Plan Review Details - Permit 22101241
| Plan Review Stops For Permit 22101241 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-12-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-12-08 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-12-08 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2022-12-08 10:43:00 | PARCEL READDRESSED FROM 150 CLEARWATER DR TO 134 | | | CLEARWATER DR UPDATED PERMIT |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-11-03 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-11-03 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2022-11-03 08:06:20 | PER PPRC REVIEW Z22040014 APPLICANT NEEDS TO CONTACT | | | [email protected] OR CALL 561-805-6659. NEW ADDRESSES NEED | | | TO BE ESTABLISHED FOR THIS PROJECT. PLEASE PROVIDE A | | | SITE PLAN SHOWING ALL THE ENTRANCES TO THE DIFFERENT | | | BUILDINGS, ALSO PLEASE PROVIDE A GROUND FLOOR PLAN. FYI | | | THE ADDRESS OF 150 CLEARWATERDR MAY NOT BE AN | | | APPROPRIATE ADDRESS. UNIT ADDRESSES ALSO NEED TO BE | | | ESTABLISHED. |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
4 |
Status |
P |
Date |
2023-06-27 |
|
|
Cont ID |
|
| Sent By |
swelter |
Date |
2023-06-27 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
swelter |
Date |
2023-06-27 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2023-06-27 10:51:13 | APPLICANT SATISFIED PERMIT #22102241 - 9 STORY GARAGE - | | | ELECTED OPTION #2 RCVD. 6.20.23 |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
3 |
Status |
P |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
swelter |
Date |
2023-01-13 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
swelter |
Date |
2023-03-07 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2023-01-13 10:12:22 | APPLICANT SATISFIED PUBLIC ART REQUIREMENT - OPTION 2 | | | | | | AS THE APPLICANT HAS SUBMITTED FOR PERMITTING, | | | THEREFORE THE APPLICANT MUST PROVIDE A COMPLETE ART | | | ASSESSMENT APPLICATION ALONG WITH EVIDENCE OF ESCROW TO | | | OBTAIN A PERMIT. AN ART ASSESSMENT APPLICATION WAS | | | EMAILED TO BRETT COLEMAN ON 1.13.2023 | | | | | | CONTACT [email protected] | | | |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
F |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
swelter |
Date |
2022-12-01 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
swelter |
Date |
2022-12-01 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2022-12-01 14:37:49 | ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $500,000 ARE SUBJECT TO THE | | | PUBLIC ART REQUIREMENT PURSUANT TO SEC. 78-129 OF THE | | | CODE OF ORDINANCES. | | | | | | ART ASSESSMENT APPLICATION SENT 12.01.22 MUST BE | | | COMPLETED AND RETURNED WITH 1% ESCROW OR .75% PUBLIC | | | ART FUND CONTRIBUTION AT TIME OF BUILDING PERMIT FEES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2023-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-05 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-05 |
Time |
11:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-22 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-22 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-15 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-15 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2023-03-15 16:15:14 | 9 STORY PARKING GARAGE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PAGE 8 OF THE THRESHOLD BUILDING INSPECTOR FORM | | | NEEDS TO BE FILLED OUT AND SIGNED BY THE CONTRACTOR - | | | THRESHOLD BUILDING - SPECIAL INSPECTOR FORMS NEED TO BE | | | FILLED OUT - PLEASE READ AND FILL OUT THE REQUIRED | | | DOCUMENTS PER THE "GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT | | | INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | 2) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = NEED TO | | | CHOOSE A ROOFING SYSTEM IN THE PRODUCT APPROVAL THAT | | | SHOWS THE REQUIRED WIND DESIGN PRESSURE - PLEASE CIRCLE | | | THE ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL - | | | IF NEEDED PLEASE PROVIDE ADDITIONAL ATTACHMENT DETAILS | | | FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND | | | 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE THEN THE | | | CHOSEN ROOFING SYSTEM - SEE NOTES ON THE PRODUCT | | | APPROVAL. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-13 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-13 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2023-02-13 13:13:13 | 9 STORY PARKING GARAGE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PAGE 8 OF THE THRESHOLD BUILDING INSPECTOR FORM | | | NEEDS TO BE FILLED OUT AND SIGNED BY THE CONTRACTOR - | | | THRESHOLD BUILDING - SPECIAL INSPECTOR FORMS NEED TO BE | | | FILLED OUT - PLEASE READ AND FILL OUT THE REQUIRED | | | DOCUMENTS PER THE "GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT | | | INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | 2) PAGE 6 OF THE THRESHOLD INSPECTOR FORM - HAS BEEN | | | DIGITALLY SIGNED BY THE THRESHOLD INSPECTOR - BUT DOES | | | NOT SHOW IN ADOBE READER AS DIGITALLY SIGNED. | | | | | | 3) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = NEED TO | | | CHOOSE A ROOFING SYSTEM IN THE PRODUCT APPROVAL THAT | | | SHOWS THE REQUIRED WIND DESIGN PRESSURE - PLEASE CIRCLE | | | THE ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL - | | | IF NEEDED PLEASE PROVIDE ADDITIONAL ATTACHMENT DETAILS | | | FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND | | | 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE THEN THE | | | CHOSEN ROOFING SYSTEM - SEE NOTES ON THE PRODUCT | | | APPROVAL. | | | | | | 4) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE LIGHT | | | WEIGHT CONCRETE - FBC 1917.2.1 | | | APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF | | | DECKS SHALL BE BY APPLICATORS APPROVED BY THE | | | LIGHT-WEIGHT INSULATING CONCRETE DECK MANUFACTURER. | | | PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT | | | INSULATING CONCRETE SYSTEMS. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-30 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-27 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2023-01-27 15:42:35 | 9 STORY PARKING GARAGE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE THRESHOLD FORM PROVIDED IS FOR A DIFFERENT CITY | | | - THRESHOLD BUILDING - SPECIAL INSPECTOR FORMS NEED TO | | | BE FILLED OUT - PLEASE READ AND FILL OUT THE REQUIRED | | | DOCUMENTS PER THE "GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT | | | INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | 2) DRAWING A0-002 THE PARKING CALCS. SAY 4 ACCESSIBLE | | | PARKING SPACES FOR THE GROUND FLOOR - DRAWING A1-101 | | | SHOWS 6 PLEASE CLARIFY - ARE ALL ACCESSIBLE SPACES ON | | | ALL FLOORS "VAN" ACCESSIBLE? | | | | | | 3) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = NEED TO | | | CHOOSE A ROOFING SYSTEM IN THE PRODUCT APPROVAL THAT | | | SHOWS THE REQUIRED WIND DESIGN PRESSURE - PLEASE CIRCLE | | | THE ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL - | | | IF NEEDED PLEASE PROVIDE ADDITIONAL ATTACHMENT DETAILS | | | FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND | | | 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE THEN THE | | | CHOSEN ROOFING SYSTEM - SEE NOTES ON THE PRODUCT | | | APPROVAL. | | | | | | 4) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE LIGHT | | | WEIGHT CONCRETE - FBC 1917.2.1 | | | APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF | | | DECKS SHALL BE BY APPLICATORS APPROVED BY THE | | | LIGHT-WEIGHT INSULATING CONCRETE DECK MANUFACTURER. | | | PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT | | | INSULATING CONCRETE SYSTEMS. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-09 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-09 13:09:31 | 9 STORY PARKING GARAGE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A SOIL REPORT FBC 1803 | | | | | | 2) DRAWING S000 SHOWS WIND DESIGN SPEED AS 130 - SHOULD | | | BE 170 MPH PER FBC WPB SECTION 120 | | | | | | 3) STRUCTURAL CALCULATIONS - WIND DESIGN CALCULATION | | | PROVIDED SHOW ASCE 7-10 USED FOR WIND DESIGN - SHOULD | | | BE ASCE 7-16 PER FBC CHAPTER 35 | | | | | | 4) THRESHOLD BUILDING - SPECIAL INSPECTOR FORMS NEED TO | | | BE FILLED OUT - PLEASE READ AND FILL OUT THE REQUIRED | | | DOCUMENTS PER THE "GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT | | | INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | 5) DRAWING A0-002 SHOWS 4 ACCESSIBLE PARKING SPACES ON | | | 2ND FLOOR - THE PARKING CALCS. SAY 2 ACCESSIBLE PARKING | | | SPACES - (3RD THROUGH 8TH FLOORS SHOW 5 ACCESSIBLE | | | PARKING SPACES BUT THE PARKING CALCS. SHOW 4 ACCESSIBLE | | | PARKING SPACES) - PLEASE CLARIFY - THE ACCESSIBLE | | | PARKING SPACES SHOWN ON THE A1 FLOOR PLANS PROVIDED | | | NEED TO MATCH THE ACCESSIBLE PARKING SPACES SHOWN ON | | | DRAWING A0-002 | | | | | | 6) PRODUCT APPROVALS 16090604 ROOFING AND 19070804 ES | | | 9000 DOORS - DID NOT COMPLETELY UPLOAD TO PROJECTDOX - | | | PLEASE UPLOAD THESE TO PROJECTDOX AGAIN. | | | | | | 7) DRAWINGS S000, S001, S003, S004, S005, S100, S102, | | | S103, S104,S105, S107, S109, S110, S111, S112, S114, | | | S115, S117, S500, S601, S602 DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-30 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-29 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2022-11-30 15:11:52 | 9 STORY PARKING GARAGE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A SOIL REPORT FBC 1803 | | | | | | 2) DRAWING A6-100 - PLEASE SHOW THE AMBULANCE STRETCHER | | | DIMENSIONS IN THE ELEVATOR PER FBC 3002.4 ELEVATOR CAR | | | TO ACCOMMODATE AMBULANCE STRETCHER. | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | (7620 MM), MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE | | | PASSENGER ELEVATOR THAT IS OPERATIONAL FOR BUILDING | | | OCCUPANTS AND FIRE DEPARTMENT EMERGENCY ACCESS TO ALL | | | FLOORS. THE ELEVATOR CAR SHALL BE OF SUCH A SIZE AND | | | ARRANGEMENT TO ACCOMMODATE AN AMBULANCE STRETCHER 24 | | | INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS | | | THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, | | | OPEN POSITION AND SHALL BE IDENTIFIED BY THE | | | INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES | | | (STAR OF LIFE). THE SYMBOL SHALL BE NOT LESS THAN 3 | | | INCHES (76 MM) IN HEIGHT AND SHALL BE PLACED INSIDE ON | | | BOTH SIDES OF THE HOISTWAY DOOR FRAME. | | | | | | 3) PLEASE PROVIDE THE STAIR SMOKE CONTROL DETAILS - FBC | | | 909.4 ANALYSIS. | | | A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE | | | CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF | | | OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS | | | OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE | | | SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT | | | NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS | | | 909.4.1 THROUGH 909.4.7. | | | | | | 4) PLEASE PROVIDE THE ELEVATOR SHAFT PRESSURIZATION | | | DETAILS - FBC 909.21.2 RATIONAL ANALYSIS. | | | A RATIONAL ANALYSIS COMPLYING WITH SECTION 909.4 SHALL | | | BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. | | | | | | 5) PLEASE SHOW RESTROOM WALL FINISHES TO COMPLY WITH | | | FBC 1210.2.2 WALLS AND PARTITIONS. | | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT | | | CONSIDERED A HARD SURFACE) | | | | | | 6) PLEASE SHOW THE WALL FINISH SURROUNDING THE MOP SINK | | | TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS. | | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT | | | CONSIDERED A HARD SURFACE) | | | | | | 7) DRAWING A3-300 - DETAILS 6 AND 9 SAY "TREADS" SHOULD | | | SAY "RISERS" | | | | | | 8) DRAWING A3-300 - DETAILS SHOWING TREADS SHOULD SHOW | | | THE TREAD WIDTHS - FBC 1011.5.2 | | | | | | 9) DRAWING A3-301 - DETAILS 2,7,4,1, NEED TO SHOW THE | | | TREAD WIDTHS - FBC 1011.5.2 | | | | | | 10) DRAWING A3-302 - DETAILS 6 AND 8 - NEED TO SHOW THE | | | TREAD WIDTHS - FBC 1011.5.2 | | | | | | 11) DRAWING A3-302 - DETAILS 9 AND 10 - SAYS "TREADS" | | | SHOULD SAY "RISERS". | | | | | | 12) DRAWING A3-303 DETAIL 4 - PLEASE SHOW THE TREAD | | | WIDTHS - FBC 1011.5.2 | | | | | | 13) DRAWING A3-305 DETAIL 3 AND 6 - SAYS "TREADS" | | | SHOULD SAY "RISERS". | | | | | | 14) LIFE SAFETY DRAWINGS NEED TO SHOW STAIR ENCLOSURE | | | "NS02" AS FIRE RATED FBC 713.4 | | | | | | 15) PLEASE PROVIDE THE "OPEN GARAGE" VENTILATION | | | CALCULATIONS FOR EACH TIER PER - FBC 406.5.2 OPENINGS. | | | FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF | | | THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS | | | ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN | | | EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20 | | | PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER. | | | THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE | | | PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40 | | | PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS | | | SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY | | | DISTRIBUTED OPENINGS. | | | | | | 16) PLEASE SHOW THE WINDOW AND DOOR OPENING WIND DESIGN | | | PRESSURES - FBC 1603.1.4 | | | | | | 17) PLEASE SHOW THE ROOFING SYSTEMS AND THE REQUIRED | | | WIND DESIGN PRESSURES - FBC 1609.5.1 | | | | | | 18) PLEASE SHOW ROOF DRAINAGE - FBC 1503.4 | | | | | | 19) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) FOR THE EXTERIOR WINDOWS, | | | DOORS AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED | | | TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING | | | DESIGNER OF RECORD (UNLESS LISTED ON THE DRAWINGS) - | | | FBC WPB 107.3.4 | | | | | | 20) DRAWING S000 SHOWS WIND DESIGN SPEED AS 130 - | | | SHOULD BE ALT 170 MPH PER FBC WPB SECTION 120 | | | | | | 21) WIND DESIGN CALCULATION PROVIDED SHOW ASCE 7-10 | | | USED FOR WIND DESIGN - SHOULD BE ASCE 7-16 PER FBC | | | CHAPTER 35 | | | | | | 22) THRESHOLD BUILDING - PROVIDE THE FOLLOWING | | | STATEMENT ON THE DRAWINGS - FBC WPB 110.8.4.4 ALL PLANS | | | FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND | | | SEALED | | | BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A | | | STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR | | | ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS | | | COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND | | | THE APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY | | | THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND | | | CHAPTER 633. FLORIDA STATUTES. | | | | | | 23) THRESHOLD BUILDING - SPECIAL INSPECTOR FORMS NEED | | | TO BE FILLED OUT - PLEASE READ AND FILL OUT THE | | | REQUIRED DOCUMENTS PER THE "GUIDELINES AND POLICIES FOR | | | PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND | | | RESIDENT INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A | | | COPY. | | | | | | 24) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW | | | THE TOILET REAR GRAB BAR LOCATION DIMENSIONS FROM THE | | | CENTER OF THE TOILET - FBC A 604.5.2 REAR WALL. | | | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG | | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 | | | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. | | | | | | 25) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW | | | THE TOILET PAPER HOLDER LOCATION DIMENSIONS FROM THE | | | FACE OF THE TOILET PER FBC A 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. | | | | | | 26) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW | | | THE MAXIMUM HEIGHT OF THE GRAB BARS TO THE TOP OF THE | | | GRIPPING SURFACE NOT THE CENTER OF THE BAR AS SHOWN - | | | FBC A 609.4 POSITION OF GRAB BARS. | | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | | THE GRIPPING SURFACE, | | | | | | 27) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE USE | | | THE WORDS "REFLECTIVE SURFACE" WHEN REFERRING TO THE | | | DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE MIRROR - | | | FBC A 603.3 MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | 28) DRAWING A0-002 SHOWS 4 ACCESSIBLE PARKING SPACES ON | | | 2ND FLOOR - THE PARKING CALCS. SAY 2 - (3RD THROUGH 8TH | | | FLOORS SHOW 5 BUT THE PARKING CALCS. SHOW 4) - PLEASE | | | CLARIFY - THE A1 FLOOR PLANS PROVIDED NEED TO MATCH | | | A0-002 | | | | | | 29) DRAWING A1-200 - PARKING SPACE "005" PLEASE SHOW | | | THE ACCESSIBLE ROUTE TO AN ENTRY FROM THE PARKING | | | ACCESS AISLE THAT DOESN'T LEAD BEHIND ANOTHER PARKED | | | CAR FBC A 208.3.1 ALL SPACES MUST BE LOCATED ON AN | | | ACCESSIBLE ROUTE THAT IS AT LEAST 44 INCHES (1118 MM) | | | WIDE AND SO THAT USERS ARE NOT COMPELLED TO WALK OR | | | WHEEL BEHIND PARKED VEHICLES EXCEPT BEHIND HIS OR HER | | | OWN VEHICLE. | | | | | | 30) 1) DRAWINGS LS-1, S000,S001, S002, S100, S101, | | | S102, S103, S104,S105, S107, S108, S109, S110, S111, | | | S112, S115, S116, S200, S300, S400, S501, S601, S602 DO | | | NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-01-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-12 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-11 |
Time |
16:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-12-01 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-12-01 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2022-12-01 14:39:19 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NO LOAD CALCULATIONS SHOWN 215.5 | | | | | | 220.1 SCOPE. | | | | | | THIS ARTICLE PROVIDES REQUIREMENTS FOR CALCULATING | | | BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS. PART I | | | PROVIDES GENERAL REQUIREMENTS FOR CALCULATION METHODS. | | | PART II PROVIDES CALCULATION METHODS FOR BRANCH-CIRCUIT | | | LOADS. PARTS III AND IV PROVIDE CALCULATION METHODS FOR | | | FEEDER AND SERVICE LOADS. PART V PROVIDES CALCULATION | | | METHODS FOR FARM LOADS. | | | | | | 220.40 GENERAL. | | | | | | THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE | | | LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS | | | SUPPLIED, AS DETERMINED BY PART II OF THIS ARTICLE, | | | AFTER ANY APPLICABLE DEMAND FACTORS PERMITTED BY PART | | | III OR IV OR REQUIRED BY PART V HAVE BEEN APPLIED. | | | | | | | | | 2) NO RISER DIIAGRAM SHOWN 215.5 | | | | | | 215.5 DIAGRAMS OF FEEDERS. | | | | | | IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, A | | | DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED PRIOR | | | TO THE INSTALLATION OF THE FEEDERS. SUCH A DIAGRAM | | | SHALL SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR | | | OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL | | | CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE | | | DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING | | | DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO | | | BE USED. | | | | | | | | | 3) NO FAULT CURRENT CALCULATION SHOWN 110.9 | | | | | | 110.9 INTERRUPTING RATING. | | | | | | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS | | | SHALL HAVE AN INTERRUPTING RATING AT NOMINAL CIRCUIT | | | VOLTAGE AT LEAST EQUAL TO THE CURRENT THAT IS AVAILABLE | | | AT THE LINE TERMINALS OF THE EQUIPMENT. | | | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT OTHER THAN | | | FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING AT | | | NOMINAL CIRCUIT VOLTAGE AT LEAST EQUAL TO THE CURRENT | | | THAT MUST BE INTERRUPTED. | | | | | | | | | 4) PANELS G2A,B THROUGH GA,B LOADS FIGURE AT 100% WHEN | | | THEY SHALL BE AT 125% 625.41 | | | | | | 625.41 OVERCURRENT PROTECTION. | | | | | | OVERCURRENT PROTECTION FOR FEEDERS AND BRANCH CIRCUITS | | | SUPPLYING EQUIPMENT SHALL BE SIZED FOR CONTINUOUS DUTY | | | AND SHALL HAVE A RATING OF NOT LESS THAN 125 PERCENT OF | | | THE MAXIMUM LOAD OF THE EQUIPMENT. WHERE NONCONTINUOUS | | | LOADS ARE SUPPLIED FROM THE SAME FEEDER, THE | | | OVERCURRENT DEVICE SHALL HAVE A RATING OF NOT LESS THAN | | | THE SUM OF THE NONCONTINUOUS LOADS PLUS 125 PERCENT OF | | | THE CONTINUOUS LOADS. | | | | | | 625.42 RATING. | | | | | | THE EQUIPMENT SHALL HAVE SUFFICIENT RATING TO SUPPLY | | | THE LOAD SERVED. ELECTRIC VEHICLE CHARGING LOADS SHALL | | | BE CONSIDERED TO BE CONTINUOUS LOADS FOR THE PURPOSES | | | OF THIS ARTICLE. WHERE AN AUTOMATIC LOAD MANAGEMENT | | | SYSTEM IS USED, THE MAXIMUM EQUIPMENT LOAD ON A SERVICE | | | AND FEEDER SHALL BE THE MAXIMUM LOAD PERMITTED BY THE | | | AUTOMATIC LOAD MANAGEMENT SYSTEM. | | | | | | | | | 5) SITE LIGHTING, GENERATOR, FIRE ALARM, AND ALL LOW | | | VOLTAGE SYSTEMS REQUIRE SEPARATE PERMITS AND PLANS. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
7 |
Status |
P |
Date |
2023-05-31 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
2023-05-31 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
2023-05-31 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
6 |
Status |
F |
Date |
2023-04-12 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
2023-04-12 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
2023-04-12 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2023-04-12 14:05:29 | UNDER FORMAL ENGINEERING SUBMITTAL REVIEW. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
F |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2023-03-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2023-03-20 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2023-02-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2023-02-13 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-02-13 12:10:57 | UNDER FORMAL ENGINEERING SUBMITTAL REVIEW. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2023-01-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2023-01-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-30 11:00:09 | FORMAL ENGINEERING SUBMITTAL REQUIRED AFTER SITE PLAN | | | APPROVAL. | | | | | | THANKS, | | | RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES | | | DEPT., 561-494-1098, FAX: 561-494-1116 [email protected] | | | FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-12-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-12-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-12-27 08:39:33 | FORMAL ENGINEERING SUBMITTAL REQUIRED AFTER SITE PLAN | | | APPROVAL. | | | | | | THANKS, | | | RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES | | | DEPT., 561-494-1098, FAX: 561-494-1116 [email protected] | | | FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-11-07 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
