITIONS FROM THE 2020 FMC LISTED
 BELOW.
 FMC DEFINITIONS:
  
 CONDITIONED SPACE. AN AREA, ROOM OR SPACE THAT IS
 ENCLOSED WITHIN THE BUILDING THERMAL ENVELOPE AND THAT
 IS DIRECTLY HEATED OR COOLED OR THAT IS INDIRECTLY
 HEATED OR COOLED.
 SPACES ARE INDIRECTLY HEATED OR COOLED WHERE THEY
 COMMUNICATE THROUGH OPENINGS WITH CONDITIONED SPACES,
 WHERE THEY ARE SEPARATED FROM CONDITIONED SPACES BY
 UNINSULATED WALLS,
 FLOORS OR CEILINGS, OR WHERE THEY CONTAIN UNINSULATED
 DUCTS, PIPING OR OTHER SOURCES OF HEATING OR COOLING.
  
 AIR CONDITIONING. THE TREATMENT OF AIR SO AS TO CONTROL
 SIMULTANEOUSLY THE TEMPERATURE, HUMIDITY, CLEANNESS AND
 DISTRIBUTION OF THE AIR TO MEET THE REQUIREMENTS OF A
 CONDITIONED
 SPACE.
  
 AIR-CONDITIONING SYSTEM. A SYSTEM THAT CONSISTS OF HEAT
 EXCHANGERS, BLOWERS, FILTERS, SUPPLY, EXHAUST AND
 RETURN DUCTS, AND SHALL INCLUDE ANY APPARATUS INSTALLED
 IN CONNECTION THEREWITH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By medwards Date 2022-12-14 Time 15:48 Rev Time  
Received By medwards Date 2022-12-14 Time   Sent To  
Notes
2022-12-14 15:48:381ST REVIEW FMC
 PERMIT: 22110423
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMPLETE OUTDOOR AIR CALCULATION
 AND EXHAUST FOR EACH SPACE IN THIS PROJECT ACCORDING TO
 THE OCCUPANCY CLASSIFICATION AND OCCUPANT DENSITY FROM
 FMC TABLE 403.3.1.1. I SEE ON SHEET M-2 THE FRESH AIR
 CALCULATIONS ARE SHOWN SHOWING THE ENTIRE SQUARE
 FOOTAGE AS PET AREA. THIS IS OK BUT THE NEW EXHAUST
 EQUIPMENT SCHEDULE ONLY SHOWS EXHAUST IN CERTAIN ROOMS.
 THE CALCULATIONS SHOULD SHOW THE ENTIRE STORY OF THIS
 SPACE. ACCORDING TO FOOT NOTE B OF TABLE 403.3.1.1
 B. MECHANICAL EXHAUST REQUIRED AND THE RECIRCULATION OF
 AIR FROM SUCH SPACES IS PROHIBITED. RECIRCULATION OF
 AIR THAT IS CONTAINED COMPLETELY WITHIN SUCH SPACES
 SHALL NOT BE PROHIBITED (SEE SECTION 403.2.1, ITEM 3).
 IF A SPACE IS TO HAVE PETS IN IT, EXHAUST WOULD BE
 REQUIRED AND RECIRCULATION OF AIR TO OTHER AREAS WOULD
 NOT BE ALLOWED. IF THE ENTIRE 5600 SQUARE FEET OF AREA
 IS TO BE USE AS PET AREA THEN THE EXHAUST AIR WOULD
 INCREASE.
  
 2) PLEASE SHOW THE MECHANICAL DESIGN FOR THIS TENANT
 CAN SUPPORT THE REQUIRED OUTDOOR AND EXHAUST AIR FOR
 THIS NEW TENANT. FMC 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-05-03 Cont ID  
Sent By rwbrown Date 2023-05-03 Time 14:58 Rev Time 0.00
Received By rwbrown Date 2023-05-03 Time 14:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-26 Cont ID  
Sent By rwbrown Date 2023-04-26 Time 07:57 Rev Time 0.00
Received By rwbrown Date 2023-04-26 Time 07:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-02-28 Cont ID  
Sent By rwbrown Date 2023-02-28 Time 09:34 Rev Time 0.00
Received By rwbrown Date 2023-02-28 Time 09:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-06 Cont ID  
Sent By jesmith Date 2022-12-06 Time 16:35 Rev Time 0.00
Received By jesmith Date 2022-12-06 Time 16:35 Sent To  
Notes
2022-12-06 16:35:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22110423 2617 N AUSTRALIAN AVE
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
  
 1. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE
  
 2. PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 3. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. FBC ACC 603.3.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS
 TO THE REFLECTING SURFACE OF THE MIRROR
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1. PER FBC PL 410.3, TWO OR A BI-LEVEL ARE REQUIRED
 AND SHALL COMPLY WITH FBC ACC 305, 306, 307, 602.2,
 602.3, 602.4, 602.5 AND 602.7.
 PER WPB FBC 107.2.1, 107.3.5.1.1(10) PROVIDE A DETAIL
 SHOWING COMPLIANCE
  
 5. PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606
 PER FBC ACC 212.3.
 PLEASE SHOW COMPLIANCE FOR NEW SINK INCLUDING
 COMPLIANCE WITH FBC ACC 305, 306, 606.3. PROVIDE DETAIL
 IF APPLICABLE. THIS RULE DOES NOT APPLY TO A MOP OR
 SERVICE SINK.
  
  
 6. A MOP OR SERVICE SINK IS REQUIRED PER FBC PL TABLE
 403.1.
  
 7. PER WPB FBC 107.2.1, 107.3.5.1.3(2), PROVIDE A
 PLUMBING FIXTURE SCHEDULE LISTING ALL PLUMBING FIXTURES
 WITH DESCRIPTION (BE SURE TO INCLUDE CONTROL VALVE).
 NOTE WASTE AND WATER CONNECTIONS, CONNECTION SIZES,
 DRAINAGE FIXTURE UNITS PER FBC PL 709.1, MAXIMUM FLOW
 RATES GPM PER FBC PL 604.4. TAG FIXTURES ON PIPING
 DRAWINGS TO MATCH SCHEDULE.
 I.E., WC-1 WATER CLOSET-TANK TYPE/FLOOR
 MOUNTED/ELONGATED BOWL, ADA COMPLIANT 3 INCH WASTE 4
 DFU 1/2 COLD WATER 1.28 GPM
  
  
 8. PER WPB FBC 107.2.1, 107.3.5.1.3(3)(10)(13), PROVIDE
 WATER DISTRIBUTION PLAN VIEW AND RISER DIAGRAM. INCLUDE
 REQUIRED HOT WATER SHOWING COMPLIANCE WITH FBC PL 607.
 NOTE APPLICABLE VALVES, BACKFLOW PREVENTERS,
 TEMPERATURE-ACTUATED MIXING VALVES, WATER HAMMER
 ARRESTORS, APPURTENANCES.
 PLEASE NOTE, PER FBC PL 607.2, DEVELOPED LENGTH HOT OR
 TEMPERED WATER FROM SOURCE SHALL NOT EXCEED 50 FEET.
 PER FBC EC C404.5.1, TABLE C404.5.1, 1/2 -INCH HOT
 WATER PIPE TO THE LAVATORY SHALL NOT EXCEED 2FEET FROM
 THE HOT WATER SOURCE.
  
 9. PER WPB FBC 107.2.1, 107.3.5.1.3(5), PROVIDE
 SCHEDULE AND DETAIL OF WATER HEATER SHOWING HEATER
 W/STORAGE CAPACITY, PIPING INCLUDING CW, HW, VALVES
 (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC PL
 504.2) , THERMAL EXPANSION CONTROL DEVICE IF
 APPLICABLE(SEE 607.3), T&P DISCHARGE (INCLUDING
 TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION); COMPLY WITH FBC PL 607.3, 503.1, 504.1,
 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND 504.7,
 607.1.1, 613.1.
 PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY WITH
 FBC EC TABLE C404.2
  
 10. PER WPB FBC 107.2.1, 107.3.5.1.3(3)(4), PROVIDE
 PIPING MATERIAL SPEC FOR SANITARY AND WATER SYSTEMS.
 COMPLY WITH FBC PL CHAPTERS 6, 7, 911. PER
  
 11. WPB FBC 107.2.1, PROVIDE INSULATION SPECIFICATION
 SPEC FOR HOT WATER INSULATION AS APPLICABLE. COMPLY
 WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-05-09 Cont ID  
Sent By jgomez Date 2023-05-09 Time 17:28 Rev Time 0.00
Received By jgomez Date 2023-05-09 Time 17:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-04-25 Cont ID  
Sent By medwards Date 2023-04-25 Time 10:30 Rev Time 0.00
Received By medwards Date 2023-04-25 Time 10:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-04-24 Cont ID  
Sent By medwards Date 2023-04-24 Time 12:23 Rev Time 0.00
Received By medwards Date 2023-04-24 Time 12:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 14:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-02 Cont ID  
Sent By medwards Date 2023-03-02 Time 09:57 Rev Time 0.00
Received By medwards Date 2023-03-02 Time 09:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-28 Cont ID  
Sent By jwitmer Date 2022-12-28 Time 13:05 Rev Time  
Received By jwitmer Date 2022-12-28 Time   Sent To  
Notes
2022-12-14 15:49:46MECHANICAL DIGITAL SIGNATURES APPROVED ME
2022-12-06 16:41:44ELECTRONIC SIGNATURES FOR PLUMBING ARE APPROVED. JS

Review Stop Z ZONING
Rev No 6 Status P Date 2023-05-08 Cont ID  
Sent By llouie Date 2023-05-08 Time   Rev Time 0.00
Received By llouie Date 2023-05-08 Time   Sent To  
Notes
2023-05-08 09:47:18ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) INTERIOR MODIFICATIONS ONLY. SEPARATE PERMITS
 REQUIRED FOR ALL EXTERIOR IMPROVEMENTS (I.E. PARKING
 LOT, LANDSCAPING, ETC.).
  
 2.) USE IS SUBJECT TO THE CONDITIONS PROVIDED IN ZBA
 FINAL ORDER 3414.
  
 3.) SEE ATTACHED STAMPED SHEETS FOR ZONING APPROVAL.
  
 (REFERENCE: ZBA 3414, APPROVED SEPTEMBER 1, 2022)
  

Review Stop Z ZONING
Rev No 5 Status P Date 2023-04-28 Cont ID  
Sent By llouie Date 2023-04-28 Time   Rev Time 0.00
Received By llouie Date 2023-04-28 Time   Sent To  
Notes
2023-04-28 16:27:54ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) INTERIOR MODIFICATIONS ONLY. SEPARATE PERMITS
 REQUIRED FOR ALL EXTERIOR IMPROVEMENTS (I.E. PARKING
 LOT, LANDSCAPING, ETC.).
  
 2.) USE IS SUBJECT TO THE CONDITIONS PROVIDED IN ZBA
 FINAL ORDER 3414.
  
 3.) SEE ATTACHED STAMPED SHEETS FOR ZONING APPROVAL.
  
 (REFERENCE: ZBA 3414, APPROVED SEPTEMBER 1, 2022)
  

Review Stop Z ZONING
Rev No 4 Status P Date 2023-04-18 Cont ID  
Sent By llouie Date 2023-04-18 Time   Rev Time 0.00
Received By llouie Date 2023-04-18 Time   Sent To  
Notes
2023-04-18 14:17:57ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) INTERIOR MODIFICATIONS ONLY. SEPARATE PERMITS
 REQUIRED FOR ALL EXTERIOR IMPROVEMENTS (I.E. PARKING
 LOT, LANDSCAPING, ETC.).
  
 2.) USE IS SUBJECT TO THE CONDITIONS PROVIDED IN ZBA
 FINAL ORDER 3414.
  
 3.) SEE ATTACHED STAMPED SHEETS FOR ZONING APPROVAL.
  
 (REFERENCE: ZBA 3414, APPROVED SEPTEMBER 1, 2022)
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-04-06 Cont ID  
Sent By llouie Date 2023-04-06 Time   Rev Time 0.00
Received By llouie Date 2023-04-06 Time   Sent To  
Notes
2023-04-06 15:33:36** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE (MORE INFORMATION REQUIRED ON THE PROPOSED
 USE):
  
 1.) PET GROOMING ESTABLISHMENTS ARE STRICTLY PROHIBITED
 IN THE OFFICE COMMERCIAL (OC) ZONING DISTRICT.
  
 ANIMAL DAYCARE AND BOARDING FACILITIES ARE CLASSIFIED
 AS "ENCLOSED VETERINARY CLINICS, HOSPITALS AND ANIMAL
 SHELTERS." BOARDING OF ANIMALS IS PROHIBITED, UNLESS TO
 PROVIDE REQUIRED TREATMENT. THIS TYPE OF USE IS
 PERMITTED WITH RESTRICTIONS IN THE OC ZONING DISTRICT
 AND COULD POTENTIALLY REQUIRE A CLASS B SPECIAL USE
 PERMIT (REQUIRES APPROVAL BY THE ZONING BOARD OF
 APPEALS) IF THE REQUIRED STANDARDS ARE MET (IT WOULD
 OTHERWISE BE A PROHIBITED USE). THE MINIMUM
 REQUIREMENTS FOR THE USE ARE PROVIDED IN S.94-273(D) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 [1//11/2023 AND 3/8/2023 REPEAT COMMENTS: THE RESPONSES
 PROVIDED IN THE PERMIT RESUBMITTAL ACKNOWLEDGES THE
 REQUIREMENT FOR THE CLASS B SPECIAL USE PERMIT;
 HOWEVER, AT THIS TIME, THERE IS NO RECORD OF A FORMAL
 APPLICATION WITH THE DEVELOPMENT SERVICES DEPARTMENT
 ??? PLANNING DIVISION. PLEASE NOTE THAT AN APPLICATION
 FOR A CLASS B SPECIAL USE PERMIT REQUIRES A
 PRE-APPLICATION MEETING WITH PLANNING STAFF PRIOR TO
 THE FORMAL SUBMISSION OF THE CLASS B APPLICATION.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: OC
  
