| 2022-10-31 08:18:10 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND 105.1 - THE TEST REPORT TO CERTIFY A |
| | BACKFLOW IS NOT REQUIRED FOR PLAN REVIEW. THE BACKFLOW |
| | CANNOT BE TESTED BEFORE THE PERMIT IS ISSUED. A PERMIT |
| | IS REQUIRED TO INSTALL THE BACKFLOW. IF AN EMERGENCY |
| | REPAIR IS NEEDED, PER 105.2.1 YOU CAN CONTACT THE |
| | BUILDING DEPARTMENT AT [email protected] AND COPY ME AT |
| | [email protected] AND NOTIFY US OF THE EMERGENCY REPAIR |
| | BEFORE THE WORK BEGINS. THEN, WITHIN 24 HOURS OR ONE |
| | BUSINESS DAY, YOU NEED TO SUBMIT THE APPLICATION FOR |
| | THE WORK PERFORMED. |
| | |
| | 2. 2017 WPB AMEND - 107.3.5 - AS PART OF THE |
| | REQUIREMENTS FOR A BACKFLOW PERMIT, PLEASE PROVIDE A |
| | BASIC SITE PLAN SHOWING THE LOCATION OF THE BACKFLOW |
| | PREVENTER. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |