Plan Review Details - Permit 22101061
Plan Review Stops For Permit 22101061
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By mpeterso Date 2022-11-28 Time 08:57 Rev Time 0.00
Received By mpeterso Date 2022-11-28 Time 08:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-11-03 Cont ID  
Sent By jleahy Date 2022-11-03 Time 16:04 Rev Time 0.00
Received By mpeterso Date 2022-11-03 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-14 Cont ID  
Sent By medwards Date 2022-12-14 Time 11:29 Rev Time 0.00
Received By medwards Date 2022-12-06 Time 07:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-28 Cont ID  
Sent By mpeterso Date 2022-11-28 Time 08:59 Rev Time 0.00
Received By mpeterso Date 2022-11-06 Time 06:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-03 Cont ID  
Sent By mpeterso Date 2022-11-03 Time 16:06 Rev Time 0.00
Received By mpeterso Date 2022-10-24 Time 07:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-12-14 Cont ID  
Sent By medwards Date 2022-12-14 Time 11:26 Rev Time 0.00
Received By medwards Date 2022-12-14 Time 11:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-15 Cont ID  
Sent By medwards Date 2022-11-15 Time 15:56 Rev Time 0.00
Received By medwards Date 2022-11-15 Time 15:56 Sent To  
Notes
2022-11-15 15:56:212ND REVIEW FMC
 PERMIT: 22101061
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 SUBMITTED THIS CYCLE INDICATE AN AREA OF 2400 SQ. FT.
 IS TO BE CONDITIONED. IT IS NOT CLEAR IF THIS IS THE
 SALES, KITCHEN AREA, OFFICE SPACE AND STORAGE OR JUST A
 PORTION OF THIS TENANT SPACE. THE TOTAL SIZE OF THE
 SYSTEM IS TO BE 9.30 TONS. THE NEWLY SUBMITTED SHEET
 M6.1 SHOWS THE EXISTING RTU IS 124,100 BTU???S THIS
 DIVIDED BY 12000 = 10.34 TONS. THE NEWLY SUBMITTED FC-1
 HAS A TOTAL BTU LOAD OF 24000 BTU???S, THIS DIVIDED BY
 12000 = 2 TONS. THIS MEANS THE TOTAL OF ALL SYSTEMS IS
 12.34 TONS. THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS CALLS FOR 9.30 TONS. THIS MEANS THE
 MECHANICAL SYSTEM IS OVER SIZED BY 3.04 TONS. IT IS
 UNCLEAR TO THIS REVIEWER WITH THE DRAWINGS SUBMITTED IF
 THE ENERGY CALCULATIONS IS ONLY FOR THE FRONT OF THE
 TENANT SPACE OR FOR THE ENTIRE SPACE. THE OUTSIDE AIR
 CALCULATIONS SEEM TO BE FOR THE ENTIRE TENANT SPACE. IF
 THIS IS FOR THE ENTIRE TENANT SPACE THEN THE MECHANICAL
 DESIGN IS TOO LARGE FOR THE TENANT SPACE AND THE
 DESIGNER MUST COMPLY WITH FEC C403.2.2. THE RESPONSE
 LETTER INDICATED THAT THE SYSTEM WAS UPSIZED BECAUSE OF
 HUMIDITY AND IT BEING FLORIDA. IF THE UNITS ARE OVER
 SIZED THEN IN FACT THE UNITS WOULD SHORT CYCLE WHICH
 MEANS THEY WOULD SHUT OFF ONCE THE THERMOSTAT
 TEMPERATURE HAS BEEN MET. THIS WOULD HAPPEN QUICKER
 THAN IF THE SYSTEM WAS SIDED CORRECTLY. THIS IN TURN
 WOULD MEAN THE SYSTEMS WOULD SHUT OFF BEFORE THE
 HUMIDITY HAD BEEN REMOVED FROM THE BUILDING. THE
 SYSTEMS MUST MEET THE REQUIREMENTS OF FEC C403.2.2.
 PLEASE PROVIDE THE SQUARE FOOTAGE THAT EACH MECHANICAL
 SYSTEM IS SUPPLYING AND SIZE EACH UNIT ACCORDING TO FEC
 C403.2.1 AND C403.2.2
  
 C403.2.2 EQUIPMENT SIZING. THE OUTPUT CAPACITY OF
 HEATING AND COOLING EQUIPMENT SHALL BE NOT GREATER THAN
 THE
 LOADS CALCULATED IN ACCORDANCE WITH SECTION C403.2.1. A
 SINGLE PIECE OF EQUIPMENT PROVIDING BOTH HEATING AND
 COOLING SHALL SATISFY THIS PROVISION FOR ONE FUNCTION
 WITH THE CAPACITY FOR THE OTHER FUNCTION AS SMALL AS
 POSSIBLE, WITHIN AVAILABLE EQUIPMENT OPTIONS.
  
 2) WITH THE NEWLY ADDED FC-1 ADDED FOR THE STORAGE AND
 OFFICE PLEASE SHOW HOW THE REQUIRED OUTSIDE AIR WILL BE
 INTRODUCED TO THE RETURN SIDE OF THE FC-1 SYSTEM. FMC
 403.3.1.1
  
 3) THE CONDENSING UNIT FOR FC-1 LOCATED ON THE ROOF
 WILL NEED TO MEET THE ROOF EDGE CLEARANCES OR INSTALL
 GUARDS PER FMC 304.11
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-03 Cont ID  
Sent By medwards Date 2022-10-31 Time 11:43 Rev Time 0.00
Received By medwards Date 2022-10-31 Time 11:43 Sent To  
Notes
2022-10-31 14:56:581ST REVIEW FMC
 PERMIT: 22101061
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS NEW FC-1. FEC C403.2.1
  
 2) PROVIDE A ROOF DRAWING INDICATING WHERE THE NEW
 CONDENSING UNIT FORFC-1 WILL BE LOCATED. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2022-10-31 11:44:00 
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-15 Cont ID  
Sent By rwbrown Date 2022-11-15 Time 14:29 Rev Time 0.00
Received By rwbrown Date 2022-11-15 Time 14:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-28 Cont ID  
Sent By ccole Date 2022-10-28 Time 11:24 Rev Time 0.00
Received By ccole Date 2022-10-28 Time 10:52 Sent To  
Notes
2022-10-28 11:25:171ST REVIEW FBC-2020 PLUMBING
 PERMIT-22101061
 10/28/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1.1 & P6.1: THE CONDENSATE FROM THE NEW FAN
 COIL UNIT SHALL NOT DRAIN INTO THE SANITARY IN
 ACCORDANCE WITH SEC. 90-126 (5) WPB CODE OF ORDINANCES.
 PLEASE RELOCATE TO AN APPROVED LOCATION SUCH AS THE
 STORM DRAIN OR TO A DRY WELL ON THE EXTERIOR OF THE
 BUILDING- SEC. 314.2.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-14 Cont ID  
Sent By medwards Date 2022-12-14 Time 11:27 Rev Time 0.00
Received By medwards Date 2022-12-14 Time 11:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By mpeterso Date 2022-11-28 Time 08:58 Rev Time 0.00
Received By mpeterso Date 2022-11-28 Time 08:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-03 Cont ID  
Sent By mpeterso Date 2022-11-03 Time 16:06 Rev Time 0.00
Received By mpeterso Date 2022-11-03 Time 16:06 Sent To  
Notes
2022-10-31 14:58:57MECHANICAL DIGITAL SIGNATURES APPROVED ME
  
2022-10-28 10:55:19PLUMBING PLANS ARE GOOD.