| Plan Review Stops For Permit 22110232 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-04-03 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-04-03 |
Time |
13:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-01 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-01 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2022-12-01 12:11:15 | ELECTRIC REVIEW FAILED | | | 1) RISER DIAGRAM DOES NOT INDICATE CONDUCTOR SIZES OR | | | ANY OVERCURRENT PROTECTION. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5, NEC 210.20, AND NEC 230.90 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
2023-04-26 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
2023-04-26 |
Time |
07:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2022-12-30 |
|
|
Cont ID |
|
| Sent By |
sberglun |
Date |
2022-12-30 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
sberglun |
Date |
2022-12-30 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2022-12-30 10:27:27 | 1) PLANS NEED TO SHOW EXISTING CITY UTILITIES. PLEASE | | | WORK WITH DON GUSTAFSON, CITY PM. | | | SUZANNE BERGLUND | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-27 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-27 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-22 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-01-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-27 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-07 |
Time |
07:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-04-03 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-04-03 |
Time |
13:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-01-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-27 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-27 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2023-01-27 14:33:07 | SIGNATURE REVIEW FAILED | | | 1)THE REQUIRED DIGITAL SIGNATURE IS NOT DETAILED ON ALL | | | DRAWINGS. PLEASE CORRECT AS OUTLINED BELOW. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-25 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2023-04-25 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2023-04-25 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2023-04-19 09:05:39 | PER CONVERSATION WITH ENGINEERING DEPT. PROJECT IS | | | CITY-INITIATED AND CONFIRMED TO BE WITHIN ROW AND | | | AVOIDING CONFLICTS WITH UNDERGROUND UTILITIES OR ADA | | | ACCESSIBILITY ALONG SIDEWALKS. POLES TO BE LOCATED | | | WITHIN LANDSCAPE STRIP ALONG ROW. | | | PROPOSED DECORATIVE LIGHTS MEET THE DOWNTOWN MASTER | | | PLAN'S STREETSCAPE LIGHTING SPECS AND TYPICALS. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822-1426 [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-01-26 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2023-01-26 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2023-01-26 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2023-01-26 11:21:19 | 1. SITE PLAN SHOULD SHOW DECORATIVE LIGHT POLE LOCATION | | | AND DIMENSIONAL PROXIMITY IN RELATION TO STREETSCAPE | | | FEATURES ( STREET TREES, CURBS, SIDEWALK, LANDSCAPE | | | BEDS, ETC.). | | | PLEASE PROVIDE MORE DETAILED OR 'BLOWN UP' SECTIONS | | | THAT ILLUSTRATE LIGHT LOCATIONS IN DETAIL. | | | | | | 2. PROPOSED DECORATIVE LIGHTS MEET THE DOWNTOWN MASTER | | | PLAN'S STREETSCAPE LIGHTING SPECS AND TYPICALS. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822-1426 [email protected] |
|
|