| Plan Review Stops For Permit 22110014 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-13 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-13 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-13 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-12 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2022-12-13 07:48:35 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: PLAN SHEETS ARE MIS-LABLED: | | | | | | 1. SHEETS 2 THRU 5 ARE FLOOR PLANS NOT SITE PLANS. | | | 2. SHEETS 6 THRU 19 ARE 3-D ELEVATION RENDERINGS, NOT | | | FLOOR PLANS. | | | | | | PLEASE LABEL YOUR PLAN SHEETS ACCORDING TO STANDARD | | | NAMING CONVENTIONS: | | | | | | 4. PROVIDE A FLOOR PLAN OF THE ENTIRE STRUCTURE. | | | IDENTIFY THE LOCATION OF WORK. (KITCHEN AND M/BATH) | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 5. PROVIDE SMOKE ALARMS. LOCATE ON FLOOR PLAN. | | | FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A | | | BUILDING. | | | | | | SMOKE ALARMS | | | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-11 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-11 |
Time |
13:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-12-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-02 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-02 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2022-12-02 14:07:15 | ELECTRIC REVIEW FAILED | | | 1) PLANS LACK THE CLARITY REQUIRED TO DO A COMPLETE | | | REVIEW. PLEASE PREPARE DRAWINGS WITH SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. IT MAY BE HELPFUL TO PREPARE TWO LARGER | | | DRAWINGS, ONE FOR LIGHTING AND ONE FOR POWER TO ALLOW | | | ENOUGH ROOM ON THE DRAWINGS TO CLEARLY SHOW THE | | | ELECTRIC WORK BEING PROPOSED. FBC 107.2.1.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-13 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-09 |
Time |
08:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-13 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-17 |
Time |
08:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-10 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-10 |
Time |
12:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-18 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-18 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2022-11-18 14:58:33 | IS THE EXISTING HOOD IN THE KITCHEN EXHAUSTED TO THE | | | OUTDOORS? IS THE NEW HOOD EXHAUST TO THE OUTDOORS? WHAT | | | IS THE CFM'S OF THE HOOD MOTOR? FRC M1503.4 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-10 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-10 |
Time |
10:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-11-21 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-11-21 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2022-11-21 12:38:15 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22110014 | | | 11/21/22 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS SP-1,2,3,4: THE KITCHEN AND BATH BEFORE AND | | | AFTER DRAWINGS INDICATE RELOCATED SINK AND DISHWASHER, | | | AND TUB TO SHOWER CONVERSION WITH NEW DRAIN LOCATION. | | | PLEASE PROVIDE SANITARY RISER DRAWINGS- SEC. 107.3.5.3 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-13 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-13 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-13 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-12 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2022-12-13 07:30:23 | 1ST SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | | | | 1.THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD | | | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN | | | SHEETS UNDER THEIR AUTHORITY. | | | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, SECTION 107.2.1. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|