Plan Review Details - Permit 22101226
Plan Review Stops For Permit 22101226
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-11-22 Cont ID  
Sent By fgiaquin Date 2022-11-22 Time 21:08 Rev Time 0.00
Received By fgiaquin Date 2022-10-27 Time 21:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-12-15 Cont ID  
Sent By ccole Date 2022-12-15 Time 10:11 Rev Time 0.00
Received By ccole Date 2022-12-15 Time 10:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By ccole Date 2022-11-17 Time 07:33 Rev Time 0.00
Received By ccole Date 2022-11-17 Time 07:33 Sent To  
Notes
2022-11-17 07:36:271ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22101226
 11/17/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT REVISED GAS PLANS AND RISER DRAWINGS
 SHOWING THE LOCATIONS OF FUTURE GAS APPLIANCES AND
 PIPED CAP LOCATIONS- SEC. 107.2.1 & 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-04 Cont ID  
Sent By medwards Date 2023-01-04 Time 13:52 Rev Time 0.00
Received By medwards Date 2023-01-04 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-22 Cont ID  
Sent By fgiaquin Date 2022-11-22 Time 21:09 Rev Time 0.00
Received By fgiaquin Date 2022-10-29 Time 08:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-01-04 Cont ID  
Sent By medwards Date 2023-01-04 Time 13:51 Rev Time 0.00
Received By medwards Date 2023-01-04 Time 13:51 Sent To  
Notes
2023-01-04 13:52:17PER MECHANICAL RESPONSE LETTER SUBMITTED 12/21/2022
 MECHANICAL IS APPROVED ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-15 Cont ID  
Sent By medwards Date 2022-11-15 Time 06:18 Rev Time 0.00
Received By medwards Date 2022-11-15 Time 06:18 Sent To  
Notes
2022-11-22 13:13:021ST REVIEW FMC
 PERMIT: 22101226
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE EXPLAIN HOW THESE INTERIOR SPACES WILL BE
 CONDITIONED TO MEET THE HEATING REQUIREMENTS OF FMC
 309.1
  
 [BG] 309.1 SPACE-HEATING SYSTEMS. INTERIOR SPACES
 INTENDED FOR HUMAN OCCUPANCY SHALL BE PROVIDED WITH
 ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS CAPABLE OF
 MAINTAINING AN INDOOR TEMPERATURE OF NOT LESS THAN
 68???F (20???C) AT A POINT 3 FEET (914 MM) ABOVE FLOOR
 ON THE DESIGN HEATING DAY. THE INSTALLATION OF PORTABLE
 SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE
 WITH THIS SECTION.
 EXCEPTIONS:
 1. INTERIOR SPACES WHERE THE PRIMARY PURPOSE IS NOT
 ASSOCIATED WITH HUMAN COMFORT.
 2. GROUP F, H, S AND U OCCUPANCIES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-12-15 Cont ID  
Sent By ccole Date 2022-12-15 Time 10:11 Rev Time 0.00
Received By ccole Date 2022-12-15 Time 10:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By ccole Date 2022-11-16 Time 17:55 Rev Time 0.00
Received By ccole Date 2022-11-16 Time 17:34 Sent To  
Notes
2022-11-16 17:55:291ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22101226
 11/16/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS APPEAR TO SHOW THE PLUMBING REVISION IS TO
 INSTALL THE PIPING FOR THE KITCHEN AND BAR AND CAP THE
 LINES FOR FUTURE USE. PLEASE PLACE NOTES ON THE PLANS
 ACCORDINGLY TO CLARIFY AND SUBMIT REVISED RISER
 DRAWINGS ALSO NOTING THE CAP LOCATIONS- SECS. 107.2.1 &
 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-15 Cont ID  
Sent By ccole Date 2022-12-15 Time 10:12 Rev Time 0.00
Received By ccole Date 2022-12-15 Time 10:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-22 Cont ID  
Sent By fgiaquin Date 2022-11-22 Time 21:09 Rev Time  
Received By fgiaquin Date   Time   Sent To  
Notes
2022-11-15 06:19:19MECHANICAL DIGITAL SIGNATURES APPROVED ME
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved