| 2023-04-18 13:20:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) FIRE SPRINKLER DOCUMENTION - |
| | |
| | PER NFPA 1, CH 30 |
| | |
| | 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH |
| | 30.3.5.2. |
| | 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | INSTALLED, EITHER FOR |
| | TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| | IN ACCORDANCE WITH |
| | SECTION 9.7, AS MODIFIED BY 30.3.5.4. IN APARTMENT |
| | BUILDINGS UP TO AND |
| | INCLUDING FOUR STORIES IN HEIGHT, THAT ARE LOCATED IN |
| | BUILDINGS NOT EXCEEDING |
| | 60 FT (18.3 M) IN HEIGHT ABOVE GRADE PLANE, SYSTEMS IN |
| | ACCORDANCE WITH |
| | NFPA 13R SHALL BE PERMITTED. |
| | |
| | THERE IS AN INDICATION OF FIRE SPRINKLER PROTECTION; |
| | HOWEVER, THERE IS NO INDICATION OF FIRE SPRINKLER |
| | DOCUMENTATION REQUIRED BY F.A.C 61G |
| | |
| | FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION |
| | SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE |
| | COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING |
| | DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM |
| | INFORMATION TO BE PROVIDED ON FIRE PROTECTION |
| | ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS |
| | STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP |
| | THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA |
| | PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS |
| | BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER |
| | SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING |
| | DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING |
| | PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED |
| | FOR THE FIRE SPRINKLER INSTALLATION PERMIT. |
| | |
| | EVEN IF THE EOR DEFERS TO A LOCAL QUALIFIED CONTRACTOR, |
| | THAT CONTRACTOR MUST SUBMIT THE REQUIRED 61G |
| | INFORMATION WITH THIS MASTER. |
| | |
| | PLEASE REVIEW AND SUBMIT THE REQUIRED FAC 61G |
| | DOCUMENTATION WITH THIS MASTER PERMIT. |
| | |
| | |
| | |
| | 2) SHEET 010 C 1 - THERE IS AN INDICATION OF A FDC FOR |
| | BUILDING A, HOWEVER, THE OTHER BUILDING DOES NOT APPEAR |
| | TO HAVE ONE. |
| | |
| | FOR CLARIFICATION PURPOSES, IS THIS ONE FDC GOING TO |
| | PROVIDE PROTECTION TO THE OTHER BUILDING? |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF SUCH ON |
| | THIS SHEET. |
| | |
| | |
| | |
| | 3) SHEET 011 A01 & LS01 - ON THE 2ND FLOOR, THE NORTH |
| | UNIT, THERE IS AN INDICATION OF DOUBLE DOORS SWINGING |
| | INTO THE MASTER BEDROOM. |
| | |
| | THOSE DOORS APPEAR TO OPEN UP TO THE OPEN AIR. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS OF INTENT. |
| | |
| | |
| | |
| | 4) SHEET 044 E01 - THERE IS NO INDICATION OF A |
| | MONITORED FIRE SPRINKLER ALARM. |
| | |
| | PER NFPA 101 CH 30 AND 9 AND FAC 61G - |
| | |
| | 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH |
| | 30.3.5.2. |
| | 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | INSTALLED, EITHER FOR |
| | TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| | IN ACCORDANCE WITH |
| | SECTION 9.7, AS MODIFIED BY 30.3.5.4. IN APARTMENT |
| | BUILDINGS UP TO AND |
| | INCLUDING FOUR STORIES IN HEIGHT, THAT ARE LOCATED IN |
| | BUILDINGS NOT EXCEEDING |
| | 60 FT (18.3 M) IN HEIGHT ABOVE GRADE PLANE, SYSTEMS IN |
| | ACCORDANCE WITH |
| | NFPA 13R SHALL BE PERMITTED. |
| | |
| | 9.7.2 SUPERVISION |
| | 9.7.2.1* SUPERVISORY SIGNALS |
| | 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS |
| | ARE REQUIRED |
| | BY ANOTHER SECTION OF THIS CODE, SUPERVISORY |
| | ATTACHMENTS SHALL BE |
| | INSTALLED AND MONITORED FOR INTEGRITY IN ACCORDANCE |
| | WITH NFPA 72 AND |
| | A DISTINCTIVE SUPERVISORY SIGNAL SHALL BE PROVIDED TO |
| | INDICATE A CONDITION |
| | THAT WOULD IMPAIR THE SATISFACTORY OPERATION OF THE |
| | SPRINKLER SYSTEM |
| | 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE |
| | DISPLAYED EITHER AT |
| | A LOCATION WITHIN THE PROTECTED BUILDING THAT IS |
| | CONSTANTLY ATTENDED BY QUALI FIED PERSONNEL OR AT AN |
| | APPROVED, REMOTELY LOCATED RECEIVING FACILITY |
| | 9.7.2.2 ALARM SIGNAL TRANSMISSION. |
| | 9.7.2.2.1 WHERE SUPERVISION OF AUTOMATIC SPRINKLER |
| | SYSTEMS IS REQUIRED |
| | BY ANOTHER SECTION OF THIS CODE, WATERFLOW ALARMS SHALL |
| | BE TRANSMITTED |
| | TO AN APPROVED, PROPRIETARY ALARM-RECEIVING FACILITY, A |
| | REMOTE STATION, A |
| | CENTRAL STATION, OR THE FIRE DEPARTMENT. |
| | 9.7.2.2.2 THE CONNECTION DESCRIBED IN 9.7.2.2.1 SHALL |
| | BE IN ACCORDANCE |
| | WITH 9.6.1.3 |
| | |
| | 61G15-32.008 DESIGN OF FIRE ALARMS AND DETECTION |
| | SYSTEMS. |
| | (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE |
| | PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS, |
| | ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE |
| | SIGNALING OF EMERGENCY CONDITIONS. |
| | (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE |
| | FLORIDA BUILDING CODE (2007), THE FLORIDA FIRE |
| | PREVENTION CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY |
| | HAVING JURISDICTION. |
| | (3) FOR FIRE ALARM PLANS ON SMALL SYSTEMS BELOW THE |
| | THRESHOLD REQUIREMENTS FOR MANDATORY USE OF |
| | PROFESSIONAL ENGINEERING SERVICES, THE ENGINEER OF |
| | RECORD SHALL SPECIFY THE MINIMUM SYSTEM REQUIREMENTS. |
| | (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND |
| | DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS |
| | SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION |
| | WHEN APPLICABLE: |
| | (A) THE PLANS SHALL BE CLEAR, WITH A SYMBOLS LEGEND, |
| | SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND |
| | NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS. |
| | INDICATE LOCATIONS WHERE FIRE RATINGS ARE REQUIRED AS |
| | DETERMINED BY THE SYSTEM???S SURVIVABILITY |
| | REQUIREMENTS. IDENTIFY THE GENERAL OCCUPANCY OF THE |
| | PROTECTED PROPERTY, AND FOR EACH ROOM AND AREA UNLESS |
| | IT IS CLEAR FROM FEATURES SHOWN. |
| | (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND |
| | CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND |
| | SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS |
| | INCLUDE ELEVATOR CONTROLS SMOKE CONTROL SYSTEMS, |
| | DAMPERS, AND DOORS. |
| | (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL |
| | NOTIFICATION DEVICES. |
| | (D) IDENTIFY THE CLASS AND STYLE OF CIRCUITS AS LISTED |
| | IN THE NFPA 72. |
| | (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND |
| | CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY |
| | SIGNALS BEING MONITORED OR ANNUNCIATED. |
| | (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR |
| | ADDRESSABLE, AND INDICATE ALL ZONING. |
| | (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED |
| | PROTECTIVE FEATURES. |
| | (H) LOCATE SYSTEM DEVICES THAT ARE SUBJECT TO |
| | ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR |
| | THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY |
| | OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR. |
| | (I) THE PLANS SHALL INCLUDE A SITE PLAN OF THE |
| | IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE |
| | OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE |
| | THE STRUCTURE. |
| | (J) IN BUILDINGS WERE SMOKE DETECTION WILL BE |
| | OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE |
| | ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND |
| | DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE |
| | OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A |
| | PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH |
| | AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (K) FIRE DETECTION SYSTEMS UTILIZING SMOKE DETECTION IN |
| | SITUATIONS WHERE SMOKE STRATIFICATION IS ANTICIPATED, |
| | THE DESIGN SHALL PROVIDE THE NECESSARY CRITERIA TO |
| | MITIGATE THE DETECTION PROBLEMS. |
| | (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA |
| | SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR |
| | STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING |
| | JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE |
| | FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING |
| | CODE (2007). |
| | (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO |
| | PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED |
| | EVACUATION FOR ALL HIGH-RISE BUILDINGS OR |
| | MULTI-TENANTED PROPERTIES AS DEFINED IN THE FLORIDA |
| | BUILDING CODE (2007). |
| | (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS, |
| | CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND |
| | BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE |
| | PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND |
| | INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED |
| | TO OPERATE THE SYSTEMS AS INTENDED OVER TIME. |
| | (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO |
| | SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED |
| | WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS) |
| | CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL |
| | BE COMPLETED USING THE EQUIPMENT MANUFACTURE???S DATA |
| | AND APPLICABLE NFPA 72 PROCEDURES. |
| | (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (7) WHEN THE ENGINEER DETERMINES THAT SPECIAL |
| | REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE |
| | UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE |
| | REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | RULEMAKING AUTHORITY 471.008, 471.033(2) FS. LAW |
| | IMPLEMENTED 471.033 FS. HISTORY???NEW 5-19-93, FORMERLY |
| | 21H-32.008, AMENDED 3-26-09. |
| | |
| | PLEASE REVIEW AND CORRECT, PROVIDE FAC 61 G |
| | DOCUMENTATION |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |