Plan Review Details - Permit 22100891
Plan Review Stops For Permit 22100891
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-12-15 Cont ID  
Sent By jbrooks Date 2022-12-15 Time 10:26 Rev Time 0.00
Received By jbrooks Date 2022-12-15 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-12-12 Cont ID  
Sent By jbrooks Date 2022-12-12 Time 14:27 Rev Time 0.00
Received By jbrooks Date 2022-12-12 Time 14:26 Sent To  
Notes
2022-12-12 14:27:28JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 (FL1654-R30)
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R30 SYSTEM NO. W-60 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-01 Cont ID  
Sent By jbrooks Date 2022-12-01 Time 11:05 Rev Time 0.00
Received By jbrooks Date 2022-12-01 Time 07:51 Sent To  
Notes
2022-12-01 11:06:07JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED ROOF DIAGRAM/SKETCH APPEARS
 TO INDICATE REROOFING LOW/FLAT SLOPE AREA; IF NOT
 INDICATE BY PLACING AN X IN LOW/FLAT SLOPE AREAS; IF TO
 RECEIVE NEW ROOFING PROVIDE A COMPLETE SET OF 2020 CODE
 VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED FLAT
 ROOF SYSTEM TO BE USED. INCLUDE COVER PAGE, EVALUATION
 REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. REVISE
 ROOF DIAGRAM/SKETCH TO INCLUDE MEAN ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By jbrooks Date 2022-10-25 Time 08:51 Rev Time 0.00
Received By jbrooks Date 2022-10-25 Time 07:39 Sent To  
Notes
2022-10-25 08:51:37JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL27499.1-R4 COVERS MULTIPLE INSTALLATION
 OPTIONS TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT
 CORRECT INSTALLATION OPTION FROM PAGE #2 OF THE
 EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM
 DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE
 CATEGORY C AREAS. (-121.). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL10626-R23
 HAS BEEN REVISED TO FL10626-R24. PLEASE PROVIDE A
 COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF
 COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS, ALLOWABLE SUBSTRATES & ATTACHMENT
 LIMITATIONS. SELECT OPTIONS FROM EACH CATEGORY TO BE
 USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH TO INDICATE THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING AND INCLUDE ROOF
 SLOPE(S), MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS
 MUST SHOW POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-12-06 Cont ID  
Sent By amhamilt Date 2022-12-06 Time 15:32 Rev Time 0.00
Received By amhamilt Date 2022-12-06 Time 15:32 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-11-17 Cont ID  
Sent By amhamilt Date 2022-11-17 Time 16:44 Rev Time 0.00
Received By amhamilt Date 2022-11-17 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-15 Cont ID  
Sent By jbrooks Date 2022-12-15 Time 10:26 Rev Time 0.00
Received By jbrooks Date 2022-12-13 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-12 Cont ID  
Sent By jbrooks Date 2022-12-12 Time 14:27 Rev Time 0.00
Received By jbrooks Date 2022-12-08 Time 06:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-07 Cont ID  
Sent By aoliver Date 2022-12-07 Time 12:58 Rev Time 0.00
Received By aoliver Date 2022-11-28 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-18 Cont ID  
Sent By lmarchan Date 2022-11-18 Time 13:07 Rev Time 0.00
Received By lmarchan Date 2022-10-24 Time 08:13 Sent To  
Notes
***NONE***