| Plan Review Stops For Permit 22110045 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-03-03 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-03 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-03 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-13 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-13 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2023-02-13 16:48:52 | REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DOOR WIDTH OF 2' 8" DOES NOT ALLOW ACCESSIBILITY - | | | FBC 404.2.3 CLEAR WIDTH. | | | DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES | | | (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH | | | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF | | | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. | | | | | | 2) SIGNED AND SEALED DRAWINGS NEED TO BE DIGITALLY | | | SIGNED BY THE DESIGNER - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-15 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-15 |
Time |
09:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-01-26 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-26 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-26 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2023-01-26 09:00:52 | ELECTRIC REVIEW FAILED | | | 1) IT APPEARS NOT ALL ELECTRIC WORK IS DETAILED ON | | | FLOOR PLANS. EXAMPLE IS NOTE THAT STATES ALL RELOCATED | | | DESKS TO RECIEVE POWER AND DATA. PLEASE PROVIDE A CLEAR | | | AND ACCURATE WORK SCOPE AND DETAIL ANY ADDED, RELOCATED | | | OR MODIFIED ELECTRIC WORK IN THE WORK SCOPE AND FLOOR | | | PLAN. FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
2 |
Status |
P |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-15 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-15 |
Time |
09:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
F |
Date |
2023-01-26 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-26 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-26 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2023-01-26 09:01:38 | ELECTRIC REVIEW FAILED | | | 1) IT APPEARS NOT ALL ELECTRIC WORK IS DETAILED ON | | | FLOOR PLANS. EXAMPLE IS NOTE THAT STATES ALL RELOCATED | | | DESKS TO RECIEVE POWER AND DATA. PLEASE PROVIDE A CLEAR | | | AND ACCURATE WORK SCOPE AND DETAIL ANY ADDED, RELOCATED | | | OR MODIFIED ELECTRIC WORK IN THE WORK SCOPE AND FLOOR | | | PLAN. FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
clfranci |
Date |
2023-03-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
clfranci |
Date |
2023-03-02 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2023-01-17 |
|
|
Cont ID |
|
| Sent By |
clfranci |
Date |
2023-01-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
clfranci |
Date |
2023-01-17 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-15 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-01 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-13 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-12 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-03-03 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-03 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-03 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-01-26 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-26 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-26 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2023-01-26 09:04:47 | SIGNATURE REVIEW FAILED | | | 1) PLANS SUBMITTED DETAIL AN ENGINEERS SEAL WITHOUT THE | | | REQUIRED DIGITAL SIGNATURE. PLEASE CORRECT AS OUTLINED | | | BELOW. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-03-06 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-03-06 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-01-27 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-01-27 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-01-27 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|