| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL3318-R2 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: SELECT PRODUCT TO BE USED FROM |
| | EVALUATION REPORT PAGES 1-6; SELECT FASTENING DETAILS |
| | TO BE USED FROM APPNDIX A PAGES 2-5; SELECT APPROVED |
| | SYSTEM NO. TO BE USED FROM APPNDIX B PAGES 1-8; SELECT |
| | EXPOSURE, BUILDING TYPE, ZONE, MEAN ROOF HEIGHT & RISK |
| | CATEGORY FROM APPENDIX C PAGES 1-3. ALL APPLICABLE |
| | DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| | THE PRODUCT APPROVAL DRAWINGS. |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL |
| | FL5259-R34HAS BEEN REVISED TO FL5259-R36. PLEASE |
| | PROVIDE A COMPLETE SET; IT COVERS MULTIPLE PRODUCT |
| | TYPES; ROOF COVER OPTIONS; ALLOWABLE |
| | UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE |
| | SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS |
| | FROM EACH CATEGORY TO BE USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. |
| | 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R34 |
| | (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| | WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| | CONSIDER USING FL5259-R36 (NON-HVHZ). |
| | 4. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| | USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH TO INDICATE THE AREAS TO RECEIVE NEW |
| | ROOFING CLEARLY IDENTIFIED ON DRAWING AND INCLUDE ROOF |
| | SLOPE(S), MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS |
| | MUST SHOW POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |