Plan Review Details - Permit 22100752
Plan Review Stops For Permit 22100752
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-06-23 Cont ID  
Sent By cpuell Date 2023-06-23 Time 14:28 Rev Time 0.00
Received By cpuell Date 2023-06-23 Time 14:11 Sent To  
Notes
2023-06-23 14:29:54THIS PERMIT IS FOR THE NORTH BUILDING ONLY WITH THE
 ADDRESS OF 1970 N TAMARIND AVE. RECEIVED PRELIMINARY
 LETTER FROM THE COUNTY 74434316100100110
 74434316100100101 AND 74434316100100090 WILL MERGE INTO
 74434316100100090. APPLICANT INFORMED PLANS AND
 APPLICATIONS FORMS NEED TO BE UPDATED WITH THE PRIMARY
 ADDRESS 1970 N TAMARIND AVE.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-04-18 Cont ID  
Sent By cpuell Date 2023-04-18 Time 14:53 Rev Time 0.00
Received By cpuell Date 2023-04-18 Time 14:53 Sent To  
Notes
2023-04-18 14:55:41APPLICATION FORM LISTS 1980 N TAMARIND AVE WITH THE PCN
 74434316100100101, HOWEVER THE SCOPE OF WORK APPEARS TO
 BE FOR THE PARCEL 74434316100100110 (1940 N TAMARIND
 AVE)T. A UNITY OF TITLE WILL NEED TO BE APPLIED FOR AS
 WELL AS THE OWNERS REPRESENTATIVES CONTACTING
 [email protected] OR 561-805-6659 TO ESTABLISH AN
 ADDRESS FOR THE PROJECT THAT MEETS THE CITY'S ROAD
 CENTERLINES AS WELL AS ESTABLISHING ADDRESSES FOR THE
 UNITS AS WELL AS THE RETAIL SPACE. TO START THE UNITY
 OF TITLE PROCEDURE CONTACT VINCE NOEL [email protected] OR
 CALL 561-494-1040. ONCE THE PARCEL COMINATION IS
 APPROVED BY ENGINEERING YOU WILL NEED TO GET THE
 DOCUMENT YOU RECEIVE NOTARIZED FROM THE PALM BEACH
 COUNTYS CLERK OF COURTS. YOU WILL NEED TO GO FILL OUT
 PALM BEACH COUNTYS PARCEL COMBINATION REQUEST FORM
 WHICH CAN BE FOUND AT THIS LINK
 HTTPS://WWW.PBCGOV.ORG/PAPA/DEPARTMENTS/GIS.HTM, THEY
 WILL ISSUE YOU WITH A UNIFIED PARCEL CONTROL NUMBER
 (PCN). WHEN YOU CONTACT THE PROPERTY APPRAISERS YOU
 NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED PCN.
 ONCE YOU HAVE RECEIVED THE PRELIMINARY LETTER PLEASE
 CONTACT DS_ADDRESSING OR CALL 561-805-6659 TO BE ISSUED
 AN ADDRESS.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2023-05-03 Cont ID  
Sent By swelter Date 2023-05-03 Time 13:02 Rev Time 0.00
Received By swelter Date   Time   Sent To  
Notes
2023-05-03 13:04:20IF THE DEVELOPMENT IS AFFORDABLE HOUSING AT 51% THEY
 ARE NOT SUBJECT TO THE PUBLIC ART REQUIREMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-07-27 Cont ID  
Sent By rmcphers Date 2023-07-27 Time 11:42 Rev Time 0.00
Received By rmcphers Date 2023-07-27 Time 11:36 Sent To  
Notes
2023-07-27 11:41:55NEW 2 STORY R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S-4.2 AND S-1.1- NORTH ELEVATION SHOWS A
 WINDOW - THE ARCHITECTURAL DRAWINGS DO NOT SHOW A
 WINDOW - THE DRAWINGS SHOULD MATCH.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-27 Cont ID  
Sent By rmcphers Date 2023-06-27 Time 13:24 Rev Time 0.00
Received By rmcphers Date 2023-06-27 Time 12:58 Sent To  
Notes
2023-06-27 13:18:57NEW 2 STORY R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ACCESSIBLE ROUTE FOR THE RETAIL
 SPACE AT THE FAR SOUTH END FROM THE ACCESSIBLE PARKING
 SPACE TO THE BUILDING ENTRY - FBC A 208.3 PARKING
 SPACES COMPLYING WITH 502 THAT SERVE A PARTICULAR
 BUILDING OR FACILITY SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE COMPLYING
 WITH 206.4. ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE
 ROUTE THAT IS AT LEAST 44 INCHES (1118 MM) WIDE AND SO
 THAT USERS ARE NOT COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE.
 WHERE PARKING SERVES MORE THAN ONE ACCESSIBLE ENTRANCE,
 PARKING SPACES COMPLYING WITH 502 SHALL BE DISPERSED
 AND LOCATED ON THE SHORTEST ACCESSIBLE ROUTE TO THE
 ACCESSIBLE ENTRANCES. IF THERE ARE MULTIPLE ENTRANCES
 FOR MULTIPLE RETAIL STORES THE PARKING SPACES MUST BE
 DISPERSED TO PROVIDE PARKING AT THE NEAREST ACCESSIBLE
 ENTRANCE.
  
 2) PLEASE SHOW THE ACCESSIBLE RAMP SLOPE - FBC A 405.2
  
 3) PLEASE SHOW THE ACCESSIBLE RAMP HAND RAIL DETAILS
 FOR BOTH SIDES OF THE RAMP - FBC A 505.2
  
 4) PLEASE SHOW THE ACCESSIBLE RAMP LANDING SIZES TO
 COMPLY WITH FBC A 405.7.3LENGTH. THE LANDING CLEAR
 LENGTH SHALL BE 60 INCHES (1525 MM) LONG MINIMUM.
 FBC A 405.7.4 CHANGE IN DIRECTION. RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM.
  
 5) CANNOT HAVE A CURB CUT IN A RAMP LANDING - FBC A
 405.7.1SLOPE. LANDINGS SHALL COMPLY WITH 302. CHANGES
 IN LEVEL ARE NOT PERMITTED.
  
 6) DRAWING A-4.2 AND A-6.00 DETAIL 1 SHOWS HANDRAIL
 HEIGHT AT 2' 9" - FBC 1014.2 HEIGHT. HANDRAIL HEIGHT,
 MEASURED ABOVE STAIR TREAD NOSINGS, OR FINISH SURFACE
 OF RAMP SLOPE, SHALL BE UNIFORM, NOT LESS THAN 34
 INCHES (864 MM) AND NOT MORE THAN 38 INCHES (965 MM).
  
 7) PLEASE SHOW THE CLEAR FLOOR SPACE INSIDE THE
 BATHROOMS FOR THE BATHTUBS - FBC FHA REQUIREMENT 7
  
 8) DRAWINGS SP-1, SP-2 AND THE SURVEY DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-20 Cont ID  
Sent By rmcphers Date 2023-04-20 Time 11:47 Rev Time 0.00
Received By rmcphers Date 2023-04-20 Time 08:19 Sent To  
Notes
2023-04-20 11:12:14NEW 2 STORY R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) 2ND FLOOR NORTH END UNIT SHOWS A DOOR OPENING WITH
 OUT A BALCONY - PLEASE CLARIFY
  
 2) DRAWING A-1.0 AND LS-1 UNDER - SCOPE OF WORK - SHOWS
 (2) 3 STORY - THE DRAWINGS SHOW A 2 STORY BUILDING -
 PLEASE CLARIFY
  
 3) DRAWING LS-1 SHOWS CONSTRUCTION TYPE AS IIIA AND
 DRAWING A-1.0 SHOWS CONSTRUCTION TYPE AS IIIB - PLEASE
 CLARIFY.
  
 4) DRAWING S-2.1 AND S-2.2 SHOW A 3 STORY BUILDING -
 ALL OTHER DRAWINGS SHOW A 2 STORY BUILDING - PLEASE
 CLARIFY.
  
 5) DRAWING A-1.0 SHOWS ASCE 7-10 USED FOR THE WIND
 DESIGN - SHOULD BE ASCE 7-16 PER FBC CHAPTER 35
  
 6) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS THAT ARE LISTED ON THE DRAWINGS FOR
 THE EXTERIOR WINDOWS, DOORS AND ROOFING SYSTEMS.
  
 7) PLEASE SHOW THE ACCESSIBLE ROUTE FOR THE RETAIL
 SPACE AT THE FAR SOUTH END - FBC A 208.3 PARKING SPACES
 COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR
 FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE
 ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4.
 ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE ROUTE THAT
 IS AT LEAST 44 INCHES (1118 MM) WIDE AND SO THAT USERS
 ARE NOT COMPELLED TO WALK OR WHEEL BEHIND PARKED
 VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE. WHERE
 PARKING SERVES MORE THAN ONE ACCESSIBLE ENTRANCE,
 PARKING SPACES COMPLYING WITH 502 SHALL BE DISPERSED
 AND LOCATED ON THE SHORTEST ACCESSIBLE ROUTE TO THE
 ACCESSIBLE ENTRANCES. IF THERE ARE MULTIPLE ENTRANCES
 FOR MULTIPLE RETAIL STORES THE PARKING SPACES MUST BE
 DISPERSED TO PROVIDE PARKING AT THE NEAREST ACCESSIBLE
 ENTRANCE.
  
 8) PLEASE SHOW BARRIERS UNDER STAIRS - FBC A 307.4
 VERTICAL CLEARANCE.
 VERTICAL CLEARANCE SHALL BE 80 INCHES (2030 MM) HIGH
 MINIMUM. GUARDRAILS OR OTHER BARRIERS SHALL BE PROVIDED
 WHERE THE VERTICAL CLEARANCE IS LESS THAN 80 INCHES
 (2030 MM) HIGH. THE LEADING EDGE OF SUCH GUARDRAIL OR
 BARRIER SHALL BE LOCATED 27 INCHES (685 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 9) PLEASE PROVIDE A SITE PLAN - CLARIFYING ALL
 ACCESSIBLE PATHWAYS - WIDTHS AND LOCATIONS - FBC A 206
  
 10) PLEASE SHOW THE CLEAR FLOOR SPACE INSIDE THE
 BATHROOMS FOR THE BATHTUBS - FBC FHA REQUIREMENT 7
  
 11) PLEASE SHOW THE GRAB BAR BACKING LOCATIONS FOR THE
 2 BEDROOM UNITS - FBC FHA REQUIREMENT 6
  
 12) FOR THE 2ND FLOOR SOUND TRANSMISSION REQUIREMENT -
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 13) EXTERIOR WINDOW, DOOR AND ROOFING SYSTEM PRODUCT
 APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS
 TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - FBC
 WPB107.3.4.1 DEFERRED SUBMITTALS.

Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-07-05 Cont ID  
Sent By rperdomo Date 2023-07-05 Time 14:14 Rev Time 0.00
Received By rperdomo Date 2023-07-05 Time 14:02 Sent To  
Notes
2023-07-05 14:15:26FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE ONE-LINE DIAGRAM SHOWING INFORMATION OF
 SERVICE EQUIPMENTS AND FEEDERS TO THE DIFFERENT PANELS
 (SERVICE DISCONNECT, FEEDERS PROTECTIONS, GROUNDED
 ELECTRICAL CONDUCTOR, AND MINIMUM SIZE FOR EQUIPMENT
 GROUNDING CONDUCTORS) AS PER NEC 215. 230, 250
  
 END OF COMMENTS
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN P. PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-26 Cont ID  
Sent By rperdomo Date 2023-04-26 Time 16:24 Rev Time 0.00
Received By rperdomo Date 2023-04-26 Time 15:40 Sent To  
Notes
2023-04-26 16:23:59FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW
  
 1. A SEPARATE PERMIT REQUIRED FOR LOW VOLTAGE WIRING.
  
 END OF COMMENTS
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2023-07-14 Cont ID  
Sent By cseifer Date 2023-07-14 Time 07:11 Rev Time 0.00
Received By cseifer Date 2023-07-14 Time 07:11 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-07-03 Cont ID  
Sent By cseifer Date 2023-07-03 Time 11:54 Rev Time 0.00
Received By cseifer Date 2023-07-03 Time 11:53 Sent To  
Notes
2023-07-03 11:54:20PROJECT UNDER FORMAL ENGINEERING REVIEW.
  
 THANKS,
 CHLOE SEIFER, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT, [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-04-21 Cont ID  
Sent By lquinone Date 2023-04-21 Time 15:32 Rev Time 0.00
Received By lquinone Date 2023-04-21 Time 15:32 Sent To  
Notes
2023-04-21 15:33:34PROJECT WAS JUST RECEIVED FOR FORMAL ENGINEERING
 REVIEW.
  
 THANKS,
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-07-26 Cont ID  
Sent By pleduc Date 2023-07-26 Time   Rev Time 0.00
Received By pleduc Date 2023-07-26 Time 11:47 Sent To  
Notes
2023-07-26 11:50:33PROVIDING THE BELOW NOTE TO THE FAILED FIRE COMMENTS
 REGARDING THE F.A.C. OF FIRE SPRINKLER & FIRE ALARM
 DOCUMENTS TO BE SUBMITTED WITH A MASTER PERMIT DOES
 MEET THE REQUIRMENT OF F.A.C.
  
 ANSWER: FIRE ALARM AND FIRE SPRINKLER WILL BE SUBMITTED
 UNDER SEPARATE PERMIT. PLEASE SEE ADDED CRITERIA, NOTES
 IN LS-1
  
 SHOP DRAWING ARE REQUIRED, HOWEVER, THEY ARE TO BE
 DESIGNED UNDER THE EOR REQUIREMENTS PER F.A.C.
  
 FIRE WILL PASS THE PLAN REVIEW IN AN EFFORT TO MOVE
 THIS PROJECT FORWARD.
  
 THE REQUIRED DOCUMENTS SHALL BE SUBMITTED UNDER A
 SEPARATE SUBMITTAL WHEN AVAILABLE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2023-06-28 Cont ID  
Sent By pleduc Date 2023-06-28 Time   Rev Time 0.00
Received By pleduc Date 2023-06-28 Time 13:13 Sent To  
Notes
2023-06-28 13:17:17PROVIDING THE RESPONSE OF "SHOP DRAWINGS WILL BE
 SUBMITTED" OR "DEFERRED" DOES NOT MEET THE REQUIREMENTS
 OF THE FLORIDA ADMINSTRATIVE CODE.
  
 AS STATED PREVIOUSLY:
  
 FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
 EVEN IF THE EOR DEFERS TO A LOCAL QUALIFIED CONTRACTOR,
 THAT CONTRACTOR MUST SUBMIT THE REQUIRED 61G
 INFORMATION WITH THIS MASTER.
  
 PLEASE REVIEW AND SUBMIT THE REQUIRED FAC 61G
 DOCUMENTATION WITH THIS MASTER PERMIT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-04-18 Cont ID  
Sent By pleduc Date 2023-04-18 Time   Rev Time 0.00
Received By pleduc Date 2023-04-18 Time 12:50 Sent To  
Notes
2023-04-18 13:20:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) FIRE SPRINKLER DOCUMENTION -
  
 PER NFPA 1, CH 30
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH
 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 IN ACCORDANCE WITH
 SECTION 9.7, AS MODIFIED BY 30.3.5.4. IN APARTMENT
 BUILDINGS UP TO AND
 INCLUDING FOUR STORIES IN HEIGHT, THAT ARE LOCATED IN
 BUILDINGS NOT EXCEEDING
 60 FT (18.3 M) IN HEIGHT ABOVE GRADE PLANE, SYSTEMS IN
 ACCORDANCE WITH
 NFPA 13R SHALL BE PERMITTED.
  
 THERE IS AN INDICATION OF FIRE SPRINKLER PROTECTION;
 HOWEVER, THERE IS NO INDICATION OF FIRE SPRINKLER
 DOCUMENTATION REQUIRED BY F.A.C 61G
  
 FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
 EVEN IF THE EOR DEFERS TO A LOCAL QUALIFIED CONTRACTOR,
 THAT CONTRACTOR MUST SUBMIT THE REQUIRED 61G
 INFORMATION WITH THIS MASTER.
  
 PLEASE REVIEW AND SUBMIT THE REQUIRED FAC 61G
 DOCUMENTATION WITH THIS MASTER PERMIT.
  
  
  
 2) SHEET 010 C 1 - THERE IS AN INDICATION OF A FDC FOR
 BUILDING A, HOWEVER, THE OTHER BUILDING DOES NOT APPEAR
 TO HAVE ONE.
  
 FOR CLARIFICATION PURPOSES, IS THIS ONE FDC GOING TO
 PROVIDE PROTECTION TO THE OTHER BUILDING?
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF SUCH ON
 THIS SHEET.
  
  
  
 3) SHEET 011 A01 & LS01 - ON THE 2ND FLOOR, THE NORTH
 UNIT, THERE IS AN INDICATION OF DOUBLE DOORS SWINGING
 INTO THE MASTER BEDROOM.
  
 THOSE DOORS APPEAR TO OPEN UP TO THE OPEN AIR.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS OF INTENT.
  
  
  
 4) SHEET 044 E01 - THERE IS NO INDICATION OF A
 MONITORED FIRE SPRINKLER ALARM.
  
 PER NFPA 101 CH 30 AND 9 AND FAC 61G -
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH
 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 IN ACCORDANCE WITH
 SECTION 9.7, AS MODIFIED BY 30.3.5.4. IN APARTMENT
 BUILDINGS UP TO AND
 INCLUDING FOUR STORIES IN HEIGHT, THAT ARE LOCATED IN
 BUILDINGS NOT EXCEEDING
 60 FT (18.3 M) IN HEIGHT ABOVE GRADE PLANE, SYSTEMS IN
 ACCORDANCE WITH
 NFPA 13R SHALL BE PERMITTED.
  
 9.7.2 SUPERVISION
 9.7.2.1* SUPERVISORY SIGNALS
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED
 BY ANOTHER SECTION OF THIS CODE, SUPERVISORY
 ATTACHMENTS SHALL BE
 INSTALLED AND MONITORED FOR INTEGRITY IN ACCORDANCE
 WITH NFPA 72 AND
 A DISTINCTIVE SUPERVISORY SIGNAL SHALL BE PROVIDED TO
 INDICATE A CONDITION
 THAT WOULD IMPAIR THE SATISFACTORY OPERATION OF THE
 SPRINKLER SYSTEM
 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE
 DISPLAYED EITHER AT
 A LOCATION WITHIN THE PROTECTED BUILDING THAT IS
 CONSTANTLY ATTENDED BY QUALI FIED PERSONNEL OR AT AN
 APPROVED, REMOTELY LOCATED RECEIVING FACILITY
 9.7.2.2 ALARM SIGNAL TRANSMISSION.
 9.7.2.2.1 WHERE SUPERVISION OF AUTOMATIC SPRINKLER
 SYSTEMS IS REQUIRED
 BY ANOTHER SECTION OF THIS CODE, WATERFLOW ALARMS SHALL
 BE TRANSMITTED
 TO AN APPROVED, PROPRIETARY ALARM-RECEIVING FACILITY, A
 REMOTE STATION, A
 CENTRAL STATION, OR THE FIRE DEPARTMENT.
 9.7.2.2.2 THE CONNECTION DESCRIBED IN 9.7.2.2.1 SHALL
 BE IN ACCORDANCE
 WITH 9.6.1.3
  
 61G15-32.008 DESIGN OF FIRE ALARMS AND DETECTION
 SYSTEMS.
 (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE
 PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS,
 ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE
 SIGNALING OF EMERGENCY CONDITIONS.
 (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE
 FLORIDA BUILDING CODE (2007), THE FLORIDA FIRE
 PREVENTION CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY
 HAVING JURISDICTION.
 (3) FOR FIRE ALARM PLANS ON SMALL SYSTEMS BELOW THE
 THRESHOLD REQUIREMENTS FOR MANDATORY USE OF
 PROFESSIONAL ENGINEERING SERVICES, THE ENGINEER OF
 RECORD SHALL SPECIFY THE MINIMUM SYSTEM REQUIREMENTS.
 (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND
 DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS
 SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION
 WHEN APPLICABLE:
 (A) THE PLANS SHALL BE CLEAR, WITH A SYMBOLS LEGEND,
 SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND
 NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS.
 INDICATE LOCATIONS WHERE FIRE RATINGS ARE REQUIRED AS
 DETERMINED BY THE SYSTEM???S SURVIVABILITY
 REQUIREMENTS. IDENTIFY THE GENERAL OCCUPANCY OF THE
 PROTECTED PROPERTY, AND FOR EACH ROOM AND AREA UNLESS
 IT IS CLEAR FROM FEATURES SHOWN.
 (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND
 CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND
 SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS
 INCLUDE ELEVATOR CONTROLS SMOKE CONTROL SYSTEMS,
 DAMPERS, AND DOORS.
 (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL
 NOTIFICATION DEVICES.
 (D) IDENTIFY THE CLASS AND STYLE OF CIRCUITS AS LISTED
 IN THE NFPA 72.
 (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND
 CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY
 SIGNALS BEING MONITORED OR ANNUNCIATED.
 (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR
 ADDRESSABLE, AND INDICATE ALL ZONING.
 (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED
 PROTECTIVE FEATURES.
 (H) LOCATE SYSTEM DEVICES THAT ARE SUBJECT TO
 ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR
 THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY
 OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR.
 (I) THE PLANS SHALL INCLUDE A SITE PLAN OF THE
 IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE
 OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE
 THE STRUCTURE.
 (J) IN BUILDINGS WERE SMOKE DETECTION WILL BE
 OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE
 ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND
 DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE
 OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A
 PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH
 AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE
 ENGINEERING DESIGN DOCUMENTS.
 (K) FIRE DETECTION SYSTEMS UTILIZING SMOKE DETECTION IN
 SITUATIONS WHERE SMOKE STRATIFICATION IS ANTICIPATED,
 THE DESIGN SHALL PROVIDE THE NECESSARY CRITERIA TO
 MITIGATE THE DETECTION PROBLEMS.
 (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA
 SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR
 STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING
 JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE
 FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING
 CODE (2007).
 (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO
 PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED
 EVACUATION FOR ALL HIGH-RISE BUILDINGS OR
 MULTI-TENANTED PROPERTIES AS DEFINED IN THE FLORIDA
 BUILDING CODE (2007).
 (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS,
 CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND
 BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE
 PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND
 INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED
 TO OPERATE THE SYSTEMS AS INTENDED OVER TIME.
 (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO
 SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED
 WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS)
 CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL
 BE COMPLETED USING THE EQUIPMENT MANUFACTURE???S DATA
 AND APPLICABLE NFPA 72 PROCEDURES.
 (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (7) WHEN THE ENGINEER DETERMINES THAT SPECIAL
 REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE
 UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE
 REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 RULEMAKING AUTHORITY 471.008, 471.033(2) FS. LAW
 IMPLEMENTED 471.033 FS. HISTORY???NEW 5-19-93, FORMERLY
 21H-32.008, AMENDED 3-26-09.
  
 PLEASE REVIEW AND CORRECT, PROVIDE FAC 61 G
 DOCUMENTATION
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-25 Time 13:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-14 Cont ID  
Sent By cmontell Date 2023-07-14 Time 13:49 Rev Time 0.00
Received By cmontell Date 2023-07-14 Time 13:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-04 Cont ID  
Sent By aoliver Date 2023-05-04 Time 07:48 Rev Time 0.00
Received By aoliver Date 2023-04-14 Time 08:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-13 Time 15:48 Sent To  
Notes
2023-07-13 15:48:287/13/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-04-20 Cont ID  
Sent By rmcphers Date 2023-04-20 Time 11:45 Rev Time 0.00
Received By rmcphers Date 2023-04-20 Time 11:45 Sent To  
Notes
2023-04-20 11:46:27PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-07-14 Cont ID  
Sent By cmontell Date 2023-07-14 Time 13:48 Rev Time 0.00
Received By cmontell Date 2023-07-14 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 08:29 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 08:29 Sent To  
Notes
2023-05-02 08:29:531ST REVIEW FMC
 PERMIT: 221007521)1)
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MANUAL JS SUBMITTED FOR WHAT I BELIEVE TO BE
 UNIT A-2 WILL NEED TO INCLUDE THE NAME AND THE ADDRESS
 OF THE UNIT IT IS SUBMITTED FOR.
  
 2) THE PERMIT APPLICATION WILL NEED TO IDENTIFY WHICH
 BUILDING IS INCLUDED FOR THIS PERMIT.
  
 3) SHEET M-1: THE EXHAUST DUCT TERMINATIONS MUST MEET
 THE 3 FEET REQUIREMENTS FROM OPERABLE OPENINGS. FMC
 501.3.1
  
 4) SHEET M-1: UNIT B1; THE EXHAUST TERMINATION LOCATION
 CAN NOT BE ON TO THE STAIRWAY. FMC 501.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-26 Cont ID  
Sent By ccole Date 2023-07-26 Time 11:04 Rev Time 0.00
Received By ccole Date 2023-07-26 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-06-27 Cont ID  
Sent By ccole Date 2023-06-27 Time 17:03 Rev Time 0.00
Received By ccole Date 2023-06-27 Time 15:33 Sent To  
Notes
2023-06-27 17:04:34 
 2ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22100752
 6/27/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A10.0 DETAIL 3: THE REQUIRED 30X48-INCH CLEAR FLOOR
 SPACE DIAGRAM FOR THE BATHTUB SHOWING A PERPENDICULAR
 APPROACH IN THE TYPE A BATHROOM IS NOT SHOWN. THIS
 REQUIRED CLEAR FLOOR SPACE ALSO SERVES AS THE
 MANEUVERABLE CLEARANCE BEYOND THE ARC OF THE INSWINGING
 DOOR- REFER TO EXAMPLE A BATHROOM ON PAGE 7.36 OF THE
 FHDA MANUAL.
  
 2) A10.0: PLEASE REMOVE THE ROOM DIMENSIONS FROM THE
 GENERIC FHDA FLOOR PLANS TO AVOID CONFLICT WITH THE
 DIMENSIONS SHOWN ON THE SITE SPECIFIC FLOOR PLANS- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-24 Cont ID  
Sent By ccole Date 2023-04-24 Time 07:43 Rev Time 0.00
Received By ccole Date 2023-04-21 Time 17:26 Sent To  
Notes
2023-04-24 07:44:171ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23010249
 4/24/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING
 ITEMS SHOWN ON THE PLANS:
 * POTABLE WATER SERVICE BACKFLOW PREVENTER.
 * FIRE LINE BACKFLOW PREVENTER.
 * IRRIGATION SYSTEM
 * IRRIGATION BACKFLOW PREVENTER
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
  
 2) SHEET A-1.0: PLEASE REFER TO SEC. 233 FBC
 ACCESSIBILITY. BASED ON SECS. 233.3.1 & 233.3.1.1 A
 MINIMUM OF ONE OF THE FIVE DWELLING UNITS SHALL BE
 DESIGNED WITH COMMUNICATION AND MOBILITY FEATURES IN
 COMPLIANCE WITH SECS. 809.2 & 809.4.
 PLEASE NOTE THE EXCEPTION UNDER 233.3.1 WHICH COULD BE
 APPLICABLE TO THE ENTIRE NEIGHBORHOOD RENAISSANCE
 PROJECT AS A WHOLE:
  
 EXCEPTION: WHERE FACILITIES CONTAIN 15 OR FEWER
 RESIDENTIAL DWELLING UNITS, THE REQUIREMENTS OF
 233.3.1.1 AND 233.3.1.2 SHALL APPLY TO THE TOTAL NUMBER
 OF RESIDENTIAL DWELLING UNITS THAT ARE CONSTRUCTED
 UNDER A SINGLE CONTRACT, OR ARE DEVELOPED AS A WHOLE,
 WHETHER OR NOT LOCATED ON A COMMON SITE.
  
 CONCERNING THE PLUMBING REVIEW, THE BATHROOM IN THE
 UNIT THAT MUST MEET COMPLIANCE SHALL BE DESIGNED IN
 ACCORDANCE WITH 809.4. SEC. 809.4 REFERS THE DESIGNER
 TO SECS. 603-610 FOR TOILET AND BATHING FIXTURE
 INSTALLATIONS. SEC. 809.2 REQUIRES THE SELECTED UNIT TO
 BE ON AN ACCESSIBLE ROUTE THEREFORE THE PLANS INDICATE
 THE UNIT MEETING COMPLIANCE SHALL BE ON THE GROUND
 FLOOR. PLEASE PROVIDE AN ENLARGED DRAWING OF THE
 SELECTED UNIT INDICATING COMPLIANCE WITH THE FOLLOWING
 LIST OF FBC ACC COMPLIANCES:
  
 A) SEC. 603.2.1: PROVIDE A TURNING SPACE IN THE
 BATHROOM COMPLYING WITH SEC. 304.
  
 B) SEC. 603.3 SHOW THE HEIGHT OF THE MIRROR AT THE
 LAVATORY TO BE INSTALLED WITH THE REFLECTIVE SURFACE 40
 INCHES MAXIMUM FOR THE FINISHED FLOOR.
  
 C) SEC. 604.3: CLEARANCE AROUND THE WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURE PERPENDICULAR
 FOR THE REAR WALL. PROVIDE A 60 IN. WIDE X 56 IN. CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE WATER
 CLOSETS. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
 LOCATED WITHIN THE REQUIRED CLEARANCE, HOWEVER THERE IS
 AN EXCEPTION WHICH ALLOWS A LAVATORY ON THE REAR WALL
 18 INCHES MINIMUM FROM THE WATER CLOSET CENTERLINE
 WHERE THE CLEARANCE AT THE WATER CLOSET IS 66 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 D) SEC. 606.2: A 30 INCHES X 48 INCHES CLEAR FLOOR
 SPACE POSITIONED FOR A FORWARD APPROACH IS REQUIRED FOR
 THE LAVATORY. KNEE AND TOE CLEARANCES ARE REQUIRED
 HOWEVER PLEASE NOTE EXCEPTION 3 A, B, & C WHICH ALLOWS
 FOR REMOVABLE CABINETRY AT THE LAVATORY.
  
 E) SEC. 604.2: SHOW THE CENTERLINE OF THE WATER CLOSET
 TO BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE
 SIDE WALL.
  
 F) SEC. 604.4 EXCEPTION 2: SHOW THE HEIGHT OF THE WATER
 CLOSET 15 INCHES MINIMUM AND INCHES MAXIMUM FROM THE
 FINISHED FLOOR.
  
 G) SEC. 604.5 EXCEPTION 2: SHOW LOCATIONS, LENGTHS, AND
 MOUNTING HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS-
 SECS. 604.5 & 609.4, FIGURES 604.5.1 & 604.5.2, OR
 PROVIDE REINFORCEMENT LOCATIONS FOR FUTURE
 INSTALLATIONS PER EXCEPTION 2.
  
 H) SEC. 604.7: SHOW THE CENTERLINE OF THE TOILET PAPER
 DISPENSER TO BE LOCATED 7 INCHES MINIMUM TO 9 INCHES
 MAXIMUM FROM THE FRONT OF THE WATER CLOSET TO THE
 CENTERLINE OF THE DISPENSER.
  
 I) SEC. 606.3: SHOW THE HEIGHT OF THE LAVATORY SINK RIM
 OR COUNTER SURFACE TO BE MAXIMUM 34 INCHES FROM THE
 FINISHED FLOOR UNLESS MEETING EXCEPTION 2 WHICH ALLOWS
 THE HEIGHT TO BE 29-36 INCHES WHERE THE PLUMBING ROUGH
 IN LOCATIONS ALLOW FOR A SINK AT A HEIGHT OF 29 INCHES.
  
 J) SEC. 607.2: SHOW THE CLEAR FLOOR SPACE FOR THE
 BATHTUB TO EXTEND THE LENGTH OF THE BATHTUB AND 30
 INCHES WIDE MINIMUM. A LAVATORY COMPLYING WITH SEC. 606
 IS PERMITTED AT THE CONTROL END OF THE CLEARANCE.
  
 K) SEC. 607.3: SHOW EITHER A PERMANENT SEAT AT THE HEAD
 OF THE TUB OR A REMOVABLE SEAT SHALL BE PROVIDED.
 PLEASE SEE SECS. 607.4.1- 607.4.2.3.
  
 L) SEC. 607.4: SHOW GRAB LOCATIONS IN COMPLIANCE WITH
 SEC. 607.4.1- 607.4.1.2 UNLESS INSTALLING
 REINFORCEMENTS IN ACCORDANCE WITH EXCEPTION 2.
  
 M) SEC. 607.5: SHOW THE BATHTUB CONTROLS LOCATION.
  
 3) SHEET A-10.1: PLEASE SHOW THE CLEAR FLOOR DIAGRAMS
 FOR THE BATHTUBS AS SHOWN ON PAGE 7.53 FHDA MANUAL.
  
 4) A-10.1: REFER TO PAGES 6.3- 6.9 OF THE FHDA MANUAL
 AND SHOW THE MINIMUM HEIGHT OF THE WATER CLOSET AND
 BATHTUB REINFORCEMENTS WILL BE 38-INCHES MINIMUM FROM
 THE FINISHED FLOORS.
  
 5) P-1: BASED ON TABLE 403.1 PLUMBING FIXTURES WILL BE
 REQUIRED IN THE SEPARATE RETAIL TENANT SPACE SHOWN ON
 THE FLOOR PLANS. PLEASE REVISE THE DRAWINGS TO SHOW THE
 LOCATION OF THE UNDERGROUND BUILDING DRAIN IN THE
 SPACE, THE DRAIN RUN TO POINT OF CONNECTION TO THE
 SEWER, EXTERIOR AND INTERIOR CLEANOUT LOCATIONS, AND
 INTERIOR CAP FOR FUTURE ACCESS- SEC. 107.2.1 WPB.
  
 6) P-1 & P-3: THE PLANS DO NOT SHOW THE WATER HEATER
 DRAIN PAN LINE RUNS AND DISCHARGE LOCATIONS. PLEASE
 PROVIDE DETAILS IN COMPLIANCE WITH SECS. 504.7.1 &
 504.7.2 FBC P.
  
 7) P-3: PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 WATER HEATERS SHOWING THE MAKES AND MODELS, GALLON
 SIZES, AND EFFICIENCY RATINGS TO MATCH WITH THE DATA
 LISTED ON THE SUBMITTED ENERGY COMPLIANCE FORMS- TABLE
 C404.2 FBC EC. THE WATER HEATERS SPECIFICATIONS CAN BE
 DEFERRED SUBMITTALS IF PREFERRED- SEE SEC. 107.3.4.1
 WPB.
  
 8) P-2: PLEASE PROVIDE A STORM DRAIN ISOMETRIC DRAWING
 SHOWING THE VERTICAL AND HORIZONTAL PIPING RUNS AND
 SIZES FROM THE ROOF DRAINS TO DISCHARGE LOCATIONS- SEC.
 107.3.5.1.3 (7) WPB, AND SECS. 1101.2, 1106.2 & 1106.3
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2023-06-27 Cont ID  
Sent By rmcphers Date 2023-06-27 Time 13:19 Rev Time 0.00
Received By rmcphers Date 2023-06-27 Time 13:19 Sent To  
Notes
2023-06-27 13:19:38ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-04-20 Cont ID  
Sent By rmcphers Date 2023-04-20 Time 11:46 Rev Time 0.00
Received By rmcphers Date 2023-04-20 Time 11:46 Sent To  
Notes
2023-04-20 11:46:55SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-26 Cont ID  
Sent By ccole Date 2023-07-26 Time 11:04 Rev Time 0.00
Received By ccole Date 2023-07-26 Time 10:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-06-27 Cont ID  
Sent By rmcphers Date 2023-06-27 Time 14:08 Rev Time 0.00
Received By rmcphers Date 2023-06-27 Time 14:08 Sent To  
Notes
2023-06-27 14:13:54SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP-1, SP-2 AND THE SURVEY DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-20 Cont ID  
Sent By rmcphers Date 2023-04-20 Time 12:47 Rev Time 0.00
Received By rmcphers Date 2023-04-20 Time 12:47 Sent To  
Notes
2023-04-20 12:49:31SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE PROVIDED SURVEY DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-07-11 Cont ID  
Sent By vbroglia Date 2023-07-11 Time 14:13 Rev Time 0.00
Received By vbroglia Date 2023-07-11 Time 14:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-05-11 Cont ID  
Sent By vbroglia Date 2023-04-25 Time 10:17 Rev Time 0.00
Received By vbroglia Date 2023-04-25 Time 10:17 Sent To  
Notes
2023-04-25 10:25:03 
 SEPERATE PERMIT REQUIED FOR:
  
 FENCE/WALL, AWNINGS, SIGNS, PARKING LOT, GENERATOR,
 MECHANICAL/AC/POOL EQUIPMENT, DUMPSTER ENCLOSURE,
 IRRIGATION, LANDSCAPE, OTHER.
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  