Plan Review Details - Permit 22100751
Plan Review Stops For Permit 22100751
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2023-06-15 Cont ID  
Sent By cpuell Date 2023-06-15 Time 09:17 Rev Time 0.00
Received By cpuell Date 2023-06-15 Time 09:17 Sent To  
Notes
2023-06-15 09:24:43THE PROJECT WILL BE MOVING FORWARD UNDER THE PCN OF
 74434316060000010 PER THE PRELIMINARY LETTER FROM PAPA,
 THE PRIMARY ADDRESS WILL BE 1959 N TAMARIND AVE, THE
 FOLLOWING ADDRESSES HAVE ALSO BEEN ASSIGNED TO THE
 PROJECT: 1983, 1977, 1969 AND 1963 N TAMARIND AVE, THE
 FOLLOWING SUITES ADDRESSES HAVE ALSO BEEN CREATED: 1959
 N TAMARIND AVE 201, 202. 203, 204, 301, 302, 303 AND
 304. THE PERMIT DOCUMENTS NEED TO REFLECT THE NEW
 ADDRESS.

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2023-06-14 Cont ID  
Sent By cpuell Date 2023-06-14 Time 14:23 Rev Time 0.00
Received By cpuell Date 2023-06-14 Time 14:23 Sent To  
Notes
2023-06-14 14:46:36ESTABLISHED THE PRIMARY AND GROUND FLOOR ADDRESSES,
 SENT BACK PROPOSED 2 AND 3RD FLOOR.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-06-14 Cont ID  
Sent By cpuell Date 2023-06-14 Time 12:12 Rev Time 0.00
Received By cpuell Date 2023-06-14 Time 12:12 Sent To  
Notes
2023-06-14 12:14:11PARCELS HAVE BEEN UNIFIED UNDER PCN 74434316060000010
 NOW THAT THE PRELIMINARY LETTER HAS BEEN RECIEVED
 PLEASE CONTACT [email protected] OR CALL
 561-805-6659 SO THAT WE CAN ESTABLISH ADDRESS FOR THE
 UNITS AND THE DIFFERENT BUILDINGS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-12-16 Cont ID  
Sent By cpuell Date 2022-12-16 Time 10:48 Rev Time 0.00
Received By cpuell Date 2022-12-16 Time 10:48 Sent To  
Notes
2022-12-16 10:50:20THE PROPOSED PROJECT ENCOMPASSES THREE PARCELS
 74434316070000560, 74434316070000570 AND
 74434316060000010, A UNITY OF TITLE WILL BE REQUIRED,
 YOU WILL NEED TO CONTACT VINCE NOEL [email protected] OR
 CALL 561-494-1040 TO START THE UNITY OF TITLE
 PROCEDURE. YOU WILL NEED TO GO FILL OUT PALM BEACH
 COUNTY???S PARCEL COMBINATION REQUEST FORM WHICH CAN BE
 FOUND AT THIS LINK
 HTTPS://WWW.PBCGOV.ORG/PAPA/DEPARTMENTS/GIS.HTM, THEY
 WILL ISSUE YOU WITH A UNIFIED PARCEL CONTROL NUMBER
 (PCN). WHEN YOU CONTACT THE PROPERTY APPRAISERS YOU
 NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED PCN.
 ONCE YOU HAVE RECEIVED THE PRELIMINARY LETTER PLEASE
 CONTACT [email protected] OR CALL 561-805-6659.
 EACH INDIVIDUAL UNIT WILL REQUIRE IT'S OWN ADDRESS
 PLEASE REACH OUT TO [email protected] OR CALL
 561-805-6659.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-06-29 Time   Rev Time 0.00
Received By swelter Date 2023-06-29 Time 12:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-10 Cont ID  
Sent By rmcphers Date 2023-07-10 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2023-07-10 Time 12:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-16 Cont ID  
Sent By rmcphers Date 2023-06-16 Time 10:55 Rev Time 0.00
Received By rmcphers Date 2023-06-16 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-15 Cont ID  
Sent By rmcphers Date 2022-12-15 Time 15:36 Rev Time 0.00
Received By rmcphers Date 2022-12-15 Time 11:05 Sent To  
Notes
2022-12-15 15:36:11NEW APT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS. ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 2) PLEASE SHOW THE REQUIRED GUARD RAILING NEAR THE ROOF
 SCUTTLE HOLE - FBC 1015.7 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 3) PLEASE SHOW UNIT FIRE RATED DOOS TO BE SELF CLOSING
 - FBC 716.5.9
  
 4) PLEASE SHOW THE FINISH FLOORING TYPE. FOR THE UNITS
 ABOVE THE GROUND FLOOR THE FOLLOWING ACUSTICAL TEST
 REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 5) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, TRELLIS, PARKING LOT, SITE LIGHTING,
 RETAINING WALL, PLAYGROUND EQUIPMENT AND EXISTING
 BUILDING DEMOLITION - PLEASE ACKNOWLEDGE THIS.
  
 6) FLOORING TEST REPORTS, WINDOW, DOOR AND ROOFING
 SYSTEM PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY
 LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION
 DOCUMENTS - FBC WPB 107.3.4.1
  
 7) THE PROVIDED SURVEY DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-06-14 Cont ID  
Sent By mpeterso Date 2023-06-14 Time 11:44 Rev Time 0.00
Received By mpeterso Date 2023-06-14 Time 11:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-15 Cont ID  
Sent By mpeterso Date 2022-12-15 Time 13:05 Rev Time 0.00
Received By mpeterso Date 2022-12-15 Time 13:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2023-07-13 Cont ID  
Sent By cseifer Date 2023-07-13 Time 09:27 Rev Time 0.00
Received By cseifer Date 2023-07-13 Time 09:27 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-06-15 Cont ID  
Sent By lquinone Date 2023-06-15 Time 07:42 Rev Time 0.00
Received By lquinone Date 2023-06-15 Time 07:42 Sent To  
Notes
2023-06-15 07:42:40PROJECT UNDER FORMAL ENGINEERING SUBMITTAL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By rrossano Date 2022-12-14 Time   Rev Time  
Received By rrossano Date 2022-12-14 Time   Sent To  
Notes
2022-12-14 20:41:09A FORMAL ENGINEERING SUBMITTAL IS REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-07-12 Cont ID  
Sent By pleduc Date 2023-07-12 Time   Rev Time 0.00
Received By pleduc Date 2023-07-12 Time 10:51 Sent To  
Notes
2023-07-12 10:59:02FIRE COMMENTS:
  
 FIRE COMMENTS REGARDING THE 61G DOCUEMNTS DO NOT APPEAR
 TO STRICTLY MEETS THE REQUIREMENT, HOWEVER, IN AN
 EFFORT TO MOVE THIS PRORJECT
 AND PLAN REVIEW FORWARD, FIRE WILL PASS THIS REVIEW AND
 WILL REVIEW ALL APPLICABLE SHOP DRAWINGS FOR COMPLIANCE
 OF THE NFPA REQUIREMENTS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2023-06-12 Cont ID  
Sent By pleduc Date 2023-06-12 Time   Rev Time 0.00
Received By pleduc Date 2023-06-12 Time 12:04 Sent To  
Notes
2023-06-12 12:22:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION TO FIRE'S PREVIOUS COOMENTS
 REGARDING THE FIRE SPRINKLER & FIRE ALARM SYSTEMS
 REQUIRING DOCUMENTS TO BE SUBMITTED WITH THIS MASTR
 PERMITS.
  
 YOUR RESPONSE COMMENT STATED SHOP DRAWING WILL BE
 SUBMITTED, WHICH DOES NOT CORRECTLY ADDRESS THE
 COMMENT.
  
 PLEASE CONTACT YOUR EOR AND/OR A FLORIDA FIRE
 PROTECTION ENGINEER AND SUBMIT THE REQUIRED
 DOCUMENTATION WITH THIS MASTER PERMIT. SHOP DRAWINGS
 CAN THEN BE DESIGNED AND SUBMITTED LATER.
  
 THE DOCUMENTS DO NOT HAVE TO OFFICIAL PLAN SETS, THEY
 CAN BE OF LETTER/NARRATIVE TYPE STAMPED AND SEALED AS
 LONG AS THE INFORMATION AS OUTLINED IN THE F.A.C. BELOW
 IS CONTAINED IN IT.
  
 PLEASE RVIEW AND SUBMIT THE REQUIRED DOCUMENTS IN AN
 ACCEPTABLE FORMAT.
  
 FIRE'S PREVIOUS COMMENTS ARE RESUBMITTED BELOW,
 INCLUDING THE SMOKE ALARMS WHICH WOULD NOT NECESSARILY
 PART OF THE FIRE ALARM SYSTEM.
  
  
  
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
 ***************
  
  
 1) THERE ARE INDICATIONS OF A FIRE SPRINKLER SYSTEM BUT
 THERE ARE NO DOCUMENTS SUBMITTED WITH THIS MASTER
 PERMIT THAT OUTLINE THE FIRE SPRINKLER DESIGN FROM THE
 E.O.R PER THE FLORIDA ADMISTRATIVE CODE.
  
 PER F.A.C.
  
 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING
 DOCUMENTS.
 (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF
 PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR
 INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING
 PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER???S
 RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31,
 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE AHJ. THE DOCUMENTS SHALL INCLUDE:
 (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS
 REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A
 RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND
 EXPERIENCE.
 (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY
 STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH
 THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS
 ARE INTENDED TO CONFORM TO.
 (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF
 RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF
 THE SYSTEM.
 (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT
 SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING
 DOCUMENTS.
 (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY
 FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE
 ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE
 STATED PURPOSE OF THESE RESPONSIBILITY RULES.
 (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS.
 (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN
 ENGINEERING DOCUMENT ONLY FOR INFORMATION OR
 CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
 (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY
 DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST
 ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS.
 (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY
 ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN
 FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC
 AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND
 INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE
 REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES
 WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE
 AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A
 PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR
 AGENCY APPROVAL ACTION ON THE SAME PROJECT.
 SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW
 IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY???NEW
 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08.
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY???NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
 THE DESIGN DOCUMENTS ARE REQUIRED TO BE SUBMITTED WITH
 THE MASTER PERMT.
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTATION
 PER THE F.A.C.
  
  
 2) THERE ARE INDICATIONS OF A FIRE ALARM SYSTEM BUT
 THERE ARE NO DOCUMENTS SUBMITTED WITH THIS MASTER
 PERMIT THAT OUTLINE THE FIRE SPRINKLER DESIGN FROM THE
 E.O.R PER THE FLORIDA ADMISTRATIVE CODE.
  
 PER F.A.C.
  
 61G15-32.008 DESIGN OF FIRE ALARMS, SIGNALING SYSTEMS,
 AND CONTROL SYSTEMS.
 (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE
 PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS,
 ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE
 SIGNALING OF EMERGENCY CONDITIONS. ITEMS TO BE
 CONSIDERED IN THE DESIGN OR ANALYSIS OF FIRE ALARM AND
 DETECTION SYSTEMS ARE, AS APPLICABLE TO THE PARTICULAR
 PROJECT: OCCUPANCY AND CLASSIFICATION, MONITORING,
 CONTROL AND COMMUNICATION, CABLING AND SUPERVISION
 REQUIREMENTS, INSTALLATION REQUIREMENTS,
 INTEROPERABILITY AND PERFORMANCE REQUIREMENTS.
 (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE
 FLORIDA BUILDING CODE, THE FLORIDA FIRE PREVENTION
 CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY HAVING
 JURISDICTION. THE FLORIDA BUILDING CODE AND THE FLORIDA
 FIRE PREVENTION CODE ARE INCORPORATED BY REFERENCE IN
 RULE 61G15-18.011, F.A.C.
 (3) FOR ENGINEERING DOCUMENTS PERTAINING TO FIRE
 PROTECTION SYSTEMS EXEMPTED BY THE THRESHOLD
 REQUIREMENTS FOR MANDATORY USE OF PROFESSIONAL
 ENGINEERING SERVICES, THE ENGINEER OF RECORD SHALL
 DETERMINE THE LEVEL OF DETAIL SHOWN ON PLANS FOR A FIRE
 PROTECTION SYSTEM. ALL SUCH PLANS SHALL INCLUDE A
 DISCLAIMER STATING THE FIRE PROTECTION SYSTEM IS EXEMPT
 FROM PROFESSIONAL ENGINEERING SERVICES AND SHALL
 PROVIDE A CLEAR UNDERSTANDING OF THE MINIMUM SYSTEM
 REQUIREMENTS EXPECTED TO BE INSTALLED BY THE CONTRACTOR
 AND PERMITTED BY THE AUTHORITY HAVING JURISDICTION
 (AHJ). IN THE EVENT THE ENGINEER OF RECORD PROVIDES
 MORE INFORMATION AND DIRECTION THAN IS MINIMALLY
 REQUIRED, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE
 TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH
 APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING
 PRINCIPLES.
 (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND
 DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS
 SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION
 WHEN APPLICABLE:
 (A) THE DOCUMENTS SHALL BE CLEAR, WITH A SYMBOLS
 LEGEND, SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND
 NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS. THE
 DOCUMENTS SHALL INDICATE LOCATIONS WHERE FIRE RATINGS
 ARE REQUIRED AS DETERMINED BY THE SYSTEM???S
 SURVIVABILITY REQUIREMENTS, AND SHALL IDENTIFY THE
 GENERAL OCCUPANCY OF THE PROTECTED PROPERTY AND EACH
 ROOM AND AREA UNLESS IT IS CLEAR FROM FEATURES SHOWN.
 (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND
 CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND
 SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS
 INCLUDE ELEVATOR CONTROLS, SMOKE CONTROL SYSTEMS,
 DAMPERS, DOOR RELEASE, ANY OTHER SYSTEMS OR ELEMENTS
 DIRECTLY OR INDIRECTLY CONTROLLED OR MONITORED.
 (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL
 NOTIFICATION DEVICES.
 (D) IDENTIFY THE CLASS OF CIRCUITS AS LISTED IN NFPA
 72, WHICH IS CONTAINED WITHIN AND INCORPORATED INTO THE
 FLORIDA FIRE PREVENTION CODE.
 (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND
 CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY
 SIGNALS BEING MONITORED OR ANNUNCIATED.
 (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR
 ADDRESSABLE, AND INDICATE ALL ZONING.
 (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED
 PROTECTIVE FEATURES.
 (H) IDENTIFY AND LOCATE SYSTEM DEVICES THAT ARE SUBJECT
 TO ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR
 THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY
 OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR.
 (I) THE DOCUMENTS SHALL INCLUDE A SITE PLAN OF THE
 IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE
 OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE
 THE STRUCTURE.
 (J) IN BUILDINGS WHERE SMOKE DETECTION WILL BE
 OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE
 ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND
 DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE
 OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A
 PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH
 AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE
 ENGINEERING DESIGN DOCUMENTS.
 (K) FOR FIRE DETECTION SYSTEMS UTILIZING SMOKE
 DETECTION IN SITUATIONS WHERE SMOKE STRATIFICATION IS
 ANTICIPATED, THE DESIGN SHALL PROVIDE THE NECESSARY
 CRITERIA TO MITIGATE THE DETECTION PROBLEMS.
 (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA
 SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR
 STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING
 JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE
 FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING
 CODE.
 (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO
 PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED
 EVACUATION FOR ALL HIGH-RISE BUILDINGS OR
 MULTI-TENANTED PROPERTIES AS DEFINED IN SECTION 2 OF
 THE FLORIDA BUILDING CODE, BUILDING.
 (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS,
 CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND
 BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE
 PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND
 INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED
 TO OPERATE THE SYSTEMS AS INTENDED OVER TIME.
 (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO
 SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED
 WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS)
 CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL
 BE COMPLETED USING THE EQUIPMENT MANUFACTURER???S DATA
 AND APPLICABLE NFPA 72 PROCEDURES.
 (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (7) WHEN THE ENGINEER OF RECORD DETERMINES THAT SPECIAL
 REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE
 UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE
 REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (8) NO LATER THAN 90 DAYS PRIOR TO DECEMBER 31, 2026,
 THE BOARD SHALL REVIEW AND AMEND, MODIFY, OR SUNSET
 THIS RULE IF IT DETERMINES THIS RULE CREATES BARRIERS
 TO ENTRY FOR PRIVATE BUSINESS COMPETITION, IS
 DUPLICATIVE, OUTDATED, OBSOLETE, OVERLY BURDENSOME, OR
 IMPOSES EXCESSIVE COSTS. FAILURE BY THE BOARD TO ACT IN
 ACCORDANCE WITH THIS PROVISION WILL RESULT IN THE
 EXPIRATION OF THIS RULE ON DECEMBER 31, 2026.
 RULEMAKING AUTHORITY 471.008, 471.033(2) FS. LAW
 IMPLEMENTED 471.033 FS. HISTORY???NEW 5-19-93, FORMERLY
 21H-32.008, AMENDED 3-26-09, 3-28-17, 7-25-19, 3-23-22.
  
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTATION
 PER THE F.A.C.
  
  
  
 3) THERE ARE INDICATIONS OF SMOKE DETECTORS IN THE
 LIVING UNITS.
  
 PER NFPA 101 CH 30 , NEW APARTMENTS
  
 30.3.4.5* SMOKE ALARMS. SMOKE ALARMS SHALL BE INSTALLED
 IN ACCOR DANCE WITH 9.6.2.10 IN EVERY SLEEPING AREA,
 OUTSIDE EVERY SLEEPING AREA
 IN THE IMMEDIATE VICINITY OF THE BEDROOMS, AND ON ALL
 LEVELS OF THE
 DWELLING UNIT, INCLUDING BASEMENTS.
  
