| 2023-02-03 10:31:11 | ELECTRIC REVIEW FAILED |
| | |
| | ELECTRIC REVIEW COMMENTS |
| | |
| | 1) METER IS DESCRIBED AS UTILITY SERVICE WITH UTILITY |
| | DISCONNECT. IS THIS A METER MAIN OR METER WITH SEPARATE |
| | DISCONNECTS FOR EXISTING PANELS A AND B. ORIGINAL HOUSE |
| | PLANS DETAIL A RISER DIAGRAM WITH METER, 2 DISCONNECTS |
| | AND 2, 150-AMP, MLO PANELS? PLEASE PROVIDE AN ACCURATE |
| | ELECTRIC RISER DIAGRAM, ONE DETAILING EXISTING |
| | CONDITIONS AND ONE DETAILING PROPOSED CHANGES. ALSO |
| | PROVIDE LOAD CALCULATIONS FOR THE ENTIRE SERVICE AND |
| | EACH INDIVIDUAL LOAD CENTER, AND, ALL PANEL SCHEDULES. |
| | |
| | 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY |
| | HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS |
| | SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF THE |
| | FEEDERS. SUCH A DIAGRAM SHALL SHOW THE AREA IN SQUARE |
| | FEET OF THE BUILDING OR OTHER STRUCTURE SUPPLIED BY |
| | EACH FEEDER, THE TOTAL CALCULATED LOAD BEFORE APPLYING |
| | DEMAND FACTORS, THE DEMAND FACTORS USED, THE CALCULATED |
| | LOAD AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND |
| | TYPE OF CONDUCTORS TO BE USED. |
| | |
| | 2) EXISTING PANEL B IS DETAILED AS MAIN LUG ONLY AND |
| | MAIN BREAKER. PLEASE REMOVE ANY CONFLICTS IN EQUIPMENT |
| | DESCRIPTION. |
| | |
| | FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL |
| | |
| | 3) A DISCONNECTING MEANS MUST BE PROVIDED FOR PANEL B |
| | AND GROUPED WITH ALL OTHER DISCONNECTING MEANS |
| | |
| | 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE TWO TO |
| | SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE |
| | GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE |
| | THE LOAD SERVED. |
| | |
| | |
| | 4) DO NOT USE INCORRECT NOMENCLATURE IN THIS SUBMITTAL. |
| | IE, THE ELECTRICAL DATA SPECS, LABELS INDICATE TO BE |
| | PLACED AT MAIN SERVICE PANEL. NO EQUIPMENT ON ANY |
| | DIAGRAM INDICATES A MAIN SERVICE PANEL. FBC 107.3 |
| | |
| | 5) THE GARAGE FLOOR PLAN DETAILS 3 LOAD CENTERS |
| | DESCRIBED AS NLC-B, N-LC AND BULC. THE ONE LINE DIAGRAM |
| | DETAILS 2 LOAD CENTERS DESCRIBED AS LOAD CENTER BACKUP |
| | AND EXISTING DISTRIBUTION PANEL A. THE ONE LINE DIAGRAM |
| | DETAILS BOTH OF THESE PANELS ARE LOCATED NEAR HUB. ONCE |
| | AGAIN IT APPEARS THE NOMENCLATURE USED ON BOTH THE |
| | GARAGE FLOOR PLAN AND ONE LINE DIAGRAM DO NOT MATCH. |
| | PLEASE CLEARLY IDENTIFY ALL EQUIPMENT CORRECTLY ON ALL |
| | PLANS. FBC 107.2 |
| | |
| | |
| | 6) PROVIDE A LEGEND ON ALL PLANS IDENTIFYING ALL |
| | ACRONYMS OR SYMBOLS. IE, DOES BULC MEAN BACK UP LOAD |
| | CENTER? FBC 107.2 |
| | |
| | 7) INCLUDE SPECIFIC LABELS ON, THE ELECTRICAL DATA |
| | SPECS/ LABELS SHEET, FOR ALL EQUIPMENT TO COMPLY WITH |
| | NEC 408.4 FIELD IDENTIFICATION REQUIRED. (A) CIRCUIT |
| | DIRECTORY OR CIRCUIT IDENTIFICATION. (B) SOURCE OF |
| | SUPPLY. |
| | |
| | 8) REMOVE NOTE STATING INSTALL CREW IS TO VERIFY WIRE |
| | SIZE TO DISTRIBUTION PANEL B. ALL PLANS REQUIRE WIRE, |
| | EQUIPMENT, OVERCURRENT PROTECTION, ETC, TO BE INCLUDED |
| | IN PLANS SUBMITTED FOR ELECTRICAL PLAN REVIEW.FBC 107.2 |
| | AND NEC 215.5 |
| | |
| | |
| | 9) IT APPEARS MANY OF THE TRIANGLE NOTATIONS ON THE ONE |
| | LINE DIAGRAM ARE INCORRECT. PLEASE PROVIDE CLEAR AND |
| | ACCURATE NOTATIONS ON ALL PLANS. FBC 107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |