Plan Review Details - Permit 22101138
Plan Review Stops For Permit 22101138
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-16 Cont ID  
Sent By rmcphers Date 2023-06-16 Time 15:51 Rev Time 0.00
Received By rmcphers Date 2023-06-16 Time 15:49 Sent To  
Notes
2023-06-16 15:51:25CANOPY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ROOF PANEL ATTACHMENTS - FBC WPB
 107.2.1
  
 2) DRAWINGS NEED TO BE SIGNED AND SEALED BY A
 REGISTERED DESIGN PROFESSIONAL - FBC WPB 107.2.1. /
 107.3.4
  
 3) PLEASE SHOW HOW THE ROOF DRAINS AWAY FROM THE
 BUILDING (FLASHING, CRICKETS, ROOF SLOPE ETC.) - FBC
 1503.4
  
 4) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE
 FOLLOWING INFORMATION FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
 5) JOB COST SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - JOB COST SHALL INCLUDE THE COST OF
 ALL MATERIAL AND LABOR AS IF THE JOB IS NEW - PLEASE
 REVISE THE BUILDING PERMIT APPLICATION TO SHOW THE
 CORRECT JOB COST - FBC WPB 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-18 Cont ID  
Sent By rmcphers Date 2022-11-18 Time 11:26 Rev Time 0.00
Received By rmcphers Date 2022-11-18 Time 11:02 Sent To  
Notes
2022-11-18 11:26:05CANOPY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE CODE VERSION USED FOR DESIGN.
  
 2) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND
 DESIGN - FBC 1603.1.4
  
 3) PLEASE SHOW THE ROOF PANEL ATTACHMENTS - FBC WPB
 107.2.1
  
 4) DRAWINGS NEED TO BE SIGNED AND SEALED BY A
 REGISTERED DESIGN PROFESSIONAL - FBC 107.2.1.
  
 5) PLEASE SHOW HOW THE ROOF DRAINS AWAY FROM THE
 BUILDING (FLASHING, CRICKETS, ROOF SLOPE ETC.) - FBC
 1503.4
  
 6) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE
 FOLLOWING INFORMATION FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
 7) JOB COST SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - JOB COST SHALL INCLUDE THE COST OF
 ALL MATERIAL AND LABOR AS IF THE JOB IS NEW - PLEASE
 REVISE THE BUILDING PERMIT APPLICATION TO SHOW THE
 CORRECT JOB COST - FBC WPB 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2023-06-14 Cont ID  
Sent By pleduc Date 2023-06-14 Time   Rev Time 0.00
Received By pleduc Date 2023-06-14 Time 14:47 Sent To  
Notes
2023-06-14 14:52:43THE PREVIOUS COMMENTS FROM FIRE WERE NOT SPECIFICAALY
 ADDRESS AND HAVE BEED RESUBMITTED BELOW:
  
  
 *******************************************************
 *******************************************************
 ***********
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE REPLACEMENT OF
 EXISTING MATERIAL; HOWEVER, THERE IS NO SITE PLAN
 SHOWING THE LOCATION OF THE EXISTING STRUCTURE.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDEA SITE PLAN
 INDICATING WHERE THE PROPOSED REPLACEMENT STRUCTURE IS
 LOCATED
  
  
 2) PLEASE PROVIDE DETAILS IF THERE IS ANY ELECTRICAL
 WORK IS PROPOSED OR IS BEING SYBMITTED UNDER SEPARATE
 PERMIT.
  
  
  
 3) PLEASE PROVIDE DETAILS IF THERE IS ANY EXITING
 THROUGH THIS AREA AND IF THE WORK WILL BE DONE WHILE
 THE OCCUPANCY IS OPEN.
  