 * ANIMAL BOARDING - CLASSIFICATION "ENCLOSED VETERINARY
 CLINICS, HOSPITALS AND ANIMAL SHELTERS."
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-03-08 Cont ID  
Sent By llouie Date 2023-03-08 Time   Rev Time 0.00
Received By llouie Date 2023-03-08 Time   Sent To  
Notes
2023-03-08 10:12:02** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE (MORE INFORMATION REQUIRED ON THE PROPOSED
 USE):
  
 1.) PET GROOMING ESTABLISHMENTS ARE STRICTLY PROHIBITED
 IN THE OFFICE COMMERCIAL (OC) ZONING DISTRICT.
  
 ANIMAL DAYCARE AND BOARDING FACILITIES ARE CLASSIFIED
 AS "ENCLOSED VETERINARY CLINICS, HOSPITALS AND ANIMAL
 SHELTERS." BOARDING OF ANIMALS IS PROHIBITED, UNLESS TO
 PROVIDE REQUIRED TREATMENT. THIS TYPE OF USE IS
 PERMITTED WITH RESTRICTIONS IN THE OC ZONING DISTRICT
 AND COULD POTENTIALLY REQUIRE A CLASS B SPECIAL USE
 PERMIT (REQUIRES APPROVAL BY THE ZONING BOARD OF
 APPEALS) IF THE REQUIRED STANDARDS ARE MET (IT WOULD
 OTHERWISE BE A PROHIBITED USE). THE MINIMUM
 REQUIREMENTS FOR THE USE ARE PROVIDED IN S.94-273(D) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 [1//11/2023 REPEAT COMMENT: THE RESPONSES PROVIDED IN
 THE PERMIT RESUBMITTAL ACKNOWLEDGES THE REQUIREMENT FOR
 THE CLASS B SPECIAL USE PERMIT; HOWEVER, AT THIS TIME,
 THERE IS NO RECORD OF A FORMAL APPLICATION WITH THE
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION.
 PLEASE NOTE THAT AN APPLICATION FOR A CLASS B SPECIAL
 USE PERMIT REQUIRES A PRE-APPLICATION MEETING WITH
 PLANNING STAFF PRIOR TO THE FORMAL SUBMISSION OF THE
 CLASS B APPLICATION.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: OC
  
 * ANIMAL BOARDING - CLASSIFICATION "ENCLOSED VETERINARY
 CLINICS, HOSPITALS AND ANIMAL SHELTERS."
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-01-11 Cont ID  
Sent By llouie Date 2023-01-11 Time   Rev Time  
Received By llouie Date 2023-01-11 Time   Sent To  
Notes
2023-01-11 12:36:46** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE (MORE INFORMATION REQUIRED ON THE PROPOSED
 USE):
  
 PET GROOMING ESTABLISHMENTS ARE STRICTLY PROHIBITED IN
 THE OFFICE COMMERCIAL (OC) ZONING DISTRICT.
  
 ANIMAL DAYCARE AND BOARDING FACILITIES ARE CLASSIFIED
 AS "ENCLOSED VETERINARY CLINICS, HOSPITALS AND ANIMAL
 SHELTERS." BOARDING OF ANIMALS IS PROHIBITED, UNLESS TO
 PROVIDE REQUIRED TREATMENT. THIS TYPE OF USE IS
 PERMITTED WITH RESTRICTIONS IN THE OC ZONING DISTRICT
 AND COULD POTENTIALLY REQUIRE A CLASS B SPECIAL USE
 PERMIT (REQUIRES APPROVAL BY THE ZONING BOARD OF
 APPEALS) IF THE REQUIRED STANDARDS ARE MET (IT WOULD
 OTHERWISE BE A PROHIBITED USE). THE MINIMUM
 REQUIREMENTS FOR THE USE ARE PROVIDED IN S.94-273(D) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: OC
  
 * ANIMAL BOARDING ??? CLASSIFICATION "ENCLOSED
 VETERINARY CLINICS, HOSPITALS AND ANIMAL SHELTERS"
  