Plan Review Details - Permit 22101437
Plan Review Stops For Permit 22101437
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 14:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-05 Cont ID  
Sent By rmcphers Date 2022-12-05 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2022-12-05 Time 14:37 Sent To  
Notes
2022-12-05 14:39:54EXTERIOR WALL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
  
 1) PLEASE SHOW THE EXTERIOR PLYWOOD ATTACHMENT DETAILS
 (FASTNER TYPE, SIZE, ON CENTER SPACING ETC.) FBC 2304.6
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-23 Cont ID  
Sent By rmcphers Date 2022-11-22 Time 16:46 Rev Time 0.00
Received By rmcphers Date 2022-11-22 Time 16:37 Sent To  
Notes
2022-11-22 16:46:22EXTERIOR WALL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
  
 1) PLEASE PROVIDE AN EXTERIOR WALL DETAIL THAT MATCHES
 THE EXISTING - 107.2.4 2017 CHAPTER 1 WPB AMENDMENTS
 FRAMING TYPE (WOOD, METAL)?
 FRAMING SPACING O.C.
 SHEATHING Y/N AND IS YES WHAT THICKNESS
  
 2) PLEASE SHOW LATH FASTENERS TO COMPLY WITH R703.7.1
  
 3) FBC R703.7.2 PLASTER.
 PLASTERING WITH CEMENT PLASTER SHALL BE NOT LESS THAN
 THREE COATS WHERE APPLIED OVER ANY TYPE OF
 CODE-APPROVED LATH AND SHALL BE NOT LESS THAN TWO COATS
 WHERE DIRECTLY APPLIED OVER MASONRY, CONCRETE, CLAY
 BRICK, STONE OR TILE. IF THE PLASTER SURFACE IS
 COMPLETELY COVERED BY VENEER OR OTHER FACING MATERIAL
 OR IS COMPLETELY CONCEALED, PLASTER APPLICATION NEED BE
 ONLY TWO COATS, PROVIDED THE TOTAL THICKNESS IS AS SET
 FORTH IN TABLE R702.1(1).
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-05 Cont ID  
Sent By rmcphers Date 2022-12-05 Time 14:40 Rev Time 0.00
Received By rmcphers Date 2022-12-02 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-23 Cont ID  
Sent By rmcphers Date 2022-11-22 Time 16:46 Rev Time 0.00
Received By rmcphers Date 2022-11-01 Time 12:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 14:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-06 Cont ID  
Sent By jgomez Date 2022-12-06 Time 14:27 Rev Time 0.00
Received By jgomez Date 2022-12-06 Time 14:27 Sent To  
Notes
2022-12-06 14:31:00HARD COPY OF DRAWING A1 UPLOADED TO PROJECTDOX ON
 12/2/2022 HAS ENGINEER'S SEAL AND WET SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-11-22 Cont ID  
Sent By rmcphers Date 2022-11-22 Time 16:46 Rev Time 0.00
Received By rmcphers Date 2022-11-22 Time 16:46 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved