| 2022-11-02 11:47:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION ON THE APPLICATION OF "TILING |
| | A BEDROMM AND DEN USING 8" CONCRETE FLOOR WITH A GYPSUM |
| | BOARD CEILING ASSEMBLY." |
| | |
| | THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE |
| | LOCATION OF THE PROPOSED TILE NOR OF ANY PROPOSED |
| | CEILING ASSEMBLY. |
| | |
| | PER NFPA 101 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN |
| | INDICATING THE LOCATION OF ALL PROPOSED WORK. |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION ON THE APPLICATION OF A |
| | CEILING ASSEMBLY, BUT NO CONSTRUCTION CALL-OUT OF WHAT |
| | THE ASSEMBLY CONSIST OF, FASTENING DEVICES, LISTING |
| | SPECIFICATIONS, FIRE SPRINKLER LOCATIONS/MODIFICATIONS, |
| | FIRE ALARM, SMOKE ALARM, ELECTRICAL WORK, ETC. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A DETAILED |
| | DRAWING/PLAN OF THE CEILING ASSEMBLY AND ALL APPLICABLE |
| | SPECIFICATIONS. |
| | |
| | |
| | 2A) ANY FIRE SPRINKLER WORK, INCLUDING DEMO, SHALL BE |
| | COMPLETED UNDER SEPARATE PERMIT AND SHOP DRAWINGS IN |
| | COMPLIANCE WITH NFPA 13. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 2B) ANY FIRE ALARM WORK, INCLUDING DEMO, SHALL BE |
| | COMPLETED UNDER SEPARATE PERMIT AND SHOP DRAWINGS IN |
| | COMPLIANCE WITH NFPA 13. |
| | |
| | PLEASE REVIEW AND IF APPLICABLE, ENSURE COMPLIANCE. |
| | |
| | |
| | 2C) SMOKE ALARM MODIFICATIONS, RELOCATION, NEW |
| | INSTALLATIONS SHALL BE REFLECTED ON THE ELECTICAL |
| | DRAWING/PLAN. |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |