Plan Review Details - Permit 22110045
Plan Review Stops For Permit 22110045
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-03 Cont ID  
Sent By rmcphers Date 2023-03-03 Time 15:52 Rev Time 0.00
Received By rmcphers Date 2023-03-03 Time 15:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-13 Cont ID  
Sent By rmcphers Date 2023-02-13 Time 16:50 Rev Time 0.00
Received By rmcphers Date 2023-02-13 Time 16:35 Sent To  
Notes
2023-02-13 16:48:52REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DOOR WIDTH OF 2' 8" DOES NOT ALLOW ACCESSIBILITY -
 FBC 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 2) SIGNED AND SEALED DRAWINGS NEED TO BE DIGITALLY
 SIGNED BY THE DESIGNER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-15 Cont ID  
Sent By mpeterso Date 2023-03-15 Time 09:12 Rev Time 0.00
Received By mpeterso Date 2023-03-15 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-26 Cont ID  
Sent By mpeterso Date 2023-01-26 Time 08:56 Rev Time 0.00
Received By mpeterso Date 2023-01-26 Time 08:56 Sent To  
Notes
2023-01-26 09:00:52ELECTRIC REVIEW FAILED
 1) IT APPEARS NOT ALL ELECTRIC WORK IS DETAILED ON
 FLOOR PLANS. EXAMPLE IS NOTE THAT STATES ALL RELOCATED
 DESKS TO RECIEVE POWER AND DATA. PLEASE PROVIDE A CLEAR
 AND ACCURATE WORK SCOPE AND DETAIL ANY ADDED, RELOCATED
 OR MODIFIED ELECTRIC WORK IN THE WORK SCOPE AND FLOOR
 PLAN. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2023-03-15 Cont ID  
Sent By mpeterso Date 2023-03-15 Time 09:13 Rev Time 0.00
Received By mpeterso Date 2023-03-15 Time 09:13 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status F Date 2023-01-26 Cont ID  
Sent By mpeterso Date 2023-01-26 Time 09:01 Rev Time 0.00
Received By mpeterso Date 2023-01-26 Time 09:01 Sent To  
Notes
2023-01-26 09:01:38ELECTRIC REVIEW FAILED
 1) IT APPEARS NOT ALL ELECTRIC WORK IS DETAILED ON
 FLOOR PLANS. EXAMPLE IS NOTE THAT STATES ALL RELOCATED
 DESKS TO RECIEVE POWER AND DATA. PLEASE PROVIDE A CLEAR
 AND ACCURATE WORK SCOPE AND DETAIL ANY ADDED, RELOCATED
 OR MODIFIED ELECTRIC WORK IN THE WORK SCOPE AND FLOOR
 PLAN. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-02 Cont ID  
Sent By clfranci Date 2023-03-02 Time   Rev Time 0.00
Received By clfranci Date 2023-03-02 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-17 Cont ID  
Sent By clfranci Date 2023-01-17 Time   Rev Time 0.00
Received By clfranci Date 2023-01-17 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-15 Cont ID  
Sent By mpeterso Date 2023-03-15 Time 09:13 Rev Time 0.00
Received By mpeterso Date 2023-03-01 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-13 Cont ID  
Sent By rmcphers Date 2023-02-13 Time 16:50 Rev Time 0.00
Received By rmcphers Date 2023-01-12 Time 14:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-03 Cont ID  
Sent By rmcphers Date 2023-03-03 Time 15:53 Rev Time 0.00
Received By rmcphers Date 2023-03-03 Time 15:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-26 Cont ID  
Sent By mpeterso Date 2023-01-26 Time 09:02 Rev Time 0.00
Received By mpeterso Date 2023-01-26 Time 09:02 Sent To  
Notes
2023-01-26 09:04:47SIGNATURE REVIEW FAILED
 1) PLANS SUBMITTED DETAIL AN ENGINEERS SEAL WITHOUT THE
 REQUIRED DIGITAL SIGNATURE. PLEASE CORRECT AS OUTLINED
 BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop Z ZONING
Rev No 2 Status P Date 2023-03-06 Cont ID  
Sent By asangele Date 2023-03-06 Time 15:58 Rev Time 0.00
Received By asangele Date 2023-03-06 Time 15:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-01-27 Cont ID  
Sent By ASangele Date 2023-01-27 Time 14:06 Rev Time 0.00
Received By asangele Date 2023-01-27 Time 14:06 Sent To  
Notes
***NONE***