2022-11-07 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-11-07 13:45:25 | FORMAL ENGINEERING SUBMITTAL REQUIRED AFTER SITE PLAN | | | APPROVAL. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2023-03-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2023-01-24 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2023-01-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-12-22 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-12-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-11-02 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-11-02 12:20:02 | FIRE REVIEW COMMENTS: | | | | | | (1) FIRE DEPARTMENT CONNECTIONS SHALL NOT BE LOCATED | | | MORE THAN 100 FEET FROM THE NEAREST FIRE HYDRANT | | | CONNECTED TO AN APPROVED WATER SUPPLY PER THE | | | REQUIREMENTS OF NFPA 14. | | | | | | (2) PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, AND | | | NFPA 101 FOR THE APPLICABLE OCCUPANCY CHAPTER TO | | | INCLUDE CHAPTER 42 (STORAGE OCCUPANCIES). | | | | | | (3) NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM AND NFPA 14 | | | COMPLIANT STANDPIPE SYSTEM SHALL HAVE SEPARATE SHOP | | | DRAWINGS TO BE SUBMITTED AND APPROVED PRIOR TO | | | INSTALLATION. TEMPORARY STANDPIPES ARE REQUIRED WHEN | | | THE BUILDING REACHES THREE LEVELS OR 35??? IN HEIGHT | | | WHILE BEING CONSTRUCTED. | | | | | | (4) SEVERAL REFERENCES TO CITY OF MIAMI, OR | | | HEATHER/OCEAN ADDRESSING. CORRECT FOR JURISDICTION OF | | | CITY OF WEST PALM BEACH, AND CORRECT STREET ADDRESSING. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-13 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-04-03 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-03-29 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-13 |
Time |
15:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-03-07 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-02-09 |
Time |
07:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-02-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-02-07 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-23 |
Time |
07:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-01-13 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-12-21 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-12-16 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-12-16 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-11-01 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-06-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-06-21 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-04-10 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2023-06-21 15:59:59 | RECEIPT MU-2023-017209 - $477,347.46 PAID | | 2023-04-10 08:55:24 | IMPACT FEE QUEST UPLOADED. PBCGOV EMAILED AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-30 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-30 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2022-11-30 15:13:43 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2023-02-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-17 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-17 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-01-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-31 |
Time |
06:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-31 |
Time |
06:17 |
Sent To |
|
|
| Notes |
| 2023-01-31 06:22:08 | THE ENCLOSED PARKING GARAGE SHALL MEET FMC 404.1 BELOW. | | | THE FANS SHALL NOT BE OFF. | | | | | | 404.1 ENCLOSED PARKING GARAGES. MECHANICAL VENTILATION | | | SYSTEMS FOR ENCLOSED PARKING GARAGES SHALL OPERATE | | | CONTINUOUSLY OR SHALL BE AUTOMATICALLY OPERATED BY | | | MEANS OF CARBON MONOXIDE DETECTORS APPLIED IN | | | CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS. CARBON | | | MONOXIDE DETECTORS SHALL BE INSTALLED 3 TO 5 FEET ABOVE | | | FLOOR LEVEL AND NITROGEN DIOXIDE DETECTORS SHALL BE | | | INSTALLED 1 FOOT BELOW CEILING LEVEL. SUCH DETECTORS | | | SHALL BE LISTED IN ACCORDANCE WITH UL 2075 AND | | | INSTALLED IN ACCORDANCE WITH THEIR LISTING AND THE | | | MANUFACTURERS??? INSTRUCTIONS. AUTOMATIC OPERATION | | | SHALL CYCLE THE VENTILATION SYSTEM BETWEEN THE | | | FOLLOWING TWO MODES OF OPERATION: | | | | | | 1. FULL-ON AT AN AIRFLOW RATE OF NOT LESS THAN 0.75 CFM | | | PER SQUARE FOOT OF THE FLOOR AREA SERVED. | | | | | | 2. STANDBY AT AN AIRFLOW RATE OF NOT LESS THAN 0.05 CFM | | | PER SQUARE FOOT OF THE FLOOR AREA SERVED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-09 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-09 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2023-01-09 07:46:17 | 2ND REVIEW FMC | | | PERMIT: 22101241 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | | | | 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON A | | | LISTED OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN | | | TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING | | | CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED | | | ENGINEERING ANALYSIS. FMC 403.3.1.1 | | | | | | 2) PROVIDE THE ZONE AIR DISTRIBUTION EFFECTIVENESS FOR | | | EACH ZONE. FMC 403.3.1.1.1.2 | | | | | | 3) PROVIDE THE SYSTEM VENTILATION EFFICIENCY FOR EACH | | | SYSTEM PROVIDING OUTDOOR AIR TO MULTIPLE ZONES. FMC | | | 403.3.1.1.2.3.2 | | | | | | 4) COMMENT 7 FROM PREVIOUS REVIEW: MY COMMENT WAS MEANT | | | FOR YOU TO EXPLAIN HOW THE DESIGN WAS REFLECTING THE | | | REQUIRED CFM???S OF EXHAUST PER EACH WATER CLOSET AND | | | URINAL BASED ON TABLE 403.3.1.1 AND FOOTNOTE E. I DID | | | NOT MEAN FOR YOU TO SHOW AN EXHAUST FAN OVER EACH WATER | | | CLOSET AND URINAL. PLEASE SHOW HOW THE MINIMUM CFM???S | | | OF EXHAUST FOR EACH WATER CLOSET AND URINAL IS MET IN | | | YOUR DESIGN. THERE IS NO M1-302C IN THIS SUBMITTAL. | | | | | | 5) SHEET M1-202B: THE PARKING GARAGE CALCULATIONS | | | LISTED INDICATE THAT THE 1ST FLOOR PARKING GARAGE IS AN | | | OPEN PARKING GARAGE. SHEET M1-201A SHOES A VEF-1-1. | | | SHEET M1-302 INDICATES THIS EXHAUST FANS IS EXHAUSTING | | | 30,000 CFM???S OF AIR FROM THE GARAGE. PLEASE EXPLAIN | | | WHY THIS IS NEEDED IF THIS IS AN OPEN GARAGE. FBC | | | 107.3.5 | | | | | | 6) COMMENT 11 FROM PREVIOUS REVIEW: THE REQUIRED FIRE | | | DAMPERS IN THE WALL BETWEEN THE FCC ROOM AND THE MOTOR | | | LOBBY WAS NOT ADDED TO SHEET M1-201C. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-29 |
Time |
06:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-29 |
Time |
06:22 |
Sent To |
|
|
| Notes |
| 2022-11-29 06:23:10 | 1ST REVIEW FMC | | | PERMIT: 22101241 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS. FEC C402.1 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC C403.2.1 | | | | | | 3) WHERE ARE THE CALCULATIONS FOR THE PARKING GARAGE | | | VENTILATION? IF THE PARKING GARAGE IS ENCLOSED PLEASE | | | SHOW THAT THE CONDENSING UNITS MOUNTED IN THE ENCLOSED | | | PARKING GARAGE WILL BE SUPPLIED THE REQUIRED AIR | | | CIRCULATION FOR EACH CONDENSING UNIT. MANUFACTURES | | | INSTRUCTIONS. | | | | | | 4) REVISE THE MECHANICAL DRAWINGS TO ADD A NOTE THAT | | | THE GENERATOR WILL REQUIRE A SEPARATE PERMIT | | | APPLICATION, DOCUMENT SUBMITTAL AND PLAN REVIEW. | | | | | | 5) PROVIDE A CO,NO2 LAYOUT, COVERAGE AREA FOR EACH | | | SENSOR, SHEET FOR THE GARAGES. FBC 107.3.5 | | | | | | PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH OCCUPANCY | | | CLASSIFICATION FOR THIS PROJECT. FMC 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | 6) SHEET M1-201A: REVISE THE BATH EXHAUST FANS TO | | | REFLECT EACH WATER CLOSET OR URINAL. ADD A NOTE ON THE | | | DRAWINGS TO INDICATE HOW THE EXHAUST FANS FOR THE BATH | | | ROOMS WILL BE CONTROLLED. FMC TABLE 403.3.1.1 FOOTNOTE | | | E | | | | | | 7) SHEET M1-201A: MISSING A FD FOR THE INTAKE DUCT 14 X | | | 6 AT THE WALL PENETRATION OF THE MECHANICAL ROOM. FMC | | | 607 | | | | | | 8) SHEET M1-201A: MISSING A FD FOR THE 18 X 12 SUPPLY | | | DUCT LEAVING THE MECHANICAL ROOM TO SERVE THE LOBBY. | | | FMC 607 | | | | | | 9) SHEET M1-201A: PROVIDE THE VENTILATION CALCULATIONS | | | FOR THE BIKE STORAGE ROOM. FMC TABLE 403.3.1.1 | | | | | | 10) SHEET M1-201C: REVISE THE DRAWING TO INCLUDE THE | | | REQUIRED FD???S IN THE SUPPLY AND RETURN DUCT | | | PENETRATING THE RATED WALL SEPARATING THE MOTOR LOBBY | | | FROM THE FCC ROOM. FMC 607 | | | | | | 11) SHEET M1-201C: REVISE THE DRAWING TO INCLUDE THE | | | OUTDOOR AIR DUCT SIZE FOR FCU-1-4 IN THE FCC ROOM. FBC | | | 107.3.5 | | | | | | 12) SHEET M1-202C: PROVIDE THE CFM???S OF SUPPLY AIR TO | | | THE BATHROOMS FROM FCU-2.10. FBC 107.3.5 | | | | | | 13) SHEET M1-202C: SHOW THE MEN???S BATH EXHAUST MEETS | | | THE REQUIRES OF TABLE 403.3.1.1 | | | | | | 14) SHEET LS-211 INDICATES A TERRACE ON THE ROOF FOR A | | | FUTURE TENANT, SHEET M1-204C INDICATES THIS SAME AREA | | | TO BE THE LOCATION OF CONDENSING UNIT RACK FOR FUTURE | | | SPACE AC SYSTEMS. PLEASE BE CONSISTENT WITH BOTH | | | SHEETS. FBC 107.3.5 | | | | | | 15) SHEET M1-301: REVISE THE GENERAL NOTES TO REFLECT | | | THE CURRENT 2020 7TH EDITION FLORIDA BUILDING CODES. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-10 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-10 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2023-02-10 10:58:13 | CHANGED TO PASS - INTERCEPT AND BACKFLOW PERMITS | | | SUBMITTED. | | | | | | PENDING APPLICATIONS FOR INTERCEPTOR AND BACKFLOW | | | PERMITS | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2023-01-25 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2023-01-25 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2023-01-25 14:58:09 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1 | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 22101241 150 CLEARWATER DR | | | | | | 3RD REVIEW | | | | | | PLUMBING COMMENTS: DENIED | | | | | | A SEPARATE PERMIT FOR INTERCEPTOR(S) AND/OR BACKFLOW | | | PREVENTER(S) AS APPLICABLE IS REQUIRED TO BE SUBMITTED | | | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS | | | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE | | | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY | | | EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected] . YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS | | | REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN | | | PERMIT IS ALSO REQUIRED. | | | AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY | | | ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS | | | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF | | | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH | | | THE PERMIT NUMBER(S). | | | PLEASE PROVIDE PERMIT NUMBER IF PERMIT HAS BEEN | | | GENERATED TO [email protected] | | | | | | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED | | | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING | | | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED | | | PRIOR TO A PLUMBING REVIEW APPROVAL. | | | | | | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC | | | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS | | | FOR NEW TOILET ROOMS INDICATING THE FOLLOWING: | | | THIRD REQUEST:***B) CLEARANCE AROUND A WATER CLOSET | | | SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM | | | THE SIDE WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG | | | WATER CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR | | | MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO THE | | | REAR WALL PER FBC ACC 604.3.1 AND 604.8.1.1 | | | PLUMBING FIXTURE SCHEDULE INDICATES FLOOR MOUNTED WATER | | | CLOSETS: CLEARANCE SHALL BE 59 INCHES DEEP MINIMUM. FBC | | | ACC 604.8.1.1 | | | | | | RPJ RESPONSE: SEE A0-004, A1-402 A1-403. | | | | | | ALL SHOW 56 INCHES, NOT 59 INCHES AS REQUIRED BY FBC | | | ACC 604.1.1 | | | | | | | | | 2. PARTIALLY COMPLIED: P1-302/SANITARY RISERS-VENTS; | | | PLEASE PROVIDE VENT INFRASTRUCTURE TO SERVICE PRESENT | | | AND FUTURE VENT CONNECTIONS. INDICATE SIZES, HOW AND | | | WHERE SANITARY VENTS WILL TERMINATE. FBC PL SECTIONS | | | 903, 906 | | | RPJ RESPONSE: VENT, SANITARY AND WATER HAVE BEEN ADDED | | | TO SHEETS P1-201A THROUGH P1-203B. | | | | | | NEW COMMENT: PLANS NOW INDICATE VENTS TO SERVICE | | | SANITARY BUT DO NOT ADDRESS HOW AND WHERE SANITARY | | | VENTS WILL TERMINATE AND THE SIZING OF THE VENTS. | | | PLEASE PROVIDE. FBC PL SECTIONS 903, 906 | | | | | | | | | 3. NEW COMMENT: GROUND FLOOR BATHROOMS ADJACENT TO | | | BICYCLE STORAGE; OCCUPANCY CLASSIFICATION STORAGE | | | (REVISED A1-402). A SERVICE SINK IS REQUIRED. FBC PL | | | TABLE 403.1 | | | | | | | | | 4. NEW COMMENT: P1-301/SECOND FLOOR WOMEN'S BATHROOM: | | | WATER SUPPLY TO EACH OF TWO (2) P-1 WATER CLOSET SHALL | | | BE MINIMUM 1 INCH. SEE P1-402 PLUMBING FIXTURE | | | SCHEDULE. FBC PL TABLE 604.5 | | | | | | | | | 5. NEW COMMENT: P1-202B, P1-303B, P1-304A | | | AREA DRAINS AND PLANTER DRAINS THAT HAVE BEEN ADDED ON | | | THE SOUTH GARAGE SECOND FLOOR (P1-202B) CONNECTING TO | | | BRANCH SERVICING RWL 12, 16 ARE DISCHARGING AN | | | ADDITIONAL 395 GPM TO THE BRANCH AND RWL 11. THIS | | | INCREASE IN VOLUME IS NOT REFLECTED ON P1-303B AND | | | P1-304A. | | | AREA DRAINS AND PLANTER DRAINS THAT HAVE BEEN ADDED ON | | | THE SOUTH GARAGE SECOND FLOOR (P1-202B) ARE DISCHARGING | | | AN ADDITIONAL 395 GPM TO RWL 1,2. THIS INCREASE IN | | | VOLUME IS NOT REFLECTED ON P1-303B AND P1-304A. | | | MAKE CORRECTIONS ON DRAWINGS TO REFLECT AND UPDATE | | | SIZING AS REQUIRED. FBC PL 1106.1 | | | | | | 6. NEW COMMENT: P1-202C, P1-201C | | | PLEASE SIZE HORIZONTAL PIPING FOR AREA DRAINS AND | | | PLANTER DRAINS ON THE SOUTH GARAGE SECOND FLOOR | | | (P1-202C) AND THE HORIZONTAL UNDERGROUND STORM DRAIN TO | | | CATCH BASIN (P201C). FBC PL 1106.1 | | | | | | | | | 7. THIRD REQUEST: RPJ RESPONSE: NOTE FOR NOT TO EXCEED | | | 2 FT CAN BE FOUND ALREADY IN SHEET P1-3.01 NEXT TO BOTH | | | BATHROOM ISOMETRICS. THERE ARE NO RECIRCULATION | | | SYSTEMS. | | | | | | TO BE CLEAR, NOTE NOT TO EXCEED 2 FT DOES NOT ADDRESS | | | THE ISSUE. IN ORDER TO COMPLY WITH FBC EC C404.5.1, | | | TABLE C404.5.1, THE 1/2 INCH WATER LINE CANNOT EXCEED A | | | DEVELOPED LENGTH OF 2 FEET FROM THE PUBLIC LAVATORY TO | | | THE SOURCE OF HOT WATER. THE SOURCE WOULD BE THE WATER | | | HEATER, A RECIRCULATING PIPING SYSTEM OR HEAT TRACED | | | PIPING. FBC PL 607.2 | | | PLEASE PROVIDE AN ACCEPTABLE PIPING METHOD TO | | | ACCOMPLISH THIS. PROVIDE INSULATION FOR SYSTEM (COMPLY | | | WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10) AND IF | | | RECIRCULATING, ADJUST WATER HEATER DETAIL AND PIPING | | | PLAN TO REFLECT. INCLUDE RECIRC PUMP SCHEDULE IF | | | APPLICABLE | | | | | | | | | 9. SECOND REQUEST: PLEASE PROVIDE SIZING FOR CD | | | (CONDENSATE DRAINS). FBC PL 314.2.2. | | | RPJ RESPONSE: SIZING FOR CD SYSTEM HAS BEEN ADDED TO | | | SHEETS P1-201A THROUGH P1-201C. | | | | | | TO BE CLEAR, UNDERGROUND CONDENSATE DRAINS FROM RISERS | | | TO CATCH BASINS ARE NOT SIZED. P1-201A, P1-201C | | | | | | | | | 10. PARTIALLY COMPLIED: PLEASE PROVIDE CONDENSATE | | | DRAINS FOR FCUS NOTRD ON P1-201B, P1-201C. FBC PL 314.2 | | | RPJ RESPONSE: REQUIRED CONDENSATE DRAWINGS WERE ADDED | | | THROUGH OUT | | | | | | SEE P1-201C/ELEVATOR LOBBY FCU-1-3 AND PROVIDE DRAIN. | | | | | | | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | PLEASE PROVIDE A COMPREHENSIVE RESPONSE LETTER | | | ADDRESSING EACH ITEM. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER PX928 | | | PLUMBING INSPECTOR BN2148 | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | MOBILE 561-246-0882 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-01-04 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2023-01-04 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2023-01-03 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2023-01-04 14:09:28 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1 | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 22101241 150 CLEARWATER DR | | | | | | 2ND REVIEW | | | | | | PLUMBING COMMENTS: DENIED | | | | | | A SEPARATE PERMIT FOR INTERCEPTOR(S) AND/OR BACKFLOW | | | PREVENTER(S) AS APPLICABLE IS REQUIRED TO BE SUBMITTED | | | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS | | | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE | | | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY | | | EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected] . YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS | | | REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN | | | PERMIT IS ALSO REQUIRED. | | | AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY | | | ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS | | | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF | | | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH | | | THE PERMIT NUMBER(S). | | | NEW COMMENT: PLEASE PROVIDE PERMIT NUMBER IF PERMIT HAS | | | BEEN GENERATED TO [email protected] | | | | | | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED | | | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING | | | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED | | | PRIOR TO A PLUMBING REVIEW APPROVAL. | | | | | | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC | | | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS | | | FOR NEW TOILET ROOMS INDICATING THE FOLLOWING: | | | SECOND REQUEST:***B) CLEARANCE AROUND A WATER CLOSET | | | SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM | | | THE SIDE WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG | | | WATER CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR | | | MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO THE | | | REAR WALL PER FBC ACC 604.3.1 AND 604.8.1.1 | | | PLUMBING FIXTURE SCHEDULE INDICATES FLOOR MOUNTED WATER | | | CLOSETS: CLEARANCE SHALL BE 59 INCHES DEEP MINIMUM. FBC | | | ACC 604.8.1.1 | | | | | | 2. SECOND REQUEST: PER WPB FBC 107.2.1, REGARDING PLAN | | | SHEET A1-402, TO SHOW COMPLIANCE WITH FBC PL 403.1 AND | | | TABLE 403.1, PROVIDE OCCUPANCY AND OCCUPANCY LOAD FOR | | | THE BATHROOMS SERVICING THE NORTH GARAGE GROUND FLOOR. | | | A0-403 ONLY ADDRESSES REQUIREMENTS FOR SECOND FLOOR | | | RESTROOMS | | | | | | 3. COMPLIED | | | | | | 4. SECOND REQUEST: PLAN PAGES 262 P1-201A NORTH GARAGE | | | GROUND FLOOR PLAN PLUMBING AND 114 C-15 WSU PLAN: | | | SANITARY BUILDING DRAINS/BUILDING SEWERS DO NOT MATCH | | | UP TO CIVIL CONNECTIONS. PER WPB FBC 107.2.1 AND | | | 107.3.5.1.3, PLEASE CLARIFY AND RECONCILE. | | | ITEM 4 IS NOT IN RESPONSE LETTER; NOTED AS ITEM 6 BUT | | | NO RESPONSE IS GIVEN | | | | | | 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE | | | SANITARY DRAINAGE, SANITARY VENTS, SANITARY FORCE | | | MAINS, WATER DISTRIBUTION, STORM DRAINAGE, GD DRAINAGE | | | RISER DIAGRAMS COMPLIED; RESPONSE NOTED AS ITEM 7 SEE | | | P1-300 SERIES | | | NEW COMMENT: P1-302/SANITARY RISERS; P-4 MOP SINK AT | | | SECOND FLOOR BATHROOMS IS NOT INDICATED ON THE WATER | | | RISER. PLEASE INDICATE. WPB FBC 107.2.1, 107.3.5.1.3 | | | NEW COMMENT: P1-302/SANITARY RISERS-VENTS; PLEASE | | | PROVIDE VENT INFRASTRUCTURE TO SERVICE PRESENT AND | | | FUTURE VENT CONNECTIONS. INDICATE SIZES, HOW AND WHERE | | | SANITARY VENTS WILL TERMINATE. FBC PL SECTIONS 903, 906 | | | | | | 6. COMPLIED | | | 7. COMPLIED | | | | | | 8. COMPLIED: PER WPB FBC 107.2.1 AND 107.3.5.1.3, | | | CALCULATIONS FOR STORM PIPING SHALL BE ACCUMULATED AND | | | APPLIED TO SIZING OF ALL STORM PIPING TO INCLUDE | | | VERTICAL CONDUCTORS AND LEADERS, BUILDING STORM DRAINS, | | | BUILDING STORM SEWERS AND ANY HORIZONTAL BRANCHES OF | | | SUCH DRAINS OR SEWERS PER FBC PL 1106.1. | | | CALCULATIONS FOR AREA SHALL INCLUDE VERTICAL SURFACES | | | AS WELL AS HORIZONTAL SURFACES. FBC PL 1106.4 | | | ENGINEER RESPONSE: REFER TO SHEET P1-304A AND P1-304B | | | FOR ALL | | | CALCULATIONS. | | | | | | NEW COMMENT: PLEASE ADD NOTE TO P1-303A, P1-303B, | | | P1-304A AND P1-304B STATING "PLEASE NOTE, PER WPB FBC | | | 107.2.1 AND 107.3.5.1.3, CALCULATIONS FOR STORM PIPING | | | SHALL BE ACCUMULATED AND APPLIED TO SIZING OF ALL STORM | | | PIPING TO INCLUDE VERTICAL CONDUCTORS AND LEADERS, | | | BUILDING STORM DRAINS, BUILDING STORM SEWERS AND ANY | | | HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS. PER FBC | | | PL 1106.1. CALCULATIONS FOR AREA SHALL INCLUDE VERTICAL | | | SURFACES AS WELL AS HORIZONTAL SURFACES. FBC PL 1106.4. | | | SEE P1-303A, P1-303B, P1-304A AND P1-304B. SEE | | | P1-4.01/GENERAL PLUMBING NOTES SECTION 5/NOTE D FOR | | | MINIMUM SLOPE OF 1/8 INCH PER FOOT FOR HORIZONTAL | | | PIPING." | | | | | | 9. COMPLIED | | | | | | 10. SECOND REQUEST: PER WPB FBC 107.3.5.1.3, FBC PL | | | 604.1, 604.3, PROVIDE CALCULATIONS FOR SIZING OF WATER | | | DISTRIBUTION | | | AT A MINIMUM PLEASE PROVIDE MAXIMUM GPM FOR GIVEN | | | SIZES. | | | | | | 11. SECOND REQUEST: PER WPB FBC 107.3.5.1.3, FBC PL | | | 710.1, PROVIDE CALCULATIONS FOR SIZING OF SANITARY | | | DRAINAGE. | | | IT IS NOTED THAT FIXTURE UNITS HAVE BEEN PROVIDED FOR | | | BATHROOM PIPING. AT A MINIMUM, PLEASE PROVIDE MAXIMUM | | | AMOUNT OF FIXTURE UNITS THAT MAY CONNECT TO GIVEN SIZES | | | OF THE BUILDING DRAIN. | | | | | | 12. COMPLIED | | | 13. COMPLIED | | | | | | 14. PARTIALLY COMPLIED: PER WPB FBC 107.2.1 AND | | | 107.3.5.1.3, PLEASE PROVIDE A PLUMBING LEGEND; I.E., | | | GD=?, FM=?, ETC. | | | NEW COMMENT: P1-4.01; PLEASE AMEND DESCRIPTION OF "SD" | | | LEGENDS TO READ STORM DRAIN/EXISTING STORM DRAIN, NOT | | | GREASY WASTE/EXISTING GREASY WASTE | | | | | | 15. COMPLIED | | | 16. COMPLIED | | | 17. COMPLIED | | | | | | 18. SECOND REQUEST: P1-2.01A: SANITARY BRANCH FROM | | | BATHROOMS ADJACENT TO BICYCLE PARKING SPACE IS SHOWN | | | DISCHARGING INTO THE FM (FORCE MAIN?) FROM ELEVATOR | | | SUMP PUMP AT GRID LINES G-13 AND THEN INTO HD (HUB | | | DRAIN?) IS THIS BRANCH A SUBDRAIN UNABLE TO DRAIN BY | | | GRAVITY INTO BUILDING DRAIN? IF SO, IT SHALL BE | | | DISCHARGED INTO THE SANITARY BUILDING DRAIN IN | | | ACCORDANCE WITH FBC PL 712.3.5, THROUGH A SEWAGE PUMP | | | OR SEWAGE EJECTOR PER FBC PL 712.4. AN EQUIPMENT | | | SCHEDULE/SPECIFICATION FOR PUMP AND SUMP WITH A DETAIL | | | SHALL BE PROVIDED. IF NOT A SUBDRAIN THEN CONNECT | | | DIRECTLY TO THE BUILDING DRAIN PER FBC PL 712.1, NOT TO | | | THE FM (FORCE MAIN). | | | NO RESPONSE INDICATED IN RESPONSE LETTER; PLEASE NOTE, | | | NEW SHEET P1-302 ISOMETRIC INDICATES ELEVATOR SUMP PUMP | | | DISCHARGING INDEPENDENTLY TO A HUB DRAIN WHICH IS | | | COMPLIANT. | | | THE SANITARY BRANCH FROM THE WOMEN???S BATHROOM IS | | | SHOWN BUT THE POINT OF CONNECTION IS NOT SHOWN. PLEASE | | | INDICATE THE CONNECTION TO THE SANITARY BUILDING DRAIN. | | | IF THIS IS A SUB-DRAIN, DISCHARGE THROUGH A SEWAGE | | | PUMP/EJECTOR TO THE SANITARY BUILDING DRAIN IN | | | ACCORDANCE WITH FBC PL SECTION 712. IF NOT A SUBDRAIN | | | THEN CONNECT BY GRAVITY DIRECTLY TO THE BUILDING DRAIN. | | | IF SEWAGE PUMP IS REQUIRED PLEASE PROVIDE SPEC AND | | | DETAIL. WPB FBC 107.2.1, 107.3.5.1.3 | | | PLEASE SHOW ON P1-2.01A AND P1-3.02. WPB FBC 107.2.1, | | | 107.3.5.1.3 | | | | | | 19. COMPLIED | | | 20. NOT REQUIRED | | | | | | 21. PARTIALLY COMPLIED: PROVIDE A PLUMBING FIXTURE | | | SCHEDULE AND SPECIFICATION, TAG IN ACCORDANCE WITH | | | FIXTURE TAGS NOTED ON PLUMBING PLAN VIEW DRAWINGS. | | | SECOND REQUEST: *** LAVATORIES (INCLUDE THERMOSTATIC | | | MIXING VALVES; FPC PL 419.5) TO BE CLEAR, PLEASE ADD A | | | THERMOSTATIC MIXING VALVE COMPLYING WITH ASSE 1070 TO | | | P1-4.02/PLBG FIXTURE SCHEDULE | | | SECOND REQUEST: ***SHOWERS (INCLUDE THERMOSTATIC MIXING | | | CONTROL VALVES; FPC PL 412.3) TO BE CLEAR, PLEASE ADD | | | P-4H SHOWER AND CONTROL VALVE TO P1-4.02/PLBG FIXTURE | | | SCHEDULE | | | | | | 22. PARTIALLY COMPLIED: PER WPB FBC 107.2.1 AND | | | 107.3.5.1.3, PROVIDE A WATER HEATER SCHEDULE AND DETAIL | | | SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, | | | HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE | | | FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE | | | (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION) | | | AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) | | | PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.1.1, 607.3, | | | 613.1, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, | | | 504.7, 504.7.1 AND 504.7.2. | | | NEW COMMENT: P1-4.02/WATER HEATER DETAIL; PROVIDE A | | | THERMAL EXPANSION CONTROL DEVICE BETWEEN THE CHECK | | | VALVE AND THE TANK TYPE STORAGE WATER HEATER. FBC PL | | | 607.3 | | | NEW COMMENT: THERMAL MIXING VALVE SHALL COMPLY WITH | | | ASSE 1017. PLEASE NOTE ON DETAIL AND WATER HEATER | | | SCHEDULE | | | | | | 23. COMPLIED | | | 24. COMPLIED | | | | | | 25. SECOND REQUEST: PER FBC EC C404.5.1, TABLE | | | C404.5.1, 1/2 INCH HOT WATER TO PUBLIC LAVATORY SHALL | | | NOT EXCEED 2 FEET FROM SOURCE. | | | PLEASE NOTE PER FBC PL 607.2, THE DEVELOPED LENGTH OF | | | HOT OR TEMPERED WATER IN GENERAL SHALL NOT EXCEED 50 | | | FEET FROM THE SOURCE. RECIRCULATING SYSTEM PIPING AND | | | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF | | | HOT OR TEMPERED WATER. | | | IF A RECIRCULATING HOT WATER SYSTEM IS PROVIDED, | | | PROVIDE A RECIRC PUMP SCHEDULE/SPECIFICATION & DETAIL | | | TO BE CLEAR, A RECIRCULATING OR HEAT TRACED HOT WATER | | | SYSTEM IS REQUIRED TO KEEP 1/2 INCH HOT WATER TO PUBLIC | | | LAVATORIES WITHIN 2 FEET OF THE SOURCE. PLEASE PROVIDE | | | AN ACCEPTABLE PIPING METHOD TO ACCOMPLISH THIS. PROVIDE | | | INSULATION FOR SYSTEM (SEE ITEM 26) AND IF | | | RECIRCULATING, ADJUST WATER HEATER DETAIL AND PIPING | | | PLAN TO REFLECT. INCLUDE RECIRC PUMP SCHEDULE IF | | | APPLICABLE. | | | | | | 26. SEE ITEM 25 CLARIFICATION: PER WPB FBC 107.2.1, | | | PROVIDE INSULATION SPECIFICATION SPEC FOR HOT WATER | | | INSULATION COMPLY WITH FBC EC C404.4 (A-E) AND TABLE | | | C403.2.10. | | | THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN | | | IN TABLE C403.2.10: | | | ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY | | | AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER | | | HEATER. | | | ***B) THE FIRST 8 FEET OF OUTLET PIPING FOR A | | | CONSTANT-TEMPERATURE NONRECIRCULATING STORAGE SYSTEM. | | | ***C) THE FIRST 8 FEET OF BRANCH PIPING CONNECTING TO | | | RECIRCULATED, HEAT-TRACED, OR IMPEDANCE HEATED PIPING. | | | ***D) THE INLET PIPING BETWEEN THE STORAGE TANK AND A | | | HEAT TRAP IN A NONRECIRCULATING STORAGE SYSTEM. | | | ***E) PIPING THAT IS EXTERNALLY HEATED (SUCH AS HEAT | | | TRACE OR IMPEDANCE HEATING). | | | | | | 28. NEW COMMENT: P1-4.02/TRASH CHUTE DETAIL; SANITATION | | | UNIT SHALL CONNECT DOWNSTREAM OF THE BACKFLOW | | | PREVENTER. FBC PL 608.1 | | | | | | 29. NEW COMMENT: PLEASE SHOW LOCATION OF TRASH CHUTE | | | AND INCLUDE PIPING IN PIPING PLANS. WPB FBC 107.2.1, | | | 107.3.5.1.3 | | | | | | 30. NEW COMMENT: PLEASE PROVIDE SIZING FOR CD | | | (CONDENSATE DRAINS). FBC PL 314.2.2. | | | | | | 31. NEW COMMENT: PLEASE PROVIDE CONDENSATE DRAINS FOR | | | FCUS NOTRD ON P1-201B, P1-201C. FBC PL 314.2 | | | | | | 32. NEW COMMENT: P1-201B, P1-302; PLEASE PROVIDE | | | BUILDING DRAIN FOR SANITARY FROM SECOND FLOOR BATHROOMS | | | TO SEWER POINT OF CONNECTION. FBC PL 701.2 | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | PLEASE PROVIDE A COMPREHENSIVE RESPONSE LETTER | | | ADDRESSING EACH ITEM. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER PX928 | | | PLUMBING INSPECTOR BN2148 | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | MOBILE 561-246-0882 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2022-11-07 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2022-11-02 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2022-11-07 16:54:20 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1 | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 22101241 150 CLEARWATER DR | | | | | | 1ST REVIEW | | | ELECTRONIC SIGNATURE CERTIFICATE FOR PLUMBING PLANS | | | NOTES ???THE SELECTED CERTIFICATE HAS ERRORS; INVALID | | | POLICY CONSTRAINT??? | | | PLUMBING COMMENTS: DENIED | | | | | | A SEPARATE PERMIT FOR INTERCEPTOR(S) AND/OR BACKFLOW | | | PREVENTER(S) AS APPLICABLE IS REQUIRED TO BE SUBMITTED | | | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS | | | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE | | | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY | | | EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected] . YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS | | | REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN | | | PERMIT IS ALSO REQUIRED. | | | AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY | | | ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS | | | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF | | | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH | | | THE PERMIT NUMBER(S). | | | | | | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED | | | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING | | | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED | | | PRIOR TO A PLUMBING REVIEW APPROVAL. | | | | | | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC | | | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS | | | FOR NEW TOILET ROOMS INDICATING THE FOLLOWING: | | | ***A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL | | | OR PARTITION TO THE REAR AND TO ONE SIDE. THE | | | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES | | | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR | | | PARTITION PER FBC ACC 604.2 | | | ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 | | | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER | | | CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED | | | WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL | | | PER FBC ACC 604.3.1 AND 604.8.1.1 | | | ***C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE | | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | | WALL PER FBC ACC 604.5.1 | | | ***D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES | | | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 | | | ***E) FLUSH CONTROLS SHALL BE HAND OPERATED OR | | | AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY | | | WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN | | | SIDE OF THE WATER CLOSET PER FBC ACC 604.6 | | | ***F) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL | | | COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 | | | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED | | | BEHIND GRAB BARS. | | | ***G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE | | | FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 | | | INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE | | | SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED | | | POSITION PER FBC ACC 604.4. | | | ***H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED | | | IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE | | | TOP (NOT THE CENTER) OF THE GRIPPING SURFACE | | | ***I) URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG | | | TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP | | | MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM | | | TO THE BACK OF THE FIXTURE PER FBC ACC 605.2. | | | ***J) LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS | | | REQUIRED BY FBC ACC 306.2 AND 306.3 | | | ***K) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER | | | SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE | | | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST | | | CONTACT. | | | ***L) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. | | | ***M) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND PER FBC ACC 603.3. | | | ***N) DRINKING FOUNTAINS SHOWING COMPLIANCE WITH 306.2, | | | 306.3, 307.2, 602.4, 602.5, 602.7 | | | ***O) ROLL IN TYPE SHOWER COMPARTMENT; COMPLY WITH FBC | | | ACC 608.2.2, 608.2.2.1, 608.3, 608.3.2, 608.4, 608.5, | | | 309.4, 608.5.2, 608.7. | | | | | | 2. PER WPB FBC 107.2.1, REGARDING PLAN SHEET A1-402, TO | | | SHOW COMPLIANCE WITH FBC PL 403.1 AND TABLE 403.1, | | | PROVIDE OCCUPANCY AND OCCUPANCY LOAD FOR THE BATHROOMS | | | SERVICING THE NORTH GARAGE GROUND FLOOR. | | | | | | 3. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE WALL | | | FINISHES FOR WALLS ADJACENT TO WATER CLOSETS AND | | | SERVICE SINKS. COMPLY WITH FBC PL 310.3, FBC 1210.2.2 | | | | | | 4. PLAN PAGES 262 P1-201A NORTH GARAGE GROUND FLOOR | | | PLAN PLUMBING AND 114 C-15 WSU PLAN: SANITARY BUILDING | | | DRAINS/BUILDING SEWERS DO NOT MATCH UP TO CIVIL | | | CONNECTIONS. PER WPB FBC 107.2.1 AND 107.3.5.1.3, | | | PLEASE CLARIFY AND RECONCILE. | | | | | | 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE | | | SANITARY DRAINAGE, SANITARY VENTS, SANITARY FORCE | | | MAINS, WATER DISTRIBUTION, STORM DRAINAGE, GD DRAINAGE | | | RISER DIAGRAMS | | | | | | 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PIPING | | | PLAN VIEW FOR SOUTH PLAZA SECOND FLOOR PLUMBING. | | | INCLUDE WATER HEATER. | | | | | | 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PIPING | | | AND DRAIN FOR SOUTH GARAGE LEVEL 2 AREA DRAIN | | | | | | 8. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CALCULATIONS | | | FOR STORM PIPING SHALL BE ACCUMULATED AND APPLIED TO | | | SIZING OF ALL STORM PIPING TO INCLUDE VERTICAL | | | CONDUCTORS AND LEADERS, BUILDING STORM DRAINS, BUILDING | | | STORM SEWERS AND ANY HORIZONTAL BRANCHES OF SUCH DRAINS | | | OR SEWERS PER FBC PL 1106.1. | | | CALCULATIONS FOR AREA SHALL INCLUDE VERTICAL SURFACES | | | AS WELL AS HORIZONTAL SURFACES. FBC PL 1106.4 | | | | | | 9. PROVIDE SECONDARY ROOF DRAINS OR SCUPPERS IN | | | ACCORDANCE WITH FBC PL SECTION 1108. | | | | | | 10. PER WPB FBC 107.3.5.1.3, FBC PL 604.1, 604.3, | | | PROVIDE CALCULATIONS FOR SIZING OF WATER DISTRIBUTION. | | | | | | 11. PER WPB FBC 107.3.5.1.3, FBC PL 710.1, PROVIDE | | | CALCULATIONS FOR SIZING OF SANITARY DRAINAGE. | | | | | | 12. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE SIZING | | | OF SANITARY DRAINAGE, SANITARY VENTS, SANITARY FORCE | | | MAINS, WATER DISTRIBUTION, STORM DRAINAGE, GD DRAINAGE | | | ON PLAN VIEWS AND RISER DIAGRAMS | | | | | | 13. PER WPB FBC 107.2.1 AND 107.3.5.1.3, IDENTIFY | | | SANITARY DRAIN LINES ON PLAN VIEWS | | | | | | 14. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PLEASE PROVIDE | | | A PLUMBING LEGEND; I.E., GD=?, FM=?, ETC. | | | | | | 15. REFERENCE TO DETAILS ARE NOTED ON THE PLUMBING | | | PLANS. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE | | | DETAIL(S) FOR THE FOLLOWING: | | | ***A) SUMP PITS AND PUMP WITH PUMP | | | SCHEDULE/SPECIFICATION | | | ***B) HOSE BIBB PROTECTION IN PARKING AREAS | | | | | | 16. PER FBC PL 901.2.1, PROVIDE VENT FOR THE SANITARY | | | HUB DRAIN(S) | | | | | | 17. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE DETAIL | | | FOR TYPICAL SANITARY HUB DRAIN AND INDIRECT WASTE | | | CONNECTION | | | | | | 18. P1-2.01A: SANITARY BRANCH FROM BATHROOMS ADJACENT | | | TO BICYCLE PARKING SPACE IS SHOWN DISCHARGING INTO THE | | | FM (FORCE MAIN?) FROM ELEVATOR SUMP PUMP AT GRID LINES | | | G-13 AND THEN INTO HD (HUB DRAIN?) IS THIS BRANCH A | | | SUBDRAIN UNABLE TO DRAIN BY GRAVITY INTO BUILDING | | | DRAIN? IF SO, IT SHALL BE DISCHARGED INTO THE SANITARY | | | BUILDING DRAIN IN ACCORDANCE WITH FBC PL 712.3.5, | | | THROUGH A SEWAGE PUMP OR SEWAGE EJECTOR PER FBC PL | | | 712.4. AN EQUIPMENT SCHEDULE/SPECIFICATION FOR PUMP AND | | | SUMP WITH A DETAIL SHALL BE PROVIDED. IF NOT A SUBDRAIN | | | THEN CONNECT DIRECTLY TO THE BUILDING DRAIN PER FBC PL | | | 712.1, NOT TO THE FM (FORCE MAIN?). | | | | | | 19. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PIPING | | | MATERIAL SPEC FOR EACH SYSTEM (SANITARY DRAINAGE, | | | SANITARY FORCE MAINS, VENT PIPING, STORM DRAINAGE, | | | WATER DISTRIBUTION, A/C CONDENSATE) TO INCLUDE PIPE, | | | VALVES, FITTINGS AND JOINTS. COMPLY WITH FBC PL | | | CHAPTERS 3, 6, 7, 9 AND 11. | | | | | | 20. PROVIDE MINIMUM AVAILABLE WATER PRESSURE AT THE | | | HIGHEST POINT OF THE WATER DISTRIBUTION SYSTEM. FBC PL | | | 604.3 AND TABLE 604.3 | | | | | | 21. PROVIDE A PLUMBING FIXTURE SCHEDULE AND | | | SPECIFICATION, TAG IN ACCORDANCE WITH FIXTURE TAGS | | | NOTED ON PLUMBING PLAN VIEW DRAWINGS. ITEMS SHALL | | | INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: | | | ***WATER CLOSETS | | | *** LAVATORIES (INCLUDE THERMOSTATIC MIXING VALVES; FPC | | | PL 419.5) | | | ***SINKS | | | ***URINALS | | | ***SHOWERS (INCLUDE THERMOSTATIC MIXING CONTROL VALVES; | | | FPC PL 412.3) | | | ***DRINKING FOUNTAINS | | | ***HOSE BIBS | | | ***WALL HYDRANTS | | | ***TRAP PRIMER DEVICES | | | ***ACCESS PANELS | | | ITEMS SHALL INCLUDE APPLICABLE FAUCETS, CONTROL VALVES, | | | ETC. | | | | | | 22. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A | | | WATER HEATER SCHEDULE AND DETAIL SHOWING HEATER | | | W/STORAGE CAPACITY, PIPING INCLUDING CW, HW, VALVES | | | (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC PL | | | 504.2) , THERMAL EXPANSION CONTROL DEVICE (INCLUDING | | | SIZE), T&P DISCHARGE (INCLUDING TERMINATION) AND WATER | | | HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER WPB | | | FPC 107.2.1; COMPLY WITH FBC PL 607.1.1, 607.3, 613.1, | | | 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, | | | 504.7.1 AND 504.7.2. | | | PROVIDE ENERGY EFFICIENCY SHOWING COMPLIANCE WITH FBC | | | EC TABLE C404.2. | | | | | | 23. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A | | | PLUMBING DRAIN SCHEDULE/SPECIFICATION | | | ***FLOOR DRAINS | | | ***GD | | | | | | 24. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE SUMP | | | PUMP SCHEDULE/SPECIFICATION | | | | | | 25. PER FBC EC C404.5.1, TABLE C404.5.1, 1/2 INCH HOT | | | WATER TO PUBLIC LAVATORY SHALL NOT EXCEED 2 FEET FROM | | | SOURCE. | | | PLEASE NOTE PER FBC PL 607.2, THE DEVELOPED LENGTH OF | | | HOT OR TEMPERED WATER IN GENERAL SHALL NOT EXCEED 50 | | | FEET FROM THE SOURCE. RECIRCULATING SYSTEM PIPING AND | | | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF | | | HOT OR TEMPERED WATER. | | | IF A RECIRCULATING HOT WATER SYSTEM IS PROVIDED, | | | PROVIDE A RECIRC PUMP SCHEDULE/SPECIFICATION & DETAIL | | | | | | 26. PER WPB FBC 107.2.1, PROVIDE INSULATION | | | SPECIFICATION SPEC FOR HOT WATER INSULATION COMPLY WITH | | | FBC EC C404.4 (A-E) AND TABLE C403.2.10. | | | THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN | | | IN TABLE C403.2.10: | | | ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY | | | AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER | | | HEATER. | | | ***B) THE FIRST 8 FEET OF OUTLET PIPING FOR A | | | CONSTANT-TEMPERATURE NONRECIRCULATING STORAGE SYSTEM. | | | ***C) THE FIRST 8 FEET OF BRANCH PIPING CONNECTING TO | | | RECIRCULATED, HEAT-TRACED, OR IMPEDANCE HEATED PIPING. | | | ***D) THE INLET PIPING BETWEEN THE STORAGE TANK AND A | | | HEAT TRAP IN A NONRECIRCULATING STORAGE SYSTEM. | | | ***E) PIPING THAT IS EXTERNALLY HEATED (SUCH AS HEAT | | | TRACE OR IMPEDANCE HEATING). | | | | | | 27. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER AND | | | SUPPORT DETAILS SHOWING COMPLIANCE WITH FBC PL TABLE | | | 308.5. | | | | | | 28. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A | | | CROSS-SECTION SHOWER WALL/FLOOR/DRAIN AND THRESHOLD | | | DETAIL TO SHOW COMPLIANCE WITH FBC PL 421.5.2, 421.4.1, | | | 421.5 | | | | | | 29. PER FBC FL 1002.4.1, PROVIDE TRAP SEAL PROTECTION | | | FOR THE FLOOR DRAIN. PER WPB FBC 107.2.1, PROVIDE A | | | TRAP SEAL PROTECTION SPECIFICATION AND DETAIL COMPLYING | | | WITH ONE OF THE FOLLOWING: FBC 1002.4.1.1, 1002.4.1.2, | | | 1002.4.1.3 OR 1002.4.1.4. | | | | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | PLEASE PROVIDE A COMPREHENSIVE RESPONSE LETTER | | | ADDRESSING EACH ITEM. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER PX928 | | | PLUMBING INSPECTOR BN2148 | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | MOBILE 561-246-0882 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
6 |
Status |
P |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-27 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-27 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-15 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-15 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2023-03-15 16:23:04 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-13 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-13 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2023-02-13 13:13:53 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-30 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-30 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2023-01-30 07:52:17 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-09 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-09 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2023-01-09 15:45:29 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-30 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-30 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2022-11-30 15:14:08 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2023-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-05 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-05 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-15 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-15 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-13 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-13 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2023-02-13 13:18:39 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE SIGNED AND SEALED THRESHOLD INSPECTOR FORM DOES | | | NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-30 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-30 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-09 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-09 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2023-01-09 15:47:56 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS S000, S001, S003, S004, S005, S100, S102, | | | S103, S104,S105, S107, S109, S110, S111, S112, S114, | | | S115, S117, S500, S601, S602 DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | 2023-01-09 07:47:33 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | | 2023-01-04 12:08:13 | ELECTRONIC SIGNATURES FOR PLUMBING PLANS ARE VALID. JS |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-30 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-30 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2022-11-30 16:52:05 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS LS-1, S000,S001, S002, S100, S101, S102, | | | S103, S104,S105, S107, S108, S109, S110, S111, S112, | | | S115, S116, S200, S300, S400, S501, S601, S602 DO NOT | | | SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | 2022-11-29 06:23:44 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | | 2022-11-07 16:38:38 | ELECTRONIC SIGNATURE CERTIFICATE FOR PLUMBING PLANS | | | NOTES "THE SELECTED CERTIFICATE HAS ERRORS; INVALID | | | POLICY CONSTRAINT". PLEASE CORRECT. JS |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
6 |
Status |
P |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-22 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-22 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
5 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-15 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-15 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2023-03-15 16:23:46 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
4 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-13 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-13 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2023-02-13 13:14:38 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-30 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-30 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2023-01-30 07:57:16 | THRESHOLD BUILDING | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING | | | PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY | | | BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET | | | IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY | | | CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE | | | WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT | | | CONTENT OF GREATER THAN 500 PERSONS. | | | | | | PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE | | | "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". | | | YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | 1) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED | | | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED | | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. SEE "GUIDELINES | | | AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL | | | INSPECTORS AND RESIDENT INSPECTORS". | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-09 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-09 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2023-01-09 15:50:38 | THRESHOLD BUILDING | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING | | | PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY | | | BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET | | | IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY | | | CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE | | | WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT | | | CONTENT OF GREATER THAN 500 PERSONS. | | | | | | PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE | | | "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". | | | YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | 1) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED | | | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED | | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. SEE "GUIDELINES | | | AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL | | | INSPECTORS AND RESIDENT INSPECTORS". | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-30 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-30 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2022-11-30 16:56:41 | THRESHOLD BUILDING | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING | | | PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY | | | BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET | | | IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY | | | CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE | | | WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT | | | CONTENT OF GREATER THAN 500 PERSONS. | | | | | | PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE | | | "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". | | | YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | 1) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT | | | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED | | | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF | | | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE | | | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS | | | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. | | | | | | 2) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED | | | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED | | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. SEE "GUIDELINES | | | AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL | | | INSPECTORS AND RESIDENT INSPECTORS". | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
P |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2023-04-07 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2023-04-07 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2023-04-07 14:00:31 | ZONING COMMENTS | | | 1. SHEET A0-002 PROJECT DATA SHOWS INCORRECT FAR | | | DIAGRAMS AND DATA TABLE REFLECTS OLDER NUMBERS. [NOT | | | SATISFIED 3.28.23] REGARDLESS OF GREY HATCHED AREAS, | | | THE FOOTPRINT DIAGRAMS/DRAWINGS ARE INCORRECT AND DOES | | | NOT MATCH APPROVAL SET. DRAWINGS REFLECT OLD SITE | | | DESIGN WHICH HAS BEEN ALTERED. AREA SCHEDULE | | | (GROSS BUILDING AREA) TABLE CALCULATIONS DO NOT MATCH | | | THE APPROVED SET, PLEASE NOTE CHANGES IN EACH FLOORS | | | GBA AND TOTAL (WHEN ADDED UP EQUALS 1,128,080SF, | | | APPROVED SET WAS 1,296,814 SF). BIKE SPACES REDUCED | | | FROM 618 SPACES IN APPROVED SET TO 324 IN THIS SET, | | | WHAT IS THE REASON FOR THIS REDUCTION? ARE BIKE SPACES | | | DISTRIBUTED EVENLY ACROSS THE PROJECT SITE? | | | RESPONSE: FAR DIAGRAMS WERE UPDATED TO REFLECT THE | | | APPROVED SET COMBINED WITH THE CURRENT DESIGN. THE AREA | | | TABLES ARE UPDATED AND THE ORIGINAL FAR TABLE IS | | | INCLUDED IN THE REVISED SHEET FOR CLARITY. NUMBER OF | | | BIKE SPACES WERE REDUCED SINCE THE RESIDENTIAL | | | COMPONENT WASN???T INCLUDED IN THIS PHASE. REGARDLESS, | | | WE ADDED THE MISSING SPACED IN THIS REVISION TO MATCH | | | THE QUANTITIES IN THE APPROVED SITE PLAN. | | | REFER TO REVISED SUBMITTED SHEET WHERE NEW BIKE STORAGE | | | AREA ARE PROPOSED. | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 2. SHEET A1-101 GROUND LEVEL APPEARS TO SHOW OLDER | | | VERSION OF LANDSCAPING AND STREET TREE CONFIGURATION | | | ALONG CLEARWATER DRIVE AND BANYAN FRONTAGES. IN A1-200 | | | NORTHERN PORTION OF GROUNDLEVEL SHOWS ALTERATIONS TO | | | PARKING RAMPS AND ADA SPACES WHICH APPEAR TO POSE | | | ACCESSIBILITY ISSUES WITH NAVIGATING BEHIND OTHER | | | PARKING SPACES AND ACROSS DRIVE AISLE. SHEET DOES NOT | | | REFLECT THE GROUND LEVEL OF THE RESENTIAL TOWER AT THE | | | MID-BLOCK PORTION OF THE SITE ALONG CLEARWATER DRIVE. | | | [PARTIALLY SATISFIED 3.28.23] A1-101 REVISIONS ARE | | | OKAY. FOR SHEET A1-200, THE ADA SPACE APPEARS TO POSE | | | ACCESSIBILITY AND SAFETY ISSUES WITH NAVIGATING BEHIND | | | PARKED CARS AND ACROSS THE DRIVE AISLE. AREA NOW NEEDS | | | A MARKED TURNAROUND SPACE FOR CARS, AS IT IS A DEAD-END | | | CORRIDOR. WHY WAS THIS PORTION OF THE GROUND FLOOR | | | CHANGED FROM THE APPROVAL? APPEARS EGRESS RAMP PUSHED | | | BACK, LOADING SPACE INCLUDES A BUFFER, NEW BIKE | | | ROOM/RESTROOMS, AND ADA RECONFIGURATION. | | | RESPONSE: CORRECT, PARKING RAMPS WERE ALTERED AFTER | | | COORDINATION WITH THE STRUCTURAL DESIGN, WITH THE MAIN | | | INTENTION OF PROVIDING LESS-STEEP SLOPES. FOR THAT | | | REASON, RAMPS ARE LONGER IN THE CURRENT DESIGN, | | | ALTERING THE AREA ON THE GROUND FLOOR AND REDUCING THE | | | AREA OF THE BIKE STORAGES IN THE UPPER LEVELS. THE | | | DISTRIBUTION OF THE ADA SPACES IS MODIFIED TO AVOID ANY | | | USER WALKING BEHIND A PARKED CAR. THE SPACE ACROSS FROM | | | THE DRIVEWAY (UNDER THE RAMP) IS CROSSING PERPENDICULAR | | | TO THE DRIVEWAY, CONFIGURATION ALLOWED BY THE ADA CODE, | | | AS LONG AS HAVING THE PROPER MARKINGS. | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 3. PLEASE INDICATE LOCATION OF ALL ADA SPACES ON ALL | | | LEVELS OF THE PARKING GARAGE. PLEASE PROVIDE TABULAR | | | DATA OF TOTAL PARKING SPACE COUNT, ADA SPACE COUNT, | | | NOTE ANY DESIGNATED SPACES FOR COUNTY/SFRTA, AND NOTATE | | | ANY REDUCTIONS OR RELOCATIONS FROM THE APPROVED PLANS. | | | [NOT SATISFIED 3.28.23] PARKING TABLE ADJUSTED AND | | | APPEARS TO MEET REQUIREMENTS FOR APPROVED PROJECT. | | | PLANS SHOW 5 FT. ADA AISLES IN VARIOUS LOCATIONS ON | | | EACH PARKING LEVEL BUT ONLY A HANDFUL OF SPACES SHOWN | | | TO BE ADA DESIGNATED (FOR EXAMPLE: SHEET A1-203 & SHEET | | | A1-204 ONLY SHOWS 1 DESIGNATED ADA SPACE ON NORTH | | | GARAGE PORTION BUT ILLUSTRATES 8 TOTAL SPACES WITH A | | | STRIPED 5' AISLE ADJACENT TO THEM, BETWEEN BOTH NORTH | | | AND SOUTH PORTIONS). ON A1-203 & A1-204 ADA SPACE NO | | | LONGER LOCATED ADJACENT TO ELEVATOR CORRIDOR. MINOR | | | REVISION BUT PLEASE CLEARLY INDICATE WHICH SPACES ARE | | | ADA (12X18) AND WHICH ARE REGULAR OR COMPACT SPACES. | | | RESPONSE: ADA SYMBOLS AREA ADDED TO ALL DESIGNATED ADA | | | SPACES IN ALL THE LEVELS. REFER TO REVISED SHEETS: A1- | | | 203, A1-206, A1-209, A1-212 AND A1-215 | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 4. SHEET A1-206 NORTHERN GARAGE FOR LEVEL 3 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | [NOT SATISFIED 3.28.23] BIKE COUNT HAD BEEN ADJUSTED, | | | STILL WITHIN MINIMUM REQUIRED. BIKE SPACES ON A1-203 | | | AND A1-204 CHANGED TO BE ALONG EASTERN PORTION OF | | | GARAGE, IS THIS AN ENCLOSED ROOM? IF SO WHAT IS THE SF | | | AND INTERNAL LAYOUT OR BIKE RACK CONFIGURATION/DETAILS. | | | IS THIS FENCED IN OR OPEN? | | | RESPONSE: NUMBER OF BIKE STORAGES WERE ADDED TO MATCH | | | QUANTITIES IN THE APPROVED SITE PLANS. REFER TO REVISED | | | SHEETS (A1-203, A1-206, A1-209, A1-212 AND A1- 215). | | | THE SPACES WERE DISTRIBUTED IN AVAILABLE AREAS AMONG | | | THE NORTH BUILDING. THE PROPOSED BIKE STORAGES ARE | | | INTENDED TO BE FENCED SPACES. | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 5. SHEET A1-209 NORTHERN GARAGE FOR LEVEL 4 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | [NOT SATISFIED 3.28.23] SEE NEW COMMENT 3. | | | RESPONSE: NUMBER OF BIKE STORAGES WERE ADDED TO MATCH | | | QUANTITIES IN THE APPROVED SITE PLANS. REFER TO REVISED | | | SHEETS (A1-203, A1-206, A1-209, A1-212 AND A1- 215). | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 6. SHEET A1-212 NORTHERN GARAGE FOR LEVEL 5-7 REMOVES | | | 44 BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | [NOT SATISFIED 3.28.23] SEE NEW COMMENT #3 RESPONSE: | | | NUMBER OF BIKE STORAGES WERE ADDED TO MATCH QUANTITIES | | | IN THE APPROVED SITE PLANS. REFER TO REVISED SHEETS | | | (A1-203, A1-206, A1-209, A1-212 AND A1- 215). | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 7. SHEET A1-215 NORTHERN GARAGE FOR LEVEL 8 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | [NOT SATISFIED 3.28.23] SEE NEW COMMENT 3. | | | RESPONSE: NUMBER OF BIKE STORAGES WERE ADDED TO MATCH | | | QUANTITIES IN THE APPROVED SITE PLANS. REFER TO REVISED | | | SHEETS (A1-203, A1-206, A1-209, A1-212 AND A1- 215). | | | ZONING 4.7.23 [SATISFIED] | | | | | | | | | NEW ZONING COMMENTS 3.28.23 | | | 1. SHEET A1-101 - OVERALL GROUND FLOOR PLAN, GRAPHIC | | | ERROR OR MISLABELED LAYER FOR ADA SPACES ADJACENT TO | | | LOADING AREA AND RAMP AS COMPARED TO SHEET A1-200 NORTH | | | GARAGE GROUND FLOOR PLAN. | | | RESPONSE: NOTED. GRAPHIC ERROR HAS BEEN CORRECTED AND | | | IS COORDINATED WITH THE VERSION SHOWN IN SHEET A1-200. | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 2. SHEET A1-203 SHOWS NEW PEDESTRIAN PATH BETWEEN RAMP | | | AND PARKING SPACES, WHAT IS THE CIRCULATION OR ROUTE | | | FOR PATRONS? FORCES ADA PATRONS TO CROSS DRIVE AISLE | | | BETWEEN THE RAMPS TO ACCESS ELEVATORS, ADA SPACES | | | SHOULD BE ADJACENT TO ELEVATOR. | | | RESPONSE: CURRENT DESIGN WAS MODIFIED DUE TO | | | COORDINATION THE STRUCTURAL DESIGN AND COLUMN LOCATIONS | | | AND NEW RAMP CONFIGURATION. REGARDLESS, THE PEDESTRIAN | | | PATH FOR PATRONS IS THE SAME, PATRONS ARE CROSSING THE | | | DRIVE ISLE TO ACCESS THE ELEVATORS IN THE SAME WAY AS | | | BEFORE. THE CURRENT DESIGN REDUCED THE WIDTH OF THE | | | ACCESS TO THE ELEVATOR AND STAIR, BUT IT IS STILL IN | | | COMPLIANCE WITH MINIMUM CLEARANCE ALLOWED. THE PROPOSED | | | ADA SPACE (INSIDE THE COUNTY PARKING AREA) WAS | | | RELOCATED TO AVOID ANY SAFETY ISSUES HAVING TO | | | CIRCULATE BEHIND PARKED CARS. REFER TO REVISED SHEET | | | A1-203. | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 3. PLEASE CLARIFY DATA TABLE ON SHEET A0-002 FOR | | | VEHICULAR PARKING, SPECIFICALLY THE BICYCLE PARKING | | | COUNT. THERE ARE PORTIONS OF THE TABLE WHICH SAY 0 | | | SPACES ARE PROVIDED, AND 324 SPACES ARE PROVIDED FOR | | | RETAIL. EACH USE COMMERCIAL VS RESIDENTIAL VS | | | MICROUNITS HAVE THEIR OWN BICYCLE PARKING | | | REQUIREMENTS/COUNTS. ARE ALL THE BICYCLE SPACES NOW | | | LOCATED WITHIN THE GARAGE, OR ARE THERE STILL BICYCLE | | | ROOMS WITHIN THE RESIDENTIAL TOWERS? BICYCLE | | | REQUIREMENTS ARE TIED TO THE USE AND ASSOCIATED PARKING | | | COUNT FOR EACH USE, I.E. 200 RESIDENTIAL PARKING SPACES | | | REQUIRES 14 BICYCLE SPACES TO BE WITHIN A SECURED ROOM. | | | PLEASE ADVISE. | | | RESPONSE: TABLE IS UPDATED TO MATCH QUANTITIES FROM THE | | | APPROVED SITE PLANS SET. REFER TO REVISED SHEET A0-002 | | | | | | ZONING 4.7.23 [SATISFIED] | | | | | | 4. DUE TO ALTERATIONS IN PLANS FROM THE ORIGINAL SITE | | | PLAN APPROVAL, PRIOR TO FINAL CO OF 134 CLEARWATER DR. | | | (TRANSIT VILLAGE) THE AS-BUILT DRAWINGS WILL NEED TO BE | | | SUBMITTED UNDER AN APPLICATION FOR A MINOR SITE PLAN | | | AMENDMENT (SO THE FINAL PLAN SETS ARE ACCURATELY | | | REFLECTED AND ON RECORD). | | | RESPONSE:RESPONSE: ACKNOWLEDGED | | | | | | ZONING 4.7.23 [SATISFIED] - APPROVAL PROVISO. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | [email protected] 561-822-1426 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
F |
Date |