 IF OPEN AND EXTING OCCURS THROUGH THIS AREA, PLEASE
 PROVIDE DETAILS FOR ALTERNATIVE EXITS/EXIT ROUTING.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-26 Cont ID  
Sent By pleduc Date 2022-10-26 Time   Rev Time 0.00
Received By pleduc Date 2022-10-26 Time 11:46 Sent To  
Notes
2022-10-26 11:57:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE REPLACEMENT OF
 EXISTING MATERIAL; HOWEVER, THERE IS NO SITE PLAN
 SHOWING THE LOCATION OF THE EXISTING STRUCTURE.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDEA SITE PLAN
 INDICATING WHERE THE PROPOSED REPLACEMENT STRUCTURE IS
 LOCATED
  
  
 2) PLEASE PROVIDE DETAILS IF THERE IS ANY ELECTRICAL
 WORK IS PROPOSED OR IS BEING SYBMITTED UNDER SEPARATE
 PERMIT.
  
  
  
 3) PLEASE PROVIDE DETAILS IF THERE IS ANY EXITING
 THROUGH THIS AREA AND IF THE WORK WILL BE DONE WHILE
 THE OCCUPANCY IS OPEN.
  
 IF OPEN AND EXTING OCCURS THROUGH THIS AREA, PLEASE
 PROVIDE DETAILS FOR ALTERNATIVE EXITS/EXIT ROUTING.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2023-07-18 Cont ID  
Sent By amhamilt Date 2023-07-18 Time 12:24 Rev Time 0.00
Received By amhamilt Date 2023-07-18 Time 12:24 Sent To  
Notes
2023-07-18 12:24:48PREVIOUS COMMENTS NOT ADDRESSED

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-12-02 Cont ID  
Sent By amhamilt Date 2022-12-02 Time 11:07 Rev Time 0.00
Received By amhamilt Date 2022-12-02 Time 11:07 Sent To  
Notes
2022-12-02 11:08:03THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 SEE ZONING COMMENTS. NEED MORE INFORMATION ABOUT
 EXISTING AND PROPOSED AWNINGS--AT MINIMUM PHOTOS OF
 EXISTING AWNING AND SITE PLAN/SURVEY WITH LOCATION OF
 AWNING.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-19 Cont ID  
Sent By aoliver Date 2023-07-19 Time 08:32 Rev Time 0.00
Received By aoliver Date 2023-06-13 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-05 Cont ID  
Sent By aoliver Date 2022-12-05 Time 10:23 Rev Time 0.00
Received By aoliver Date 2022-10-25 Time 17:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-06-16 Cont ID  
Sent By rmcphers Date 2023-06-16 Time 15:51 Rev Time 0.00
Received By rmcphers Date 2023-06-16 Time 15:51 Sent To  
Notes
2023-06-16 15:51:59SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS WILL NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 PROJECTDOX.
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-18 Cont ID  
Sent By rmcphers Date 2022-11-18 Time 11:27 Rev Time 0.00
Received By rmcphers Date 2022-11-18 Time 11:27 Sent To  
Notes
2022-11-18 11:29:40SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS WILL NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 PROJECTDOX.
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-06-27 Cont ID  
Sent By vbroglia Date 2023-06-27 Time 09:43 Rev Time 0.00
Received By vbroglia Date 2023-06-27 Time 09:43 Sent To  
Notes
2023-06-27 09:44:05SEE PREVIOUS COMMENTS FROM 11/17/2022

Review Stop Z ZONING
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By vbroglia Date 2022-11-17 Time 16:11 Rev Time 0.00
Received By vbroglia Date 2022-11-17 Time 16:11 Sent To  
Notes
2022-11-17 16:13:3511/17/2022 FAILED
  
 PLEASE SHOW AN ELEVATION SHOWING HOW FAR THE AWINING
 WILL PROJECT, PER CODE PLEASE NOTE:
  
 AWNINGS SHALL NOT PROJECT MORE THAN FOUR FEET INTO ANY
 SETBACK OR BE SUPPORTED BY ANY MEANS OTHER THAN
 ATTACHMENT TO THE BUILDING.
  
 PLEASE SHOW A SURVEY OR SITE PLAN WHERE THE SCOOP OF
 WORK WILL TAKE PLACE.
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  