Plan Review Details - Permit 22100872
Plan Review Stops For Permit 22100872
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-01-26 Cont ID  
Sent By jwitmer Date 2023-01-26 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2023-01-26 Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-01-03 Cont ID  
Sent By jwitmer Date 2023-01-03 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2023-01-03 Time   Sent To  
Notes
2023-01-03 09:30:12COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 12:09 Rev Time  
Received By jwitmer Date 2022-11-29 Time   Sent To  
Notes
2022-11-29 12:09:40COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-03-28 Cont ID  
Sent By jwitmer Date 2023-03-28 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2023-03-28 Time 12:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-03-20 Cont ID  
Sent By jwitmer Date 2023-03-20 Time 17:43 Rev Time 0.00
Received By jwitmer Date 2023-03-20 Time 17:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-02-21 Cont ID  
Sent By jwitmer Date 2023-02-21 Time 15:33 Rev Time 0.00
Received By jwitmer Date 2023-02-21 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-26 Cont ID  
Sent By jwitmer Date 2023-01-26 Time 10:16 Rev Time 0.00
Received By jwitmer Date 2023-01-26 Time 09:20 Sent To  
Notes
2023-01-26 10:16:22WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22100872
 ADD: 540 NORTHWOOD RD.
 CONT: TEKTONICA INDUSTRIES INC
 TEL: 561-745-2858
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2) 3RD REVIEW
 DATE: THURS. JAN. 26TH/ 2023
 ACTION: DENIED
  
 1) 3RD REVIEW. PLEASE REVIEW THE BACK-EXIT DOOR, A
 INSWING DOOR AND ADJACENT TO THE LATCH SIDE OF THE DOOR
 THE NEW PORTION OF WALL AND EXISTING WALL ARE ONLY 8
 INCHES FROM THE EDGE OF THE DOOR, ACCESS. CODE SECTION
 404.2.4 FIGURE 404.2.4.1(A) REQUIRES 18 INCHES MINIMUM.
 2ND REVIEW COMMENTS. SHEET A.1. THIS REVIEW S NEW ADA
 RESTROOM HAS BEEN DESIGNED AND A NEW STORAGE CLOSET
 NEXT TO THE BACK EXIT. THERE IS NOT ENOUGH MANEUVERING
 CLEARANCE BETWEEN THE NEW STORAGE CLOSET & REAR EXIT.
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
 1ST ROUND OF COMMENTS. THE STATED VALUE OF THE WORK
 COVERED UNDER THIS PERMIT IS $16,000.00 DOLLARS IN
 VALUE. THE LIFE SAFETY SHEET A.2, PLEASE PROVIDE WHERE
 YOU WILL SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTION 202.4.1.
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% ($3,200.00 DOLLARS) OF THE COST OF
 THE ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT
 MAY BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 ENLARGING DOOR OPENINGS, INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COST
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COST ASSOCIATED WITH RELOCATING
 AN ACCESSIBLE DRINKING FOUNTAIN. PLEASE PROVIDE ON THE
 CONTRACTORS LETTERHEAD WHERE AND WHAT AREAS ARE GOING
 TO BE MODIFIED FOR CODE COMPLIANCE LIST ITEMS AND COST
 BREAK DOWN UP TO THE DISPROPORTIONATE COST OF $3,200.00
 DOLLARS.
  
 2) 3RD REVIEW CYCLE. SHEET A.1 SCOPE OF WORK NOTE
 STATES: NO PLUMBING BEYOND CONNECTING NEW SINK TO
 EXISTING STUB OUT, THE RESTROOM SHOWS A TOTAL NEW
 LAYOUT OF THE WATERCLOSET AND LAV AND REMOVAL OF
 SHOWER. NEW UNDERGROUND PLUMBING AND VENTING IS
 REQUIRED
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. REQUIRES PLUMBING ISOMETRIC
 FOR SANITARY & SUPPLY LINES. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 2ND ROUND OF COMMENTS. NEW COMMENT. SHEET A.1 SCOPE OF
 WORK NOTE STATES: NO PLUMBING BEYOND CONNECTING NEW
 SINK TO EXISTING STUB OUT, THE RESTROOM SHOWS A TOTAL
 NEW LAYOUT OF THE WATERCLOSET AND LAV AND REMOVAL OF
 SHOWER. NEW UNDERGROUND PLUMBING AND VENTING IS
 REQUIRED. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 3-4) COMPLIED.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-03 Cont ID  
Sent By jwitmer Date 2023-01-03 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2023-01-03 Time   Sent To  
Notes
2023-01-03 09:27:06WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22100872
 ADD: 540 NORTHWOOD RD.
 CONT: TEKTONICA INDUSTRIES INC
 TEL: 561-745-2858
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2) 2ND REVIEW
 DATE: TUES. JAN. 03RD/ 2023
 ACTION: DENIED
  
 1) 2ND REVIEW. SHEET A.1. THIS REVIEW S NEW ADA
 RESTROOM HAS BEEN DESIGNED AND A NEW STORAGE CLOSET
 NEXT TO THE BACK EXIT. THERE IS NOT ENOUGH MANEUVERING
 CLEARANCE BETWEEN THE NEW STORAGE CLOSET & REAR EXIT.
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
 1ST ROUND OF COMMENTS. THE STATED VALUE OF THE WORK
 COVERED UNDER THIS PERMIT IS $16,000.00 DOLLARS IN
 VALUE. THE LIFE SAFETY SHEET A.2, PLEASE PROVIDE WHERE
 YOU WILL SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTION 202.4.1.
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% ($3,200.00 DOLLARS) OF THE COST OF
 THE ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT
 MAY BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 ENLARGING DOOR OPENINGS, INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COST
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COST ASSOCIATED WITH RELOCATING
 AN ACCESSIBLE DRINKING FOUNTAIN. PLEASE PROVIDE ON THE
 CONTRACTORS LETTERHEAD WHERE AND WHAT AREAS ARE GOING
 TO BE MODIFIED FOR CODE COMPLIANCE LIST ITEMS AND COST
 BREAK DOWN UP TO THE DISPROPORTIONATE COST OF $3,200.00
 DOLLARS.
  
 2) NEW COMMENT. SHEET A.1 SCOPE OF WORK NOTE STATES: NO
 PLUMBING BEYOND CONNECTING NEW SINK TO EXISTING STUB
 OUT, THE RESTROOM SHOWS A TOTAL NEW LAYOUT OF THE
 WATERCLOSET AND LAV AND REMOVAL OF SHOWER. NEW
 UNDERGROUND PLUMBING AND VENTING IS REQUIRED. 2020 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3) NEW COMMENT. SHEET A2 THE LIFE SAFETY SHEET SHOWS
 ELEVATIONS FOR ACCESSIBILITY BUT NOT FOR WALL FINISHES
 IN THE NEW ADA RESTROOM AND COMPLIANCE WITH SECTION
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 3A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 3B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 3C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
  
 3D) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER???S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM (MR BOARD) SHALL NOT BE USED FOR
 SHOWER & TUB ENCLOSURES BUT CAN BE USED FOR BACKING
 BOARD FOR A BASE FOR TILE IN WATER CLOSET COMPARTMENT
 WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840 AND THE MANUFACTURE???S RECOMMENDATIONS.
  
