| Plan Review Stops For Permit 22100890 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2023-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-23 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-23 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-15 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-15 |
Time |
11:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2023-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-08 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-08 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-13 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-13 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2023-02-13 10:20:04 | CHANGE OF OCCUPANCY CLASSIFICATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | 3RD REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SIGNED AND SEALED DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-01-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-18 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-18 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2023-01-18 09:15:43 | CHANGE OF OCCUPANCY CLASSIFICATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SIGNED AND SEALED DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-08 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-08 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2022-11-08 15:13:41 | CHANGE OF OCCUPANCY CLASSIFICATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE NEW OCCUPANCY CLASSIFICATION PER FBC | | | CHAPTER 3 (DESCRIBE THE USE FOR THE SPACE SUCH AS - | | | RETAIL, OFFICE, NIGHT CLUB, THEATER ETC..) (EVENT SPACE | | | - WHAT TYPE OF EVENT?) | | | | | | 2) PLEASE SHOW THE UNIT SQUARE FOOTAGE. FBC WPB 107.2 | | | | | | 3) SHOW ALL DIMENSIONS BETWEEN WALLS. FBC WPB 107.2 | | | | | | 4) PLEASE SHOW THE STAGE OR PLATFORM DETAILS - FBC 410 | | | | | | 5) PLEASE SHOW THE KITCHEN DETAILS - FBC WPB 107.2 | | | | | | 6) SHOW THE HOURLY FIRE RATINGS FOR THE TENNANT | | | SEPARATION WALLS - FBC 508 | | | | | | 7) PLEASE SHOW THE USE FOR EACH ADJACENT TENNANT - FBC | | | 508 | | | | | | 8) THE DRAWING PROVIDED HAS A BLACKED OUT AREA - PLEASE | | | PROVIDE A DRAWING WITH OUT THE BLACKED OUT AREA. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2023-02-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-02-22 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-02-22 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2023-02-22 15:58:05 | NO ELECTRICAL WORK SHOWN JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-25 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-25 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2023-01-25 16:22:55 | SEE 11/8/22 REVIEW JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-11-08 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-11-08 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2022-11-08 16:14:54 | NO ELECTRICAL WORK SHOWN PLEASE SHOW ALL ELECTRICAL | | | WORK NEW AND EXISTING. JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-14 |
Time |
09:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-07 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2023-02-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2023-01-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-25 10:35:31 | FIRE REVIEW COMMENTS: | | | | | | (1) THE OCCUPANT LOAD CALCULATIONS ARE NOT CORRECT. THE | | | DANCE FLOOR SHALL BE CALCULATED AT 7 SQ. FT. PER PERSON | | | NET. NFPA 101, LIFE SAFETY CODE, 7.3.1.2 | | | | | | (2) PROVIDE A TOTAL OCCUPANT LOAD CALCULATION FOR THE | | | ENTIRE SPACE. NFPA 101, LIFE SAFETY CODE, 12.1.7 | | | | | | (3) PROVIDE EXIT DOOR HARDWARE DETAILS INCLUDING | | | LOCKING DEVICES. NFPA 101, LIFE SAFETY CODE, 12.2.2 | | | | | | (4) PROVIDE THE AISLE WIDTH SERVING SEATING AT TABLES. | | | NFPA 101, LIFE SAFETY CODE 12.2.5.8 | | | | | | | | | (5) ANY CHANGES, ADDITIONS, MODIFICATIONS, ETC. TO ANY | | | LIFE SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE ALARM) | | | SHALL BE PERFORMED BY PROPERLY LICENSED CONTRACTORS | | | UNDER SEPARATE PERMITS AND SHOP DRAWINGS. A REVIEW OF | | | LIFE SAFETY FEATURES MAY NEED TO BE CONDUCTED. NFPA | | | 101, LIFE SAFETY CODE, 12.4.1.3.3 | | | | | | (6) PROVIDE DETAILS ON INTERIOR FINISHES. NFPA 101, | | | LIFE SAFETY CODE, 12.3.3 | | | | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-11-03 |
Time |
|
Rev Time |
|
| Received By |
bdolan |
Date |
2022-11-03 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2022-11-03 12:22:27 | THE FOLLOWING COMMENTS WERE SUBMITTED BY CAPT. BRIAN | | | DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH | | | FIRE RESCUE. | | | | | | THE PLAN SET DOES NOT SPECIFY THE TYPE OF EVENTS SPACE | | | IS TO BE USED FOR, PROPOSED OCCUPANT LOAD, LIFE SAFETY | | | FEATURES PRESENT IN THE SPACE, A SITE PLAN FOR THE | | | OVERALL PROJECT AREA, AND ANY CHANGES TO BE MADE TO | | | MEET LIFE SAFETY CODE REQUIREMENTS FOR THE PROPOSED | | | OCCUPANCY TYPE. | | | | | | PLEASE SUBMIT A MORE COMPREHENSIVE PAN SET FOR THE | | | PROPOSED CHANGE OF OCCUPANCY. | | | | | | | | | | | | CAPT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-24 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-22 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-03-22 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-13 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-03-09 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-03-09 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-06 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-02-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-02-22 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-02-10 |
Time |
07:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-25 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-17 |
Time |
17:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-11-08 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-10-27 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-03-26 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-26 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-24 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2023-03-26 08:05:03 | NO IMPACT FEES DUE. LEM | | 2023-03-24 12:26:38 | EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-08 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-08 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2022-11-08 15:14:30 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-24 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-24 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-14 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-14 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2023-03-14 10:05:55 | 5TH REVIEW FMC | | | PERMIT: 22100890 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 1) MAIN ENTRY LOBBIES: 349 SQ FT 349/1000 = .349; .349 | | | X 10 OCCUPANT DENSITY = 3.49, ROUND UP TO 4; 4 X 5 | | | CFM/PERSON = 20 CFMS REQUIRED FOR THE OCCUPANTS; 349 SQ | | | FT X .06 CFM/SQ.FT. = 20.94 CFM FOR THE SPACE; 20 + 21 | | | = 41 CFM REQUIRED FOR THE MAIN ENTRY LOBBY. | | | | | | 2) MULTI-USE ASSEMBLY: 4,976 SQ. FT., 4976/1000 = 4.976 | | | OCCUPANTS ROUND UP; 5 X 100 = 500; 500 X 7.5 = 3750 CFM | | | FOR OCCUPANTS; 4976 X .06 = 298.56 ROUND UP; 3750 + 299 | | | = 4049 CFM REQUIRED FOR MULTI-USE ASSEMBLY. | | | | | | 3) DINING: 400 SQ. FT., 400/ 1000 = .4; .4 X 70 = 28 | | | OCCUPANTS; 28 X 7.5 = 210 CFM REQUIRED FOR THE | | | OCCUPANTS; 400 X .18 = 72 CFM FOR THE SPACE. 210 + 72 = | | | 282 CFM REQUIRED FOR DINING | | | | | | 4) THE TOTAL OUTDOOR AIR REQUIRED FOR THIS CHANGE OF | | | USE IS 4,414 CFMS. | | | | | | 4414/ 3 = 1471 CFM OF O.A. PER UNIT | | | TYPICAL O.D. SUPPLIED FROM A 5-TON UNIT IS 350 CFM: SO, | | | 700 CFMS X 3 10-TON UNIT = 2100 CFM???S OF OUTDOOR AIR. | | | | | | PLEASE SHOW THAT THE EXISTING UNITS WILL BE SIZED TO | | | BRING IN THE REQUIRED OUTDOOR AIR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-07 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-07 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2023-03-07 13:43:00 | 4TH REVIEW FMC | | | PERMIT: 22100890 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) WITH THIS CHANGE OF USE GOING FROM EDUCATIONAL TO AN | | | ASSEMBLY OCCUPANCY THE OUTDOOR AIR CALCULATIONS MUST BE | | | SUBMITTED TO SHOW THAT THE MECHANICAL SYSTEMS CAN | | | HANDLE THE EXTRA LOAD OF MORE PEOPLE BEING ABLE TO | | | OCCUPY THE SAME SPACE. PLEASE SUBMIT THE REQUIRED | | | OUTDOOR AIR CALCULATIONS FOR THIS USE OF SPACE. THE | | | OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES | | | THE USE FROM TABLE 403.3.1.1 MUST BE USED FOR THE | | | CALCULATIONS. THE OCCUPANT DENSITY FOR THIS OCCUPANCY | | | CLASSIFICATION MUST BE USED TO FIND THE MINIMUM | | | REQUIRED OCCUPANTS FOR THIS CALCULATION. FMC 403.3.1.1 | | | AND TABLE 403.3.1.1. | | | | | | 2) THE DESIGNER MUST SHOW THAT THE MECHANICAL SYSTEMS | | | THAT ARE EXISTING ARE SIZED CORRECTLY FOR THIS CHANGE | | | OF USE. FEC C403.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-14 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-14 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2023-02-14 14:17:37 | 3RD REVIEW FMC | | | PERMIT: 22100890 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS CHANGE OF USE DOES REQUIRE THE SPACE TO MEET | | | THE OUTDOOR AIR REQUIREMENTS FOR THIS NEW OCCUPANCY. | | | PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS FOR THIS | | | NEW CHANGE OF USE. THE OUTDOOR AIR CALCULATIONS SHALL | | | BE DESIGNED FROM THE OCCUPANCY CLASSIFICATION AND | | | OCCUPANT DENSITY OF FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-19 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-19 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2023-01-19 11:30:41 | 1ST REVIEW FMC | | | PERMIT: 22100890 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ADDRESS THE PREVIOUS MECHANICAL COMMENTS. | | | | | | 1) PLEASE PROVIDE THE MECHANICAL DESIGN FOR THE CURRENT | | | PERMITTED USE OF THIS TENANT SPACE ALONG WITH A DRAWING | | | SHOWING THE PURPOSED USE. THE DRAWING SUBMITTED DOES | | | NOT SHOW MUCH INFORMATION FOR THE MECHANICAL DESIGN. | | | PROVIDE A COMPLETE OUTDOOR AIR CALCULATION SHOWING EACH | | | USE OF SPACE IN THIS TENANT SPACE. FMC 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | 2) PROVIDE MORE INFORMATION ABOUT THE STAGE ON THE | | | DRAWING. FBC 410.3.7, 410.3.7.2 | | | | | | 3) PROVIDE MORE INFORMATION ABOUT THE KITCHEN AREA ON | | | THE DRAWING. FMC 507 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-08 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-08 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2022-11-08 14:34:22 | 1ST REVIEW FMC | | | PERMIT: 22100890 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE MECHANICAL DESIGN FOR THE CURRENT | | | PERMITTED USE OF THIS TENANT SPACE ALONG WITH A DRAWING | | | SHOWING THE PURPOSED USE. THE DRAWING SUBMITTED DOES | | | NOT SHOW MUCH INFORMATION FOR THE MECHANICAL DESIGN. | | | PROVIDE A COMPLETE OUTDOOR AIR CALCULATION SHOWING EACH | | | USE OF SPACE IN THIS TENANT SPACE. FMC 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | 2) PROVIDE MORE INFORMATION ABOUT THE STAGE ON THE | | | DRAWING. FBC 410.3.7, 410.3.7.2 | | | | | | 3) PROVIDE MORE INFORMATION ABOUT THE KITCHEN AREA ON | | | THE DRAWING. FMC 507 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2023-03-23 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-23 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-23 |
Time |
06:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-14 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-14 |
Time |
06:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-07 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-07 |
Time |
06:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-02-28 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-13 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-13 |
Time |
07:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-01-18 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2023-01-18 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2023-01-18 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2023-01-18 16:47:40 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1 | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 22100890 7719 S DIXIE HWY | | | | | | 2ND REVIEW | | | ELECTRONIC SIGNATURES ARE NOT VALID | | | | | | PLUMBING COMMENTS: DENIED | | | | | | | | | | | | 1. COMPLIED | | | | | | 2. PARTIALLY COMPLIED: BASED ON PLANS FROM PREVIOUS | | | TENANT (SEE CLOSED PERMIT #02060943), IT APPEARS THERE | | | ARE TO BE NO PLUMBING CHANGES FROM THE ORIGINAL | | | OCCUPANCY. PLEASE CLARIFY. PLEASE PROVIDE LOCATION