Plan Review Details - Permit 22110052
Plan Review Stops For Permit 22110052
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-12-13 Cont ID  
Sent By cpuell Date 2022-12-13 Time 17:00 Rev Time 0.00
Received By cpuell Date 2022-12-13 Time 17:00 Sent To  
Notes
2022-12-13 17:00:34ADDRESS APPROPRIATE FOR PROJECT.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status N Date 2023-01-11 Cont ID  
Sent By swelter Date 2023-01-11 Time 09:38 Rev Time 0.00
Received By swelter Date 2023-01-11 Time 09:38 Sent To  
Notes
***NONE***

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-06 Cont ID  
Sent By rmcphers Date 2023-03-06 Time 11:23 Rev Time 0.00
Received By rmcphers Date 2023-03-06 Time 11:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-07 Cont ID  
Sent By rmcphers Date 2023-02-07 Time 16:17 Rev Time 0.00
Received By rmcphers Date 2023-02-07 Time 15:45 Sent To  
Notes
2023-02-07 16:01:13NEW MANUFACTURED BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PREFAB MANUFACTURED BUILDINGS NEED TO BE FLORIDA
 STATE APPROVED - PLEASE PROVIDE THE FLORIDA STATE
 MANUFACTURED BUILDING APPROVAL FRONT PAGE - SEE (
 FLORIDABUILDING.ORG ) - FBC WPB 107.3 EXCEPTION (1)
  
 2) THE FOUNDATION DRAWING (F1) IS NOT PART OF THE PRE
 FAB MANUFACTURED BUILDING STATE APPROVAL AND WILL NEED
 TO BE SIGNED AND SEALED BY THE DESIGNER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 3) FOUNDATION DRAWINGS NEED TO SHOW THE WIND DESIGN
 PARAMETERS ( WIND SPEED, RISK CATEGORY, EXPOSURE ) USED
 FOR THE WIND DESIGN PER FBC 1603.1.4
  
 4) A SEPARATE PERMIT IS REQUIRED FOR - DUMPSTER
 ENCLOSURE, PARKING LOT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By rmcphers Date 2023-01-10 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 11:32 Sent To  
Notes
2023-01-10 12:50:54NEW MANUFACTURED BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FLORIDA STATE MANUFACTURED
 BUILDING APPROVAL FRONT PAGE.
  
 2) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 3) THE FOUNDATION DRAWING (F1) IS NOT PART OF THE
 PRODUCT APPROVAL AND WILL NEED TO BE SIGNED AND SEALED
 BY THE DESIGNER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
 4) PLEASE PROVIDE A SURVEY.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-06 Cont ID  
Sent By mpeterso Date 2023-03-06 Time 13:33 Rev Time 0.00
Received By mpeterso Date 2023-03-06 Time 13:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-02-07 Cont ID  
Sent By mpeterso Date 2023-02-07 Time 14:03 Rev Time 0.00
Received By mpeterso Date 2023-02-07 Time 14:03 Sent To  
Notes
2023-02-07 14:03:42PASSED ELECTRIC REVIEW FOR ELECTRIC SERVICE ONLY.
 SUBMITTAL IS FOR MANUFACTURED BUILDING WITH DPBR
 APPROVED PLANS. PLANS CAN BE FOUND AT WEBSITE BELOW
  
 HTTPS://WWW.FLORIDABUILDING.ORG/MB/MB_PLAN_SRCH.ASPX
  
 PFS CORPORATION (WI) AGENCY PLAN # G22SB2-REV 1
  
 PLAN TRACKING # 39846-R1
  
 DATE ACCEPTED 11/15/2022

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-04 Cont ID  
Sent By mpeterso Date 2023-01-04 Time 09:05 Rev Time 0.00
Received By mpeterso Date 2023-01-03 Time 08:12 Sent To  
Notes
2023-01-04 10:36:01PASSED ELECTRIC REVIEW FOR ELECTRIC SERVICE ONLY.
 SUBMITTAL IS FOR MANUFACTURED BUILDING WITH DPBR
 APPROVED PLANS. PLANS CAN BE FOUND AT WEBSITE BELOW
  
 HTTPS://WWW.FLORIDABUILDING.ORG/MB/MB_PLAN_SRCH.ASPX
  
 PFS CORPORATION (WI) AGENCY PLAN # G22SB2-REV 1
  
 PLAN TRACKING # 39846-R1
  
 DATE ACCEPTED 11/15/2022

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-02-13 Cont ID  
Sent By rrossano Date 2023-02-13 Time   Rev Time 0.00
Received By rrossano Date 2023-02-13 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2022-12-27 Cont ID  
Sent By rrossano Date 2022-12-27 Time   Rev Time  
Received By rrossano Date 2022-12-27 Time   Sent To  
Notes
2022-12-27 08:29:05PASSED WITH PROVISOS:
  
 1. ADDRESS ANY OTHER DISCIPLINES' COMMENTS.
 2. UPLOAD APPROVED ENGINEERING PLANS (TO BE RELEASED AT
 PENDING ENGINEERING PRE-CONSTRUCTION MEETING).
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-02-28 Cont ID  
Sent By pleduc Date 2023-02-28 Time   Rev Time 0.00
Received By pleduc Date 2023-02-28 Time 12:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-02-07 Cont ID  
Sent By pleduc Date 2023-02-07 Time   Rev Time 0.00
Received By pleduc Date 2023-02-07 Time 12:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-12-21 Cont ID  
Sent By pleduc Date 2022-12-21 Time   Rev Time 0.00
Received By pleduc Date 2022-12-21 Time 10:18 Sent To  
Notes
2022-12-21 10:45:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS ON THE ELECTICAL PLAN SHEET E
 1 OF EXIT SIGNS LEADING OUT OF THE RESTROOM AND OUT OF
 THE OPENING TO THE REAR EXIT.
  
 HOWEVER, THE RESTROOM DOOR OPENS OUT INTO THE EXIT
 TRAVEL PATH AND RESTRICTS EGRESS DUE TO THE EQUIPMENT
 INSTALLATIONS.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
  
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
  
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 7.3.4 MINIMUM WIDTH.
  
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE PROVIDED
 IN 7.3.4.1.1 THROUGH 7.3.4.1.3, SHALL BE AS FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN THIS
 CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS CHAPTER
 AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY A MINIMUM
 WIDTH
  
 7.3.4.1.1* THE WIDTH OF EXIT ACCESS SERVING NOT MORE
 THAN SIX PEOPLE
 AND HAVING A LENGTH NOT EXCEEDING 50 FT (15 M) SHALL
 MEET BOTH OF THE
 FOLLOWING CRITERIA:
 (1) THE WIDTH SHALL BE NOT LESS THAN 18 IN. (455 MM),
 AT AND BELOW A
 HEIGHT OF 38 IN. (965 MM), AND NOT LESS THAN 28 IN.
 (710 MM) ABOVE
 A HEIGHT OF 38 IN. (965 MM).
 (2) A WIDTH OF NOT LESS THAN 36 IN. (915 MM) FOR NEW
 EXIT ACCESS, AND
 NOT LESS THAN 28 IN. (710 MM) FOR EXISTING EXIT ACCESS,
 SHALL BE
 CAPABLE OF BEING PROVIDED WITHOUT MOVING PERMANENT
 WALLS
  
 7.3.4.2 WHERE A SINGLE EXIT ACCESS LEADS TO AN EXIT,
 ITS CAPACITY IN TERMS
 OF WIDTH SHALL BE NOT LESS THAN THE REQUIRED CAPACITY
 OF THE EXIT TO WHICH
 IT LEADS
  
 PLEASE REVIEW AND PROVIDE THE DIMENSION FOR PROPER
 CLEARANCE OR REMOVE THE EXIT SIGN OVER THE OPENING TO
 THE REAR AND PALCE ONE OVER ANY OF THE OTHER EXTERIOR
 DOORS IN THE FRONT.
  
  
 2) THE DOOR SCHEDULE INDICATES LOCKING HARDWARE ON D3
 DOORS.
  
 IF ONE OF THOSE DOORS HAS THE EXIT SIGN MOVED OVER IT,
 THE LOCKING HARDWARE SHALL COMPLY WITH NFPA 101 CH 7,
 MEANS OF EGRESS.
  
 38.2.2.2.3* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON
 PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE DETAILS OR A
 NOTE OF ACKNOWLEDGMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-09 Cont ID  
Sent By asangele Date 2023-03-09 Time 16:54 Rev Time 0.00
Received By asangele Date 2023-03-09 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-06 Cont ID  
Sent By mpeterso Date 2023-03-06 Time 13:33 Rev Time 0.00
Received By mpeterso Date 2023-02-27 Time 08:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-15 Cont ID  
Sent By asangele Date 2023-02-15 Time 16:04 Rev Time 0.00
Received By asangele Date 2023-02-15 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-11 Cont ID  
Sent By aoliver Date 2023-01-11 Time 08:21 Rev Time 0.00
Received By aoliver Date 2022-12-19 Time 09:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-03-03 Cont ID  
Sent By lmarchan Date 2023-03-03 Time 11:05 Rev Time 0.00
Received By lmarchan Date 2023-02-24 Time 09:32 Sent To  
Notes
2023-03-01 16:48:09RECEIPT MU-2023-008688 - $24,612.39 PAID
2023-02-24 09:32:49EMAILED IMPACT FOR REVIEW PER R MCPHERSON-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By rmcphers Date 2023-01-10 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 12:53 Sent To  
Notes
2023-01-10 12:54:02PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-03-01 Cont ID  
Sent By medwards Date 2023-03-01 Time 11:56 Rev Time 0.00
Received By medwards Date 2023-03-01 Time 11:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-02-07 Cont ID  
Sent By medwards Date 2023-02-07 Time 08:48 Rev Time 0.00
Received By medwards Date 2023-02-07 Time 08:48 Sent To  
Notes
2023-02-07 08:48:572ND REVIEW FMC
 PERMIT: 22110052
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 PROVIDE THE PREVIOUSLY REQUESTED MECHANICAL EQUIPMENT
 SIZING CALCULATIONS FROM 1ST CYCLE REVIEW BELOW:
  
 4) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-29 Cont ID  
Sent By medwards Date 2022-12-29 Time 15:11 Rev Time 0.00
Received By medwards Date 2022-12-29 Time 15:11 Sent To  
Notes
2022-12-29 15:11:301ST REVIEW FMC
 PERMIT: 22110052
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW ON THE ROOF DRAWING, M2, THAT THE RTU-1, CU-1
 AND CU-2 AND COOLER CONDENSER WILL MEET THE GUARD
 PROTECTION REQUIREMENTS OF FMC 306.5
  
 2) SHOW ON THE ROOF DRAWING, M2, THAT THE RTU-1, CU-1,
 CU-2 AND COOLER CONDENSER WILL MEET THE GUARD
 PROTECTION OF FMC 304.11
  
 3) ADD A NOTE ON THE DRAWING THAT THE REFRIGERATION
 WILL REQUIRE A SEPARATE PERMIT AND MECHANICAL REVIEW AS
 IT WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 4) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-02-28 Cont ID  
Sent By rwbrown Date 2023-02-28 Time 09:16 Rev Time 0.00
Received By rwbrown Date 2023-02-28 Time 09:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-02-21 Cont ID  
Sent By rwbrown Date 2023-02-21 Time 07:26 Rev Time 0.00
Received By rwbrown Date 2023-02-21 Time 07:26 Sent To  
Notes
2023-02-21 07:26:493RD PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. NOT ADDRESSED ---- 2020 1003.3.5.1 - PLEASE DETAIL
 YOUR GREASE WASTE CALCULATIONS AND NECESSITY.
  
 4. DONE
  
 5. DONE
  
 6. DONE
  
 ITEMS ADDRESSED BY OTHERS DOES NOT REMOVE IT FROM THE
 REQUIREMENTS OF THIS REVIEW. PLEASE ADDRESS THESE
 ITEMS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-02-07 Cont ID  
Sent By rwbrown Date 2023-02-07 Time 16:06 Rev Time 0.00
Received By rwbrown Date 2023-02-07 Time 16:02 Sent To  
Notes
2023-02-07 16:09:153RD PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. NOT ADDRESSED ---- 2020 1003.3.5.1 - PLEASE DETAIL
 YOUR GREASE WASTE CALCULATIONS AND NECESSITY.
  
 4. NOT ADDRESSED ------2017 WPB AMEND ??? 107.3 -- THE
 BACKFLOW DEVICE AT THE UTILITY CONNECTION AND THE
 GREASE TRAP REQUIRE SEPARATE PERMITS THAT ARE REQUIRED
 TO BE APPLIED FOR PRIOR TO ISSUANCE OF THE PRIMARY
 PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN APPLICATION
 ???TBD??? (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL COMPLY THAT PARTICULAR COMMENT.
  
 5. NOT ADDRESSED ------ 2017 WPB AMENDS 107.3.5.1.3 -
 PLEASE SUBMIT A SITE PLAN FOR THE LOCATION OF THE
 BACKFLOW AND GREASE TRAP.
  
 6. NOT ADDRESSED ------- 2017 WPB AMENDS
 107.3.5.1.3/2020 FPC 403.1.4 - SUBMIT A SITE PLAN THAT
 SHOWS THE OUTDOOR ASSEMBLLY AREA TO SHOW A LACK OF
 OUTDOOR SEATING OR ASSEMBLY AREA. IF THERE IS OUTDOOR
 SEATING OR ASSEMBLY AREA, PUBLIC RESTROOMS MAY BE
 REQUIRED BY 403.1.4
  
 ITEMS ADDRESSED BY OTHERS DOES NOT REMOVE IT FROM THE
 REQUIREMENTS OF THIS REVIEW. PLEASE ADDRESS THESE
 ITEMS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 13:37 Rev Time 0.00
Received By rwbrown Date 2022-12-30 Time 13:15 Sent To  
Notes
2022-12-30 13:39:201ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 403.3.2 - TOILET ROOMS SHALL NOT OPEN
 DIRECTLY INTO A ROOM USED FOR THE PREPARATION OF FOOD
 FOR SERVICE TO THE PUBLIC.
  
 2. 2020 FPC 607.1.1 - PLEASE SHOW A WATER HEATER DETAIL
 AND INCLUDE THE REQUIRED MIXING VALVE IN COMPLIANCE
 WITH ASSE 1017.
  
 3. 2020 1003.3.5.1 - PLEASE DETAIL YOUR GREASE WASTE
 CALCULATIONS AND NECESSITY.
  
 4. 2017 WPB AMEND ??? 107.3 -- THE BACKFLOW DEVICE AT
 THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION ???TBD???
 (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR
 SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 COMPLY THAT PARTICULAR COMMENT.
  
 5. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE SUBMIT A SITE
 PLAN FOR THE LOCATION OF THE BACKFLOW AND GREASE TRAP.
  
 6. 2017 WPB AMENDS 107.3.5.1.3/2020 FPC 403.1.4 -
 SUBMIT A SITE PLAN THAT SHOWS THE OUTDOOR ASSEMBLLY
 AREA TO SHOW A LACK OF OUTDOOR SEATING OR ASSEMBLY
 AREA. IF THERE IS OUTDOOR SEATING OR ASSEMBLY AREA,
 PUBLIC RESTROOMS MAY BE REQUIRED BY 403.1.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2023-01-10 Cont ID  
Sent By rmcphers Date 2023-01-10 Time 12:52 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 12:52 Sent To  
Notes
2023-01-10 12:52:56PRE MANUFACTURED BUILDING

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-06 Cont ID  
Sent By rmcphers Date 2023-03-06 Time 16:45 Rev Time 0.00
Received By rmcphers Date 2023-03-06 Time 16:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-03-06 Cont ID  
Sent By rmcphers Date 2023-03-06 Time 11:22 Rev Time 0.00
Received By rmcphers Date 2023-03-06 Time 11:21 Sent To  
Notes
2023-03-06 11:23:46SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE CIVIL DRAWINGS - C-05, C-06, C-07, C-08, C-09,
 C-12 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-02-07 Cont ID  
Sent By rmcphers Date 2023-02-07 Time 16:09 Rev Time 0.00
Received By rmcphers Date 2023-02-07 Time 16:09 Sent To  
Notes
2023-02-07 16:10:19SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING F1 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2023-02-07 08:50:00MECHANICAL SHEETS REQUIRE THE DIGITAL SIGNATURE OF THE
 DESIGNER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By rmcphers Date 2023-01-10 Time 12:51 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 12:51 Sent To  
Notes
2023-01-10 12:52:19SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING F1 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop Z ZONING
Rev No 4 Status P Date 2023-03-09 Cont ID  
Sent By asangele Date 2023-03-09 Time 16:54 Rev Time 0.00
Received By asangele Date 2023-03-09 Time 16:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-03-06 Cont ID  
Sent By asangele Date 2023-03-06 Time 12:06 Rev Time 0.00
Received By asangele Date 2023-03-06 Time 12:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-02-15 Cont ID  
Sent By asangele Date 2023-02-15 Time 16:04 Rev Time 0.00
Received By asangele Date 2023-02-15 Time 16:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-01-04 Cont ID  
Sent By asangele Date 2023-01-04 Time 17:00 Rev Time 0.00
Received By asangele Date 2023-01-04 Time 17:00 Sent To  
Notes
2023-01-04 17:19:52FAILED
 1/4/2022
  
 PLEASE PROVIDE A PROPERTY SURVEY WITH LABELED SETBACKS
 OF THE BUILDING. ADDITIONALLY THE PROPOSED USE BEING A
 COFFEE DRIVE THROUGH WILL MEET THE REQUIRED PARKING
 REQUIREMENTS. PLEASE CLEARLY IDENTIFY THE EMPLOYEE
 PARKING SPACES.
  
 ARTICLE XV. SECTION 94-486
 37. DRIVE THROUGH FACILITIES, EXCEPT RESTAURANTS AS
 PRINCIPAL USES
 1 PER EMPLOYEE FOR SHIFT WITH MOST EMPLOYEES, STACKING
 LANE TO ACCOMMODATE 5 CARS
  
  
 NEEDS TO PROVIDE THE GROSS BUILDING AREA AND SITE AREA.
  
 ARTICLE SECTION 94-145
 MAX. FAR WITH COMMMERICAL (C) FUTURE 0.75
  
  
 A SEPARATE PERMIT IS REQUIRED FOR:
  
 LANDSCAPE
 SIGNAGE
 AWNING
 MECHANICAL EQUIPMENT
  
  
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
  