 4) ACCESSIBILITY REQUIREMENTS: SHEET A.1 HAS A LIST OF
 ACCESSIBILITY ACCESSORY SCHEDULE:
  
 4A) BOTH BACK AND SIDEBARS INDICATE TO BE MEASURED FROM
 FLOOR TO CENTERLINE OF GRAB BAR. SHEET A.2 ELEVATION
 VIEW OF RESTROOM SHOW THE GRAB BAR MEASURED CENTERLINE
 TO FINISH FLOOR. 2020 FBC-ACCESSIBILITY CODE SECTION
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 4B) SHEET A.1 THE TOILET PAPER HOLDER STATES THE
 CORRECT DISTANCE FROM THE FRONT OF WATER CLOSET WHEREAS
 SHEET A.2 SHOWS THE TOILET PAPER HOLDER MEASURED FROM
 THE BACK WALL TO THE CENTER LINE OF PAPER HOLDER,
 DISCREPANCY IN PLANS. TOILET PAPER DISPENSERS. 604.7.
 THE TOILET PAPER DISPENSER SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 12:10 Rev Time  
Received By jwitmer Date 2022-11-29 Time   Sent To  
Notes
2022-11-29 12:10:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22100872
 ADD: 540 NORTHWOOD RD.
 CONT: TEKTONICA INDUSTRIES INC
 TEL: 561-745-2858
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 29TH/2022
 ACTION: DENIED
 1) THE STATED VALUE OF THE WORK COVERED UNDER THIS
 PERMIT IS $16,000.00 DOLLARS IN VALUE. THE LIFE SAFETY
 SHEET A.2, PLEASE PROVIDE WHERE YOU WILL SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE SECTION
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% ($3,200.00
 DOLLARS) OF THE COST OF THE ALTERATION TO THE PRIMARY
 FUNCTION AREA. COST THAT MAY BE COUNTED AS EXPENDITURES
 REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY
 INCLUDE: (I) COST ASSOCIATED WITH PROVIDING AN
 ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUT TO THE
 ALTERED AREA; (II) COST ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS ENLARGING DOOR OPENINGS,
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN. PLEASE PROVIDE ON THE CONTRACTORS LETTERHEAD
 WHERE AND WHAT AREAS ARE GOING TO BE MODIFIED FOR CODE
 COMPLIANCE LIST ITEMS AND COST BREAK DOWN UP TO THE
 DISPROPORTIONATE COST OF $3,200.00 DOLLARS.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2023-03-22 Cont ID  
Sent By mpeterso Date 2023-03-22 Time 13:02 Rev Time 0.00
Received By mpeterso Date 2023-03-22 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-03-10 Cont ID  
Sent By mpeterso Date 2023-03-10 Time 15:06 Rev Time 0.00
Received By mpeterso Date 2023-03-10 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-08 Cont ID  
Sent By mpeterso Date 2023-02-08 Time 10:07 Rev Time 0.00
Received By mpeterso Date 2023-02-08 Time 09:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 16:45 Rev Time 0.00
Received By mpeterso Date 2023-01-06 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-01 Cont ID  
Sent By mpeterso Date 2022-12-01 Time 11:48 Rev Time 0.00
Received By mpeterso Date 2022-12-01 Time 11:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2023-03-24 Cont ID  
Sent By pleduc Date 2023-03-24 Time   Rev Time 0.00
Received By pleduc Date 2023-03-24 Time 13:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2023-03-14 Cont ID  
Sent By pleduc Date 2023-03-14 Time   Rev Time 0.00
Received By pleduc Date 2023-03-14 Time 09:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-02-21 Cont ID  
Sent By pleduc Date 2023-02-21 Time   Rev Time 0.00
Received By pleduc Date 2023-02-21 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-01-24 Cont ID  
Sent By pleduc Date 2023-01-24 Time   Rev Time 0.00
Received By pleduc Date 2023-01-24 Time 11:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-28 Cont ID  
Sent By pleduc Date 2022-12-28 Time   Rev Time 0.00
Received By pleduc Date 2022-12-28 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-24 Cont ID  
Sent By pleduc Date 2022-10-24 Time   Rev Time 0.00
Received By pleduc Date 2022-10-24 Time 10:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-03-28 Cont ID  
Sent By jwitmer Date 2023-03-28 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2023-03-23 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-22 Cont ID  
Sent By mpeterso Date 2023-03-22 Time 13:06 Rev Time 0.00
Received By mpeterso Date 2023-03-13 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-10 Cont ID  
Sent By mpeterso Date 2023-03-10 Time 15:08 Rev Time 0.00
Received By mpeterso Date 2023-02-17 Time 15:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-08 Cont ID  
Sent By mpeterso Date 2023-02-08 Time 10:08 Rev Time 0.00
Received By mpeterso Date 2023-01-23 Time 13:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 14:18 Rev Time 0.00
Received By medwards Date 2022-12-27 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-01 Cont ID  
Sent By mpeterso Date 2022-12-01 Time 11:49 Rev Time 0.00
Received By mpeterso Date 2022-10-21 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 08:12 Rev Time 0.00
Received By medwards Date 2023-01-31 Time 08:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 14:18 Rev Time 0.00
Received By medwards Date 2023-01-11 Time 14:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By medwards Date 2022-11-17 Time 16:37 Rev Time 0.00
Received By medwards Date 2022-11-17 Time 16:37 Sent To  
Notes
2022-11-17 16:37:371ST REVIEW FMC
 PERMIT: 22100872
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THE NEW OFFICE AND LAB ROOMS HAVE
 WALLS TO THE CEILING BASED ON THE NEW DUCT FOR THE
 OFFICE AREA. PLEASE SHOW HOW THE LAB WILL BE
 CONDITIONED AND ALSO SHOW THE RETURN AIR PATH BACK TO
 THE AHU FROM EACH ROOM. FMC 601.6
  
 2) THE OUTDOOR AIR CALCULATIONS DO NOT SHOW THE
 OCCUPANCY CLASSIFICATION, THERE SHOULD BE 3 DIFFERENT
 CLASSIFICATIONS: RETAIL SALES, OFFICE AND THE LAB
 SHOULD HAVE AN OCCUPANCY BASED ON THE BEST USE OF SPACE
 IN THE OCCUPANCY CLASSIFICATION COLUMN IN FMC TABLE
 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2023-03-24 Cont ID  
Sent By rwbrown Date 2023-03-24 Time 08:55 Rev Time 0.00
Received By rwbrown Date 2023-03-24 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2023-03-14 Cont ID  
Sent By rwbrown Date 2023-03-14 Time 08:41 Rev Time 0.00
Received By rwbrown Date 2023-03-14 Time 08:41 Sent To  
Notes
2023-03-14 08:45:484TH PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1 - THE NOTE ADDED DETAILING THE
 MODEL NUMBER FOR THE WATER HEATER DOES NOT INDICATE
 THAT THE MIXING VALVE IS PRESENT. I LOOKED UP THE WATER
 HEATER AND THE DETAILS ONLINE DO NOT SHOW THAT THIS
 WATER HEATER HAS EITHER ASSE 1017 OR ASSE 1070
 COMPLIANCE. TO SUPPLY HOT WATER TO ANY FIXTURE, YOU
 MUST HAVE AN ASSE 1017 MIXING DEVICE. AND TO SUPPLY
 TEMPERED WATER TO A PUBLIC HANDWASHING STATION YOU MUST
 HAVE AN ASSE 1070 MIXING DEVICE.
  
 2. 2017 WPB AMENDS 107.2.1 - AFTER DETAILING A
 POINT-OF-USE WATER HEATER, YOU WOULD NEED TO ELEMINATE
 THE WATER HEATER DIAGRAM FOR CONSITENCY.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-02-21 Cont ID  
Sent By rwbrown Date 2023-02-21 Time 09:25 Rev Time 0.00
Received By rwbrown Date 2023-02-21 Time 09:25 Sent To  
Notes
2023-02-21 09:28:102ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 COMMENTS WERE NOT ADDRESSED ON THE 1ST CYCLE.
  
 1. DONE
  
 2. DONE
  
 3. THIS COMMENT NOT ADDRESSED - THE WATER HEATER DETAIL
 AS WILL AS THE WATER RISER DIAGRAM SHOULD DETAIL AN
 THERMOSTATIC MIXING DEVICE. AS NOTED, THIS IS IN
 "ADDITION TO" THE REQUIREMENTS FOR PUBLIC HAND WASHING.
 ALL HOT WATER SHALL GO THROUGH A LIMITING DEVICE AND
 THE THERMOSTAT FOR THE WATER HEATER SHALL NEVER BE THE
 LIMIT FOR HOT OR TEMPERED WATER DELIVERY. THIS DEVICE
 SHALL BE INSTALLED AT THE HOT WATER SOURCE.
 ESSENTIALLY, EVERY COMMERCIAL APPLICATION WILL HAVE A
 THERMOSTATIC MIXING DEVICE INSTALLED AT THE WATER
 HEATER.
 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS
 SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
 4. DONE
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-01-25 Cont ID  
Sent By rwbrown Date 2023-01-25 Time 10:15 Rev Time 0.00
Received By rwbrown Date 2023-01-25 Time 10:15 Sent To  
Notes
2023-01-25 10:15:392ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 COMMENTS WERE NOT ADDRESSED ON THE 1ST CYCLE.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 -- PLEASE SUBMIT THE
 PLUMBING PLAN PAGE. INCLUDE THE MINIMUM REQUIREMENT OF
 A PLUMBING RISER.
  
 2. 2020 FPC 403.1.1 -- SHOW THE OCCUPANCY TYPE AND LOAD
 AND INDICATE COMPLIANCE WITH THE MINIMUM NUMBER OF
 FIXTURES REQUIRED.
  
 3. 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS
 SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
 4. 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND
 SHOW COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR
 PUBLIC HANDWASHING FACILITIES AND TEMPERED WATER. THE
 DEVICE SHOULD CONFORM TO ASSE 1070.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-09 Cont ID  
Sent By rwbrown Date 2023-01-09 Time 08:01 Rev Time 0.00
Received By rwbrown Date 2023-01-09 Time 08:01 Sent To  
Notes
2023-01-09 08:04:091ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 -- PLEASE SUBMIT THE
 PLUMBING PLAN PAGE. INCLUDE THE MINIMUM REQUIREMENT OF
 A PLUMBING RISER.
  
 2. 2020 FPC 403.1.1 -- SHOW THE OCCUPANCY TYPE AND LOAD
 AND INDICATE COMPLIANCE WITH THE MINIMUM NUMBER OF
 FIXTURES REQUIRED.
  
 3. 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS
 SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
 4. 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND
 SHOW COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR
 PUBLIC HANDWASHING FACILITIES AND TEMPERED WATER. THE
 DEVICE SHOULD CONFORM TO ASSE 1070.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-03-28 Cont ID  
Sent By jwitmer Date 2023-03-28 Time 12:34 Rev Time 0.00
Received By jwitmer Date 2023-03-28 Time 12:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-03-22 Cont ID  
Sent By mpeterso Date 2023-03-22 Time 13:06 Rev Time 0.00
Received By mpeterso Date 2023-03-22 Time 13:06 Sent To  
Notes
2023-03-20 17:39:50ARCHITECTURAL SHEET ARE DIGITALLY SIGNED. J WITMER
 3/20/23

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-10 Cont ID  
Sent By mpeterso Date 2023-03-10 Time 15:08 Rev Time 0.00
Received By mpeterso Date 2023-03-10 Time 15:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-02-08 Cont ID  
Sent By mpeterso Date 2023-02-08 Time 10:07 Rev Time 0.00
Received By mpeterso Date 2023-02-08 Time 10:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 16:46 Rev Time 0.00
Received By mpeterso Date 2023-01-06 Time 16:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-17 Cont ID  
Sent By rwbrown Date 2022-11-17 Time 10:36 Rev Time  
Received By rwbrown Date 2022-11-17 Time   Sent To  
Notes
***NONE***