| 2023-01-09 15:03:13 | 2ND REVIEW FMC |
| | PERMIT: 22101347 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A COMPLETE SCOPE OF WORK FOR THIS TENANT |
| | SPACE INCLUDING THE PREVIOUS LEGAL OCCUPANCY AND USE |
| | AND THE PROPOSED OCCUPANCY AND USE. PROVIDE A COMPLETE |
| | SET OF PLANS FOR THIS NEW RESTAURANT INCLUDING ALL |
| | TRADES. FBC 107.3.5 |
| | |
| | 2) THIS IS A NEW INSTALLATION FOR THIS HOOD, GREASE |
| | DUCT AND MAKE-UP AIR. WHY IS THIS HOOD BEING INSTALLED? |
| | WHAT TYPE OF APPLIANCES ARE TO BE USED UNDER THIS NEW |
| | HOOD. FBC 107.3.5 |
| | |
| | 3) PLEASE SHOW THE EXHAUST TERMINATION LOCATION WILL |
| | MEET THE CLEARANCES IN FMC 506.3.13.3 |
| | |
| | 506.3.13.3 TERMINATION LOCATION. EXHAUST OUTLETS SHALL |
| | BE LOCATED NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY |
| | FROM PARTS OF THE SAME OR CONTIGUOUS BUILDINGS, |
| | ADJACENT BUILDINGS AND ADJACENT PROPERTY LINES AND |
| | SHALL BE |
| | LOCATED NOT LESS THAN 10 FEET (3048 MM) ABOVE THE |
| | ADJOINING GRADE LEVEL. EXHAUST OUTLETS SHALL BE LOCATED |
| | NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY FROM OR |
| | NOT LESS THAN 3 FEET (914 MM) ABOVE AIR INTAKE OPENINGS |
| | INTO ANY BUILDING. |
| | |
| | 4) PLEASE SHOW THAT ANY EQUIPMENT PLACED WITHIN 10 FOOT |
| | OF THE ROOFS EDGE WILL HAVE GUARD PROTECTION BASED ON |
| | FMC 304.11 |
| | |
| | 5) PROVIDE THE AIR BALANCE REPORT FOR THIS TENANT |
| | SPACE. FMC 508.1.2 |
| | |
| | 6) PLEASE SHOW THAT THE MAKE-UP AIR TEMPERATURE MEETS |
| | THE 10 DEGREE REQUIREMENT OF FMC 508.1.1 |
| | |
| | 7) PROVIDE CALCULATIONS THAT THE MECHANICAL SYSTEM IS |
| | DESIGNED FOR THE LOAD OF THIS NEW RESTAURANT. FMC 312.1 |
| | |
| | 8) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS |
| | RESTAURANT. FMC 403.3.1.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |