Plan Review Details - Permit 22110021
Plan Review Stops For Permit 22110021
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-12-08 Cont ID  
Sent By cthroop Date 2022-12-08 Time 13:17 Rev Time 0.00
Received By cthroop Date 2022-12-08 Time 09:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-01-20 Cont ID  
Sent By cthroop Date 2023-01-20 Time 14:15 Rev Time 0.00
Received By cthroop Date 2023-01-20 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-08 Cont ID  
Sent By cthroop Date 2022-12-08 Time 13:23 Rev Time 0.00
Received By cthroop Date 2022-12-08 Time 09:34 Sent To  
Notes
2022-12-08 13:28:381ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: RESTROOMS SHALL COMPLY WITH THE 2020 FBC,
 ACCESSIBILITY, 7TH EDITION
  
 1. PROVIDE DEMENSIONS ON THE FLOOR PLAN PER FBC ACCESS.
 CHPT 6. CANNOT VERIFY ALL REQUIRED CLEARANCES.
  
 2. PROVIDE SIGNAGE PER FBC ACCESS. CHPT 7.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-01 Cont ID  
Sent By fgiaquin Date 2022-12-01 Time 19:35 Rev Time 0.00
Received By fgiaquin Date 2022-12-01 Time 18:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-06 Cont ID  
Sent By cwalker Date 2023-01-06 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-11-15 Cont ID  
Sent By cwalker Date 2022-11-15 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-20 Cont ID  
Sent By cthroop Date 2023-01-20 Time 14:15 Rev Time 0.00
Received By cthroop Date 2023-01-05 Time 14:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-08 Cont ID  
Sent By cthroop Date 2022-12-08 Time 13:28 Rev Time 0.00
Received By cthroop Date 2022-11-14 Time 10:23 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 16:58 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-01-06 Cont ID  
Sent By rwbrown Date 2023-01-06 Time 07:04 Rev Time 0.00
Received By rwbrown Date 2023-01-06 Time 07:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-30 Cont ID  
Sent By rwbrown Date 2022-11-30 Time 08:29 Rev Time 0.00
Received By rwbrown Date 2022-11-30 Time 08:20 Sent To  
Notes
2022-11-30 09:33:401ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FEX 604.1 - THE CLASSIFICATION OF WORK IS NOT A
 LEVEL 1 ALTERATION. RECONFIGURING THE FLOOR SPACE IN AN
 AREA OF MORE THAN 50 PERCENT OF THE BUILDING AREA IS A
 LEVEL 3 ALTERATION.
  
 1. 2020 FBC 454.1.6.1 - COULD YOU PLEASE ADD THE
 OCCUPANT LOAD CALCULATION TO VERIFY YOU ARE MEETING THE
 REQUIRED FIXTURES.
  
 2. 2020 FBC 454.1.6.1.4 - PLEASE SHOW THE REQUIRED HOSE
 BIBB (WITH A VACUUM BREAKER) OR SHOW AN ACCESSIBLE ONE
 WITHIN 25FT FOR CLEANING OF THE RESTROOMS.
  
 3. 2020 FAC 604.8.1.1 - PLEASE SHOW THE SIZE OF THE ADA
 WATER CLOSET COMPARTEMENT TO COMPLY WITH A 56"X60"
 COMPARTMENT.
  
 4. 2020 FPC 905.4 - THE VENTS SHOWN FOR THE WATER
 CLOSETS AND THE URINALS ARE NOT COMPLIANT. THE DRY VENT
 FOR A FIXTURE NEEDS TO RISE 6" ABOVE THE FLOOD LEVEL
 RIM OF THE FIXTURE(S) SERVED BEFORE GOING HORIZONTAL.
  
 5. 2020 FPC 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR
 THE LIMITING DEVICE REQUIRED FOR PUBLIC HANDWASHING
 FACILITIES AND TEMPERED WATER. THE DEVICE SHOULD
 CONFORM TO ASSE 1070.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-20 Cont ID  
Sent By cthroop Date 2023-01-20 Time 14:15 Rev Time 0.00
Received By cthroop Date 2023-01-20 Time 14:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-08 Cont ID  
Sent By cthroop Date 2022-12-08 Time 13:23 Rev Time 0.00
Received By cthroop Date 2022-12-08 Time 09:34 Sent To  
Notes
***NONE***