OF | | | EXISTING WATER HEATER. WPB FBC 107.3.5.1.3 | | | | | | 3. PARTIALLY COMPLIED: PER WPB FBC 107.2.1, PLEASE | | | PROVIDE NEW OCCUPANCY DESIGNATION AS SPELLED OUT IN FBC | | | SECTION 302 AND PROVIDE OCCUPANCY LOAD FOR DESIGNATED | | | CLASSIFICATION AS SPELLED OUT IN FBC SECTION 1004 SO | | | THAT A DETERMINATION OF MINIMUM PLUMBING FIXTURE | | | REQUIREMENTS CAN BE DETERMINED IN ACCORDANCE WITH FBC | | | PL SECTION 403; PROVIDE PLUMBING FIXTURE SCHEDULE | | | SHOWING MINIMUM FIXTURE REQUIREMENTS FOR THE OCCUPANCY | | | IN ACCORDANCE WITH FBC PL TABLE 403.1 AND THE ACTUAL | | | FIXTURES PROVIDED. | | | TO BE CLEAR, PLEASE INDICATE BASED ON NEW OCCUPANCY AND | | | FBC PL TABLE 403.1, THE MINIMUM PLUMBING FIXTURE | | | REQUIREMENTS INCLUDING QUANTITIES (INCLUDE POTTY PARITY | | | FBC PL 403.1.3) AND THE ACTUAL FIXTURES (QUANTITY) | | | PROVIDED. FBC EX 1010.1 | | | | | | 4. SECOND REQUEST: A REVIEW OF MINIMUM PLUMBING FIXTURE | | | REQUIREMENTS AS REQUIRED BY FBC ACC IS PART OF THE | | | PLUMBING REVIEW PROCESS (SEE FBC PL 404.1) BUT IS | | | TYPICALLY ADDRESSED ON THE ARCHITECTURAL PLANS. ANY | | | COMMENTS CONCERNING THESE REQUIREMENTS MUST BE | | | SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW | | | APPROVAL; PROVIDE PLAN AND ELEVATION DETAILS FOR | | | ACCESSIBLE TOILET ROOM FACILITIES, DRINKING FOUNTAIN(S) | | | AND ACCESSIBLE SINKS. COMPLY WITH FBC ACC CHAPTERS 2, 3 | | | AND 6. | | | | | | ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A | | | CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH | | | THE PROVISIONS OF THE FLORIDA ACCESSIBILITY CODE 2020 | | | 7TH EDITION PER FBC EX 1006.1 | | | | | | ***A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL | | | OR PARTITION TO THE REAR AND TO ONE SIDE. THE | | | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES | | | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR | | | PARTITION PER FBC ACC 604.2 | | | ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 | | | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM | | | THE REAR WALL PER FBC ACC 604.3.1 | | | ***C) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 | | | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER | | | CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED | | | WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL | | | PER FBC ACC 604.3.1 AND 604.8.1.1. | | | ***E) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE | | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | | WALL PER FBC ACC 604.5.1 | | | ***F) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES | | | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 | | | ***G) FLUSH CONTROLS SHALL BE HAND OPERATED OR | | | AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY | | | WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN | | | SIDE OF THE WATER CLOSET PER FBC ACC 604.6 | | | ***H) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL | | | COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 | | | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED | | | BEHIND GRAB BARS. | | | ***J) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE | | | FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 | | | INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE | | | SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED | | | POSITION PER FBC ACC 604.4. | | | ***K) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED | | | IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE | | | TOP (NOT THE CENTER) OF THE GRIPPING SURFACE. | | | ***L) URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG | | | TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP | | | MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM | | | TO THE BACK OF THE FIXTURE PER FBC ACC 605.2. | | | ***M) LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS | | | REQUIRED BY FBC ACC 306.2 AND 306.3 | | | ***N) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5 | | | PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED | | | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 | | | PER FBC ACC 212.3 | | | ***O) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER | | | SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE | | | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST | | | CONTACT. | | | ***P) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | | REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE | | | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE | | | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE | | | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 | | | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 603.3. | | | TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS | | | TO THE REFLECTING SURFACE OF THE MIRROR. | | | ***Q) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 | | | OR 304.3.2. | | | ***R) DRINKING FOUNTAINS SHALL HAVE A CLEAR FLOOR OR | | | GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A | | | FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE | | | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER FBC | | | ACC 602.2. | | | ***S) SPOUT OUTLETS FOR ACCESSIBLE DRINKING FOUNTAINS | | | SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND PER FBC ACC 602.4. | | | ***T) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING | | | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 | | | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND PER FBC ACC 602.7. | | | | | | | | | 5. N/A | | | | | | | | | END OF COMMENTS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER PX928 | | | PLUMBING INSPECTOR BN2148 | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | MOBILE 561-246-0882 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2022-11-02 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2022-11-02 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2022-11-02 12:02:05 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1 | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 22100890 7719 S DIXIE HWY | | | | | | 1ST REVIEW | | | PLUMBING COMMENTS: DENIED | | | | | | 1. THE FLOOR PLAN WAS NOT DESIGNED BY EITHER AN | | | ENGINEER OR ARCHITECT. CERTIFICATION BY CONTRACTOR. THE | | | CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET OF | | | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF | | | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND | | | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND | | | PLANS DRAWN. WPB FBC 107.3.4.3 CERTIFICATION BY | | | CONTRACTOR. | | | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED | | | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE | | | NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER | | | PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE | | | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO | | | ISSUANCE OF A PERMIT. | | | PER WPB FBC 107.2.1, PLEASE REFERENCE ON THE PLANS THE | | | CODES THAT APPLY (SEE LIST ABOVE) | | | | | | 2. PROVIDE A FULL SCOPE OF WORK AND AS APPLICABLE, AN | | | EXISTING/DEMOLITION PLUMBING FLOOR PLAN WITH ALL | | | EXISTING PLUMBING FIXTURES AND EQUIPMENT INCLUDING | | | WATER HEATERS AND A PROPOSED PLUMBING FLOOR PLAN WITH | | | ALL PLUMBING FIXTURES AND EQUIPMENT INCLUDING WATER | | | HEATERS. PROVIDE AS APPLICABLE, PLUMBING PLAN VIEW TO | | | INCLUDE WATER AND SANITARY PIPING, PLUMBING FIXTURES, | | | NEW OR EXISTING WATER SERVICE BACKFLOW PREVENTER AND | | | EQUIPMENT INCLUDING WATER HEATERS AND PLUMBING | | | WATER/SANITARY RISER DIAGRAMS AND DETAILS. ADDRESS AS | | | APPLICABLE, THE REQUIREMENTS OF WPB FBC 107.3.5.1.3 | | | BELOW. | | | 1. MINIMUM PLUMBING FACILITIES | | | 2. FIXTURE REQUIREMENTS | | | 3. WATER SUPPLY PIPING | | | 4. SANITARY DRAINAGE | | | 5. WATER HEATERS | | | 6. VENTS | | | 7. ROOF DRAINAGE | | | 8. BACKFLOW PREVENTION | | | 9. IRRIGATION | | | 10. LOCATION OF WATER SUPPLY LINE | | | 11. GREASE TRAPS | | | 12. ENVIRONMENTAL REQUIREMENTS | | | 13. PLUMBING RISER (SANITARY AND WATER) | | | 14. DESIGN FLOOD ELEVATION | | | | | | 3. PER WPB FBC 107.2.1, PLEASE PROVIDE NEW OCCUPANCY | | | DESIGNATION AS SPELLED OUT IN FBC SECTION 302 AND | | | PROVIDE OCCUPANCY LOAD FOR DESIGNATED CLASSIFICATION AS | | | SPELLED OUT IN FBC SECTION 1004 SO THAT A DETERMINATION | | | OF MINIMUM PLUMBING FIXTURE REQUIREMENTS CAN BE | | | DETERMINED IN ACCORDANCE WITH FBC PL SECTION 403; | | | PROVIDE PLUMBING FIXTURE SCHEDULE SHOWING MINIMUM | | | FIXTURE REQUIREMENTS FOR THE OCCUPANCY IN ACCORDANCE | | | WITH FBC PL TABLE 403.1 AND THE ACTUAL FIXTURES | | | PROVIDED. | | | | | | 4. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED | | | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING | | | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED | | | PRIOR TO A PLUMBING REVIEW APPROVAL; PROVIDE PLAN AND | | | ELEVATION DETAILS FOR ACCESSIBLE TOILET ROOM | | | FACILITIES, DRINKING FOUNTAIN(S) AND ACCESSIBLE SINKS. | | | COMPLY WITH FBC ACC CHAPTERS 2, 3 AND 6. | | | | | | 5. VALUE OF JOB MAY NEED TO BE ADJUSTED BASED UPON A | | | PROPOSED SCOPE OF WORK AND RESUBMITTALS. PROVIDE AN | | | ACCURATE VALUATION OF ALL WORK AND COST. WPB FBC 109.3 | | | BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE | | | BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, | | | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR | | | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE | | | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE | | | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR | | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL (1) CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | | | | END OF COMMENTS. | | | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT | | | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A | | | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS | | | FROM THE FIRST REVIEW. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER PX928 | | | PLUMBING INSPECTOR BN2148 | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | MOBILE 561-246-0882 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2023-03-23 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-23 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-23 |
Time |
06:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-15 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-15 |
Time |
11:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-08 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-08 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-13 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-13 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2023-02-13 10:20:41 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SIGNED AND SEALED DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-01-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-18 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-18 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2023-01-18 09:16:32 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SIGNED AND SEALED DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-08 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-08 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2022-11-02 12:08:26 | PLUMBING SIGNATURES FAILED; SEE PLUMBING REVIEW-COMMENT | | | #1. JS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
N |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-03-22 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-22 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2023-03-09 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-03-09 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-09 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-02-16 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-02-16 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-01-24 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-01-24 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-01-24 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2023-01-24 11:07:15 | FAILED | | | 1/24/2023 | | | | | | IS ANY WORK BEING DOWN TO THE SPACE? | | | | | | IF THIS IS JUST A CHANGE OF USE THIS PROCESS IS | | | COMPLETE WITH A BTR. | | | | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-04 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-11-04 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-11-04 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2022-11-04 13:48:21 | 11/04/22 FAILED | | | | | | IS ANY WORK BEING PROPOSED UNDER THIS PERMIT? IF THIS | | | IS JUST A SIMPLE CHANGE OF USEAGE/OCCUPANCY THIS IS | | | DONE THROUGH OUR BUSINESS TAX FORMS, NOT OUR BUILDING | | | PERMIT PROCESS. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 |
|
|