Plan Review Details - Permit 22110134
Plan Review Stops For Permit 22110134
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 15:44 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-29 15:44:45COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 15:44 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-29 15:44:09WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110134
 ADD: 22110134
 CONT: S. MAC DONALD CONTRACTING LLC
 TEL: 561-689-8848
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 29TH/ 2022
 ACTION: DENIED
  
 1) SHEET A2 ELEVATIONS ,DESIGN WIND PRESSURES ON
 EXTERIOR DOORS AND WINDOWS (SERVICE) VASD. BENEATH
 THERE ARE NOTES. NOTE 1 WIND DESIGN PER 2020 FBC-B AND
 ASCE 7-16= 161MPH. THE COMPLETE WIND DESIGN CRITERIA
 NEEDS TO BE PROVIDED. 2020 FBC-B 1603.1.4 WIND DESIGN
 CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 1.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD. ALL PRODUCT APPROVALS ARE IN
 VASD.
  
 2) THE 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION USES THE PALM
 BEACH COUNTY (COUNTYWIDE) ULTIMATE DESIGN WIND SPEED
 MAP, RISK CATEGORY II BUILDING FIGURE 1609.3(1). THE
 160 VULT WIND SPEED LINE GOING OUT SOUTHERN BLVD. IS AT
 20 MILE BEND, JUST EAST OF THAT IS FPL NEWEST POWER
 PLANT. TUXEDO AVENUE WOULD BE CLOSER TO 168.75 VULT
 WIND SPEED FOR A RISK CATEGORY II BUILDING.
  
 3) SHEET A3 THE MEASUREMENT FOR THE ROOF PURLINS IS
 TAKEN HORIZONTALLY AT 3 FEET, WHEREAS THE 4/12 PITCH
 THE ACTUAL TRUE MEASUREMENT IS 3.33 FEET OR 3 FEET 4
 INCHES PLEASE UPDATE PLANS. WHAT IS MISSING ARE THE
 PRODUCT APPROVALS FOR FORMING THE WALL AND ROOF PANELS.
 WITHOUT THE PRODUCT APPROVALS FOR WALLS AND ROOF PANELS
 TO CHECK SPAN VERSES THE ASSOCIATED PRESSURES FOR THE
 EFFECTIVE WIND AREA (TRIBUTARY AREA). COMPONENTS &
 CLADDING. PLEASE SUBMIT THE COMPONENTS AND CLADDING
 PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4) PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO THE DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ROOF AND
 WALL PANELS, IDENTIFY (CIRCLE) THE METAL THICKNESS
 GAUGE, AND WIDTH OF PANEL, FASTENERS AND ASSOCIATED
 PRESSURES FOR INTERIOR, EDGE AND END ZONES.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 5) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 6) WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS
 EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
 7) SHEET A3THERE IS A NOTE: CONTINUOUS L 2 ?? X 2 ?? X
 ?? INCH ANGLE WITH ?? INCH DIA. X 4-INCH W. A. (WALL
 ANCHOR) AT 24 INCHES O. C. INTO SLAB. PLEASE PROVIDE
 THE DISTANCE THAT THE WALL ANCHOR NEEDS TO BE TO NOT
 BLOW OUT THE SIDE WALL WHEN ANCHOR IS TORQUED. THIS MAY
 DEPEND ON THE MANUFACTURERS RECOMMENDATIONS.
  
 8) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By jleahy Date 2022-12-12 Time 07:41 Rev Time 0.00
Received By jleahy Date 2022-12-12 Time 07:41 Sent To  
Notes
2022-12-12 07:47:13FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE PROVIDE A RISER DIAGRM SHOWING IF SERVICE IS
 OVERHEAD OR UNDERGROUND. PLEASE SHOW SIZE OF PANEL
 LIGHTING IS TO BE CONNECT TO.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-11-16 Cont ID  
Sent By   Date 2022-11-16 Time   Rev Time 0.00
Received By jcclark Date 2022-11-14 Time 13:29 Sent To  
Notes
2022-11-14 13:29:23PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-14 Cont ID  
Sent By rmcdouga Date 2022-12-14 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2022-11-07 Time 07:20 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 15:45 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-29 15:45:25IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM???S 2W01-2W14 WEST PALM BEACH, FL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-11-30 Cont ID  
Sent By medwards Date 2022-11-30 Time 17:04 Rev Time 0.00
Received By medwards Date 2022-11-30 Time 17:04 Sent To  
Notes
2022-11-30 17:05:32NO MECHANICAL WORK IN THE SCOPE OF WORK FOR THIS
 PROJECT. ME

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-11-16 Cont ID  
Sent By rwbrown Date 2022-11-16 Time 12:00 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-14 Cont ID  
Sent By rmcdouga Date 2022-12-14 Time 17:05 Rev Time 0.00
Received By rmcdouga Date 2022-12-14 Time 17:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-11-29 Cont ID  
Sent By kdefranc Date 2022-11-29 Time 13:51 Rev Time 0.00
Received By kdefranc Date 2022-11-29 Time 13:50 Sent To  
Notes
2022-11-29 13:51:2111/29/22 ??? FAILED
  
 REVIEW COMMENT TO BE ADDRESSED:
 1. PRIOR TO APPLICATION FOR A BUILDING PERMIT, A SITE
 PLAN REVIEW APPROVAL MUST BE OBTAINED ACCORDING TO THE
 CITY???S ZONING AND LAND DEVELOPMENT REGULATIONS
 SUBSECTION 94-35(B) AND THE PROPOSAL/INFORMATION
 SUBMITTED FOR THE SUBJECT BUILDING PERMIT REVIEW.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  