2023-03-28 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2023-03-28 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-03-28 15:16:25 | 1. SHEET A0-000 COVER PAGE SHOWS INCORRECT RENDERING OF | | | PROJECT. | | | [SATISFIED 3.28.23] | | | | | | 2. SHEET A0-002 PROJECT DATA SHOWS INCORRECT FAR | | | DIAGRAMS AND DATA TABLE REFLECTS OLDER NUMBERS. | | | [NOT SATISFIED 3.28.23] REGARDLESS OF GREY HATCHED | | | AREAS, THE FOOTPRINT DIAGRAMS/DRAWINGS ARE INCORRECT | | | AND DOES NOT MATCH APPROVAL SET. DRAWINGS REFLECT OLD | | | SITE DESIGN WHICH HAS BEEN ALTERED. AREA SCHEDULE | | | (GROSS BUILDING AREA) TABLE CALCULATIONS DO NOT MATCH | | | THE APPROVED SET, PLEASE NOTE CHANGES IN EACH FLOORS | | | GBA AND TOTAL (WHEN ADDED UP EQUALS 1,128,080SF, | | | APPROVED SET WAS 1,296,814 SF). BIKE SPACES REDUCED | | | FROM 618 SPACES IN APPROVED SET TO 324 IN THIS SET, | | | WHAT IS THE REASON FOR THIS REDUCTION? ARE BIKE SPACES | | | DISTRIBUTED EVENLY ACROSS THE PROJECT SITE? | | | | | | 3. SHEET A0-000 THROUGH A6-104 SHOWS THE OLDER RENDING | | | OF PROJECT IN TITLE BLOCK. | | | [SATISFIED 3.28.23] RENDERING UPDATED WITHIN REVISED | | | SHEETS. | | | | | | 4. SHEET A1-100 SITE PLAN APPEARS TO SHOW OLDER VERSION | | | OF LANDSCAPING AND STREET TREE CONFIGURATION ALONG | | | CLEARWATER DRIVE AND BANYAN FRONTAGES. SHOULD BE A | | | SINGLE ROW OF STREET TREES CLOSE TO CURB/ALONG THE | | | EASEMENT LINE FOR WATERMAIN ALONG CLEARWATER. BANAYN | | | FRONTAGE HAS CLEAR SIGHTLINE AT INTERSECTION FO | | | CLEARWATER AND BANYAN. | | | [SATISFIED 3.28.23] | | | | | | 5. SHEET A1-101 GROUND LEVEL APPEARS TO SHOW OLDER | | | VERSION OF LANDSCAPING AND STREET TREE CONFIGURATION | | | ALONG CLEARWATER DRIVE AND BANYAN FRONTAGES. IN A1-200 | | | NORTHERN PORTION OF GROUNDLEVEL SHOWS ALTERATIONS TO | | | PARKING RAMPS AND ADA SPACES WHICH APPEAR TO POSE | | | ACCESSIBILITY ISSUES WITH NAVIGATING BEHIND OTHER | | | PARKING SPACES AND ACROSS DRIVE AISLE. SHEET DOES NOT | | | REFLECT THE GROUND LEVEL OF THE RESENTIAL TOWER AT THE | | | MID-BLOCK PORTION OF THE SITE ALONG CLEARWATER DRIVE. | | | [PARTIALLY SATISFIED 3.28.23] A1-101 REVISIONS ARE | | | OKAY. FOR SHEET A1-200, THE ADA SPACE APPEARS TO POSE | | | ACCESSIBILITY AND SAFETY ISSUES WITH NAVIGATING BEHIND | | | PARKED CARS AND ACROSS THE DRIVE AISLE. AREA NOW NEEDS | | | A MARKED TURNAROUND SPACE FOR CARS, AS IT IS A DEAD-END | | | CORRIDOR. WHY WAS THIS PORTION OF THE GROUND FLOOR | | | CHANGED FROM THE APPROVAL? APPEARS EGRESS RAMP PUSHED | | | BACK, LOADING SPACE INCLUDES A BUFFER, NEW BIKE | | | ROOM/RESTROOMS, AND ADA RECONFIGURATION. | | | | | | 6. PLEASE CLOUD AND PROVIDE A NARRATIVE OR HIGHLIGHT | | | ALL CHANGES TO PLAN THE SETS FROM THE APPROVED SITE | | | PLAN SETS. | | | [SATISFIED 3.28.23] | | | | | | 7. SEVERAL DRAWING SHEETS ARE DATED OR SIGNED PRIOR TO | | | THE SITE PLAN APPROVAL. | | | THE ARCHITECTURAL PLANS SUBMITTED WITH PERMIT DO NOT | | | MATCH THE APPROVED SITE PLANS. SOME OF THE SUBMITTED | | | PLANS ARE DATED 12.13.22 AND SIGNED ON 12.16.22, THE | | | FINAL SITE PLAN APPROVAL SET WAS DATED 12.16.22 AND | | | SIGNED ON 01.05.23. PLEASE SUBMIT THE CORRECT SET OF | | | DRAWINGS AND MAKE SURE DRAWINGS ARE LATEST. | | | [SATISFIED 3.28.23] | | | | | | 8. SHEET A1-204 SOUTHERN GARAGE FOR LEVEL 2 APPEARS TO | | | HAVE ADJUSTED THE STAIR LOCATION. | | | [SATISFIED 3.28.23] LAFE SAFETY ALTERATION | | | | | | 9. PLEASE INDICATE LOCATION OF ALL ADA SPACES ON ALL | | | LEVELS OF THE PARKING GARAGE. PLEASE PROVIDE TABULAR | | | DATA OF TOTAL PARKING SPACE COUNT, ADA SPACE COUNT, | | | NOTE ANY DESIGNATED SPACES FOR COUNTY/SFRTA, AND NOTATE | | | ANY REDUCTIONS OR RELOCATIONS FROM THE APPROVED PLANS. | | | [NOT SATISFIED 3.28.23] PARKING TABLE ADJUSTED AND | | | APPEARS TO MEET REQUIREMENTS FOR APPROVED PROJECT. | | | PLANS SHOW 5 FT. ADA AISLES IN VARIOUS LOCATIONS ON | | | EACH PARKING LEVEL BUT ONLY A HANDFUL OF SPACES SHOWN | | | TO BE ADA DESIGNATED (FOR EXAMPLE: SHEET A1-203 & SHEET | | | A1-204 ONLY SHOWS 1 DESIGNATED ADA SPACE ON NORTH | | | GARAGE PORTION BUT ILLUSTRATES 8 TOTAL SPACES WITH A | | | STRIPED 5' AISLE ADJACENT TO THEM, BETWEEN BOTH NORTH | | | AND SOUTH PORTIONS). ON A1-203 & A1-204 ADA SPACE NO | | | LONGER LOCATED ADJACENT TO ELEVATOR CORRIDOR. MINOR | | | REVISION BUT PLEASE CLEARLY INDICATE WHICH SPACES ARE | | | ADA (12X18) AND WHICH ARE REGULAR OR COMPACT SPACES. | | | | | | 10. SHEET A1-206 NORTHERN GARAGE FOR LEVEL 3 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | [NOT SATISFIED 3.28.23] BIKE COUNT HAD BEEN ADJUSTED, | | | STILL WITHIN MINIMUM REQUIRED. BIKE SPACES ON A1-203 | | | AND A1-204 CHANGED TO BE ALONG EASTERN PORTION OF | | | GARAGE, IS THIS AN ENCLOSED ROOM? IF SO WHAT IS THE SF | | | AND INTERNAL LAYOUT OR BIKE RACK CONFIGURATION/DETAILS. | | | IS THIS FENCED IN OR OPEN? | | | | | | 11. PLEASE PROVIDE DRIVE AISLE DIMENSIONS OR WIDTHS ON | | | ALL PARKING GARAGE LEVELS (EX.A1-206, A1-207, ETC. HAS | | | DIMENSIONS MISSING). | | | [SATISFIED 3.28.23] | | | | | | 12. SHEET A1-209 NORTHERN GARAGE FOR LEVEL 4 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | [NOT SATISFIED 3.28.23] SEE NEW COMMENT 3. | | | | | | 13. SHEET A1-212 NORTHERN GARAGE FOR LEVEL 5-7 REMOVES | | | 44 BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | [NOT SATISFIED 3.28.23] SEE NEW COMMENT 3. | | | | | | 14.SHEET A1-215 NORTHERN GARAGE FOR LEVEL 8 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | [NOT SATISFIED 3.28.23] SEE NEW COMMENT 3. | | | | | | 15. PLEASE PROVIDE PARKING STALL DETAIL WITHIN ARCH | | | SETS. | | | [SATISFIED 3.28.23] | | | | | | 16. PLEASE PROVIDE GARAGE SCREENING DETAILS AND | | | MATERIAL DETAILS WITH THE ELEVATION DRAWINGS. | | | [SATISFIED 3.28.23] | | | | | | 17. DOUBLE CHECK LANDSCAPE SHEETS TO REFLECT APPROVAL. | | | 285 GROUND LEVEL LANDSCAPE PLAN APPEARS TO MISS STREE | | | TREES ALONG BANYAN FRONTAGE. | | | [SATISFIED 3.28.23] | | | | | | | | | | | | NEW COMMENTS [3.28.23]: | | | 1. SHEET A1-101 - OVERALL GROUND FLOOR PLAN, GRAPHIC | | | ERROR OR MISLABELED LAYER FOR ADA SPACES ADJACENT TO | | | LOADING AREA AND RAMP AS COMPARED TO SHEET A1-200 NORTH | | | GARAGE GROUND FLOOR PLAN. | | | | | | 2. SHEET A1-203 SHOWS NEW PEDESTRIAN PATH BETWEEN RAMP | | | AND PARKING SPACES, WHAT IS THE CIRCULATION OR ROUTE | | | FOR PATRONS? FORCES ADA PATRONS TO CROSS DRIVE AISLE | | | BETWEEN THE RAMPS TO ACCESS ELEVATORS, ADA SPACES | | | SHOULD BE ADJACENT TO ELEVATOR. | | | | | | 3. PLEASE CLARIFY DATA TABLE ON SHEET A0-002 FOR | | | VEHICULAR PARKING, SPECIFICALLY THE BICYCLE PARKING | | | COUNT. THERE ARE PORTIONS OF THE TABLE WHICH SAY 0 | | | SPACES ARE PROVIDED, AND 324 SPACES ARE PROVIDED FOR | | | RETAIL. EACH USE COMMERCIAL VS RESIDENTIAL VS | | | MICROUNITS HAVE THEIR OWN BICYCLE PARKING | | | REQUIREMENTS/COUNTS. ARE ALL THE BICYCLE SPACES NOW | | | LOCATED WITHIN THE GARAGE, OR ARE THERE STILL BICYCLE | | | ROOMS WITHIN THE RESIDENTIAL TOWERS? BICYCLE | | | REQUIREMENTS ARE TIED TO THE USE AND ASSOCIATED PARKING | | | COUNT FOR EACH USE, I.E. 200 RESIDENTIAL PARKING SPACES | | | REQUIRES 14 BICYCLE SPACES TO BE WITHIN A SECURED ROOM. | | | PLEASE ADVISE. | | | | | | 2. DUE TO ALTERATIONS IN PLANS FROM THE ORIGINAL SITE | | | PLAN APPROVAL, PRIOR TO FINAL CO OF 134 CLEARWATER DR. | | | (TRANSIT VILLAGE) THE AS-BUILT DRAWINGS WILL NEED TO BE | | | SUBMITTED UNDER AN APPLICATION FOR A MINOR SITE PLAN | | | AMENDMENT (SO THE FINAL PLAN SETS ARE ACCURATELY | | | REFLECTED AND ON RECORD). | | | | | | | | | | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822-1426 [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2023-03-07 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-03-07 10:12:00 | 1. SHEET A0-000 COVER PAGE SHOWS INCORRECT RENDERING OF | | | PROJECT. | | | | | | 2. SHEET A0-002 PROJECT DATA SHOWS INCORRECT FAR | | | DIAGRAMS AND DATA TABLE REFLECTS OLDER NUMBERS. | | | | | | 3. SHEET A0-000 THROUGH A6-104 SHOWS THE OLDER RENDING | | | OF PROJECT IN TITLE BLOCK. | | | | | | 4. SHEET A1-100 SITE PLAN APPEARS TO SHOW OLDER VERSION | | | OF LANDSCAPING AND STREET TREE CONFIGURATION ALONG | | | CLEARWATER DRIVE AND BANYAN FRONTAGES. SHOULD BE A | | | SINGLE ROW OF STREET TREES CLOSE TO CURB/ALONG THE | | | EASEMENT LINE FOR WATERMAIN ALONG CLEARWATER. BANAYN | | | FRONTAGE HAS CLEAR SIGHTLINE AT INTERSECTION FO | | | CLEARWATER AND BANYAN. | | | | | | 5. SHEET A1-101 GROUND LEVEL APPEARS TO SHOW OLDER | | | VERSION OF LANDSCAPING AND STREET TREE CONFIGURATION | | | ALONG CLEARWATER DRIVE AND BANYAN FRONTAGES. IN A1-200 | | | NORTHERN PORTION OF GROUNDLEVEL SHOWS ALTERATIONS TO | | | PARKING RAMPS AND ADA SPACES WHICH APPEAR TO POSE | | | ACCESSIBILITY ISSUES WITH NAVIGATING BEHIND OTHER | | | PARKING SPACES AND ACROSS DRIVE AISLE. SHEET DOES NOT | | | REFLECT THE GROUND LEVEL OF THE RESENTIAL TOWER AT THE | | | MID-BLOCK PORTION OF THE SITE ALONG CLEARWATER DRIVE. | | | | | | 6. PLEASE CLOUD AND PROVIDE A NARRATIVE OR HIGHLIGHT | | | ALL CHANGES TO PLAN THE SETS FROM THE APPROVED SITE | | | PLAN SETS. | | | | | | 7. SEVERAL DRAWING SHEETS ARE DATED OR SIGNED PRIOR TO | | | THE SITE PLAN APPROVAL. | | | THE ARCHITECTURAL PLANS SUBMITTED WITH PERMIT DO NOT | | | MATCH THE APPROVED SITE PLANS. SOME OF THE SUBMITTED | | | PLANS ARE DATED 12.13.22 AND SIGNED ON 12.16.22, THE | | | FINAL SITE PLAN APPROVAL SET WAS DATED 12.16.22 AND | | | SIGNED ON 01.05.23. PLEASE SUBMIT THE CORRECT SET OF | | | DRAWINGS AND MAKE SURE DRAWINGS ARE LATEST. | | | | | | 8. SHEET A1-204 SOUTHERN GARAGE FOR LEVEL 2 APPEARS TO | | | HAVE ADJUSTED THE STAIR LOCATION. | | | | | | 9. PLEASE INDICATE LOCATION OF ALL ADA SPACES ON ALL | | | LEVELS OF THE PARKING GARAGE. PLEASE PROVIDE TABULAR | | | DATA OF TOTAL PARKING SPACE COUNT, ADA SPACE COUNT, | | | NOTE ANY DESIGNATED SPACES FOR COUNTY/SFRTA, AND NOTATE | | | ANY REDUCTIONS OR RELOCATIONS FROM THE APPROVED PLANS. | | | | | | 10. SHEET A1-206 NORTHERN GARAGE FOR LEVEL 3 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | | | | 11. PLEASE PROVIDE DRIVE AISLE DIMENSIONS OR WIDTHS ON | | | ALL PARKING GARAGE LEVELS (EX.A1-206, A1-207, ETC. HAS | | | DIMENSIONS MISSING). | | | | | | 12. SHEET A1-209 NORTHERN GARAGE FOR LEVEL 4 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | | | | 13. SHEET A1-212 NORTHERN GARAGE FOR LEVEL 5-7 REMOVES | | | 44 BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | | | | 14.SHEET A1-215 NORTHERN GARAGE FOR LEVEL 8 REMOVES 44 | | | BICYCLE PARKING SPACES. WHERE HAVE THESE BEEN | | | RELOCATED, WHAT IS THE TOTAL BICYCLE PARKING COUNT ON | | | SITE? | | | | | | 15. PLEASE PROVIDE PARKING STALL DETAIL WITHIN ARCH | | | SETS. | | | | | | 16. PLEASE PROVIDE GARAGE SCREENING DETAILS AND | | | MATERIAL DETAILS WITH THE ELEVATION DRAWINGS. | | | | | | 17. DOUBLE CHECK LANDSCAPE SHEETS TO REFLECT APPROVAL. | | | 285 GROUND LEVEL LANDSCAPE PLAN APPEARS TO MISS STREE | | | TREES ALONG BANYAN FRONTAGE. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822-1426 [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2023-03-03 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2023-03-03 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2023-03-03 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2023-03-03 09:37:31 | - THE ARCHITECTURAL PLANS SUBMITTED WITH PERMIT DO NOT | | | MATCH THE APPROVED SITE PLANS. SUBMITTED PLANS ARE | | | DATED 12.13.22 AND SIGNED ON 12.16.22, THE FINAL SITE | | | PLAN APPROVAL SET WAS DATED 12.16.22 AND SIGNED ON | | | 01.05.23. PLEASE SUBMIT THE CORRECT SET OF DRAWINGS. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822-1426 [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2023-02-06 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2023-02-06 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2023-02-06 10:09:33 | FAILED PER DISCUSSION WITH APPLICANT, ZONING SHALL | | | REVIEW RESUBMITTAL. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-12-28 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2022-12-28 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2022-12-28 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2022-12-28 14:30:32 | FINAL SITE PLAN APPROVAL FOR TRANSIT VILLAGE HAS NOT | | | BEEN ISSUED, ZONING WILL NOT PASS REVIEW UNTIL FINAL | | | SITE PLAN LETTER IS ISSUED AND ALL COMMENTS/CONDITIONS | | | HAVE BEEN OUTLINED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-15 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2022-12-15 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2022-12-15 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2022-12-15 11:30:54 | FINAL SITE PLAN APPROVAL FOR TRANSIT VILLAGE HAS NOT | | | BEEN ISSUED, ZONING WILL NOT PASS REVIEW UNTIL FINAL | | | SITE PLAN LETTER IS ISSUED AND ALL COMMENTS/CONDITIONS | | | HAVE BEEN OUTLINED. |
|
|
|
Account Summary | Usage Policy | Privacy Policy