| Plan Review Stops For Permit 22101064 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-12-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-12-08 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-12-08 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2022-12-08 15:38:08 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE DRAWINGS INDICATE THAT THE SHED IS TO BE USED | | | FOR STORAGE AND WILL NOT BE USED AS HABITABLE SPACE. | | | THE SURVEY (DATED 8/15/1988) SHOWS THAT THE SHED WAS ON | | | THE PROPERTY AT THAT TIME. THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DRAWINGS IS | | | REQUIRED TO BE ON THEM. FBC 107.2.1 - INFORMATION ON | | | CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. | | | | | | 2) SPECIFY THE SIZE OF THE WINDOW AND DOOR OPENING IN | | | THE EXISTING SHED ON THE PLANS. IF THE OPENINGS ARE | | | MODIFIED TO ACCOMADATE THE NEW DOOR OR WINDOW, SUBMIT | | | STRUCTURAL DRAWINGS FOR THE OPENINGS. FBC 107.2.1 | | | | | | 3) THE FLORIDA PRODUCT APPROVAL COVERSHEET IS MISSING | | | FOR THE GLAZED DOOR. SUBMIT THE COMPLETE PRODUCT | | | APPROVAL FOR THE DOOR. CIRCLE OR HI-LIGHT THE DOOR | | | SIZE, GLASS TYPE AND DESIGN PRESSURES FOR THE DOOR ON | | | THE PRODUCT APPROVAL.FBC 107.3.4 | | | | | | 4) CIRCLE OR HI-LIGHT THE WINDOW TYPE, DIMENSIONS AND | | | DESIGN PRESSURES ON THE CHARTS IN THE WINDOW PRODUCT | | | APPROVAL. FBC 107.2.1 | | | | | | 5) PROVIDE A FLASHING DETAIL TO SHOW HOW THE DOOR AND | | | WINDOW IS GOING TO BE FLASHED. FBC 107.2.1 | | | | | | 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-11-01 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-11-01 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2022-11-01 15:37:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE CITY HAS NO RECORD OF THE SHED THAT IS SHOWN IN | | | THE DRAWING. PROVIDE THE PERMIT DOCUMENTS, PLANS, ETC. | | | FOR THE SHED. IF YOU ARE UNABLE TO SHOW THAT THE SHED | | | WAS PERMITTED IT WILL HAVE TO BE REMOVED OR BROUGHT | | | INTO COMPLIANCE. FROM THE LISTING AT THIS ADDRESS ON | | | ZILLOW, IT APPEARS THAT THE SHED MAY BE A MANUFACTURED | | | BUILDING AND THAT THE PROPOSED WORK HAS ALREADY BEEN | | | COMPLETED. THE FIRST THING TO DO IS SHOW THAT THE SHED | | | IS CONSTRUCTUTED CORRECTLY TO RESIST A VULT WIND SPEED | | | OF 170 MPH. IF IT IS A MANUFACTURED BUILDING YOU WILL | | | NEED TO SUBMIT THE APPROVED DRAWINGS FROM THE STATE | | | DBPR ALONG WITH THE TIE DOWN ENGINEERING. IF IT IS SITE | | | BUILD STRUCTURE YOU WILL NEED TO SUBMIT THE PLANS TO | | | SHOW THAT IT COMPLIES WITH THE WINDLOADS. SINCE THE | | | SHED IS BEING CONVERTED TO HABITABLE SPACE IT WILL HAVE | | | TO BE REVIEWED BY PALM BEACH COUNTY TO SEE IF ANY | | | IMPACT FEES ARE OWED. IT WILL ALSO NEED TO COMPLY WITH | | | THE ENERGY AND ELECTRICAL CODES. SINCE THE WORK HAS | | | BEEN COMPLETED AND COVERED WITH DRYWALL. THE DRYWALL | | | MAY NEED TO BE REMOVED SO THAT THE FRAMING AND | | | INSULATION CAN BE INSPECTED. FBC 107.2.1 & FBC-R301 | | | | | | 2) THE SCOPE OF WORK FOR THIS PROJECT IS NOT CLEAR. | | | PROVIDE A DETAILED SCOPE OF WORK WITH DRAWINGS AND | | | SECTIONS AS REQUIRED TO CLEARLY SHOW THE ENTIRE SCOPE | | | OF THE PROPOSED WORK. FBC 107.2.1 | | | | | | 3) THERE HAS NOT BEEN ENOUGH INFORMATION PROVIDED TO | | | COMPLETE A THROUGH REVIEW. ADDITIONAL COMMENTS MAY | | | RESULT WHEN THE REQUESTED INFORMATION IS PROVIDED. FBC | | | 107.2.1 | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-11-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-29 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-29 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2022-11-29 12:46:12 | ELECTRIC REVIEW FAILED | | | 1) ELECTRICAL PLAN DETAILS MORE THAN ONE CIRCUIT. THIS | | | IS NOT IN COMPLIANCE WITH NEC 225.30 WHICH STATES AS | | | FOLLOWS: | | | A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A | | | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE | | | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE | | | FEEDER OR BRANCH CIRCUIT. PLEASE CORRECT AS APPLICABLE | | | 2) PLEASE DETAIL WIRING METHODS USED. I.E. ROMEX, | | | CONDUIT, PLEASE DETAIL COMPLIANCE WITH APPLICABLE NEC | | | CODES. IE UNDERGROUND WIRING, INTERIOR WIRING ETC. FBC | | | 107.2 | | | 3) THERE ARE TWO ELECTRICAL PLANS SUBMITTED, PLEASE | | | SUBMIT ONLY THE CORRECT ELECTRICAL PLAN. FBC 107.2 | | | 4) IT APPEARS THERE IS NO CONTROLLING SWITCH FOR | | | OUTSIDE AND INSIDE LIGHTING OUTLETS. PLEASE DETAIL HOW | | | THESE LIGHTS ARE CONTROLLED TO COMPLY WITH NEC 210.70 | | | (A)(2)(2) AND NEC 210.70 (A)(3) | | | 5) ELECTRICAL PLAN DETAILS ELECTRICAL OUTLETS AS | | | EXISTING. I CAN NOT FIND ANY PERMIT RECORDS FOR THE | | | INSTALLATION OF THESE OUTLETS. PLEASE PROVIDE A PASSED | | | PERMIT RECORD FOR THE INSTALLATION OF THESE OUTLETS. | | | FBC 107.2 | | | | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-01 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-01 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2022-11-01 15:59:53 | ELECTRIC REVIEW FAILED | | | | | | 1) PROPOSED PLAN APPEARS TO BE INCOMPLETE, NO DOOR IS | | | SHOWN. NEED TO DETAIL COMPLIANCE WITH NEC 210 AND ALL | | | APPLICABLE ARTICLES FOR LIGHTING OUTLETS REQUIRED. FBC | | | 107.2 | | | 2) PLEASE DETAIL WIRING METHODS USED, CONDUCTOR SIZES | | | AND OVERCURRENT PROTECTION. NEC 215.5 AND 300 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-12-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-12-08 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-11-14 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-01 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-24 |
Time |
07:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-11-01 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-11-01 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2022-11-01 11:17:09 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-17 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-17 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2022-11-17 15:41:25 | THE PERMIT APPLICATION FOR THIS PROJECT CLEARLY STATES | | | THAT THIS APPLICATION IS FOR INTERIOR CONVERSION TO | | | LIVING. PROVIDE ANSWERS TO THE ORIGINAL REVIEW COMMENTS | | | BELOW: | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS | | | NEWLY CONVERTED STRUCTURE. FEC R101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THIS NEWLY CONVERTED STRUCTURE. FEC | | | R403.7.1 | | | | | | 3) PLEASE PROVIDE A MECHANICAL SYSTEM DESIGN AND | | | DRAWING INDICATING THE LOCATION OF THE INDOOR UNIT AND | | | THE OUTDOOR UNIT. FBC 107.3.5 | | | | | | 4) PLEASE SHOW THAT THE MECHANICAL SYSTEM WILL PROVIDE | | | THE REQUIRED HEAT FOR THIS LIVING SPACE. FRC R303.10 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-01 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-01 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2022-11-01 14:32:05 | 1ST REVIEW FMC | | | PERMIT: 22101064 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS | | | NEWLY CONVERTED STRUCTURE. FEC R101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THIS NEWLY CONVERTED STRUCTURE. FEC | | | R403.7.1 | | | | | | 3) PLEASE PROVIDE A MECHANICAL SYSTEM DESIGN AND | | | DRAWING INDICATING THE LOCATION OF THE INDOOR UNIT AND | | | THE OUTDOOR UNIT. FBC 107.3.5 | | | | | | 4) PLEASE SHOW THAT THE MECHANICAL SYSTEM WILL PROVIDE | | | THE REQUIRED HEAT FOR THIS LIVING SPACE. FRC R303.10 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-11-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2022-11-01 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-11-01 10:26:31 | NO PLUMBING SHOWN |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2022-12-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-12-08 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-12-08 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-11-01 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-11-01 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2022-11-01 13:05:25 | THE SIGNATURE REQUIREMENT WILL BE CHECKED WHEN THE | | | REQUESTED INFORMATION HAS BEEN SUBMITTED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-11-21 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-11-21 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-11-21 |
Time |
13:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-27 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-10-27 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-10-27 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2022-10-27 10:15:58 | FAILED | | | 10/27/2022 | | | | | | | | | PLEASE PROVIDE A SURVEY WITH APPLICATION ALSO PLEASE | | | PROVIDE MORE INFORMATION REGARDING WHAT TYPE OF SPACE | | | THE SHED IS GOING TO BE CONVERTED TO. | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|