 9.6.2.10.9* IN NEW CONSTRUCTION, WHERE TWO OR MORE
 SMOKE ALARMS ARE
 REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR
 SIMILAR AREA, THEY
 SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM
 SHALL CAUSE THE
 ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT,
 SUITE OF ROOMS, OR
 SIMILAR AREA TO SOUND, UNLESS OTHERWISE PERMITTED BY
 ONE OF THE
 FOLLOWING:
 (1) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY WHERE
 PERMITTED BY
 ANOTHER SECTION OF THIS CODE.
 (2) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY TO
 CONFIGURATIONS
 THAT PROVIDE EQUIVALENT DISTRIBUTION OF THE ALARM
 SIGNAL
  
 9.6.2.10.10 THE ALARMS DESCRIBED IN 9.6.2.10.9 SHALL
 SOUND ONLY WITHIN
 AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR SIMILAR
 AREA AND SHALL NOT
 ACTUATE THE BUILDING FIRE ALARM SYSTEM, UNLESS
 OTHERWISE PERMITTED BY
 THE AUTHORITY HAVING JURISDICTION.
 9.6.2.10.11 SMOKE ALARMS SHALL BE PERMITTED TO BE
 CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM FOR THE PURPOSE OF
 ANNUNCIATION IN ACCORDANCE
 WITH NFPA 72.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEGMENT
  
  
  
 4) THERE ARE INDICATIONS OF SMOKE DETECTORS LOCATED IN
 HALLWAYS NEAR BATHROOM DOORS.
  
 9.6.2.10.6* SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT
 BE INSTALLED
 WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM A DOOR TO
 A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIM ITY TO SUCH LOCATIONS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE DIMENSION.
  
  
  
 5) THERE ARE INDICATIONS OF SMOKE DETECTORS IN THE
 COMMON AREA THAT IS LOCATED NEAR A COOKING APPLIANCE.
  
 9.6.2.10.4* UNLESS OTHERWISE PROVIDED IN 9.6.2.10.6,
 SMOKE ALARMS AND
 SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN AN AREA
 OF EXCLUSION DETER MINED BY A 10 FT (3.0 M) RADIAL
 DISTANCE ALONG A HORIZONTAL FLOW PATH
 FROM A STATIONARY OR FIXED COOKING APPLIANCE, UNLESS
 LISTED FOR INSTALLATION
 IN CLOSE PROXIMITY TO COOKING APPLIANCES. SMOKE ALARMS
 AND SMOKE
 DETECTORS INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT
 (6.1 M) ALONG A HORI ZONTAL FLOW PATH FROM A STATIONARY
 OR FIXED COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR USE
 PHOTOELECTRIC DETECTION
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE DIMENSION.
  
  
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-12-20 Cont ID  
Sent By pleduc Date 2022-12-20 Time   Rev Time 0.00
Received By pleduc Date 2022-12-20 Time 10:29 Sent To  
Notes
2022-12-14 15:33:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF A FIRE SPRINKLER SYSTEM BUT
 THERE ARE NO DOCUMENTS SUBMITTED WITH THIS MASTER
 PERMIT THAT OUTLINE THE FIRE SPRINKLER DESIGN FROM THE
 E.O.R PER THE FLORIDA ADMISTRATIVE CODE.
  
 PER F.A.C.
  
 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING
 DOCUMENTS.
 (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF
 PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR
 INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING
 PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER???S
 RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31,
 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE AHJ. THE DOCUMENTS SHALL INCLUDE:
 (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS
 REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A
 RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND
 EXPERIENCE.
 (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY
 STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH
 THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS
 ARE INTENDED TO CONFORM TO.
 (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF
 RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF
 THE SYSTEM.
 (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT
 SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING
 DOCUMENTS.
 (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY
 FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE
 ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE
 STATED PURPOSE OF THESE RESPONSIBILITY RULES.
 (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS.
 (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN
 ENGINEERING DOCUMENT ONLY FOR INFORMATION OR
 CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
 (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY
 DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST
 ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS.
 (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY
 ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN
 FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC
 AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND
 INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE
 REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES
 WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE
 AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A
 PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR
 AGENCY APPROVAL ACTION ON THE SAME PROJECT.
 SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW
 IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY???NEW
 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08.
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY???NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
 THE DESIGN DOCUMENTS ARE REQUIRED TO BE SUBMITTED WITH
 THE MASTER PERMT.
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTATION
 PER THE F.A.C.
  
  
 2) THERE ARE INDICATIONS OF A FIRE ALARM SYSTEM BUT
 THERE ARE NO DOCUMENTS SUBMITTED WITH THIS MASTER
 PERMIT THAT OUTLINE THE FIRE SPRINKLER DESIGN FROM THE
 E.O.R PER THE FLORIDA ADMISTRATIVE CODE.
  
 PER F.A.C.
  
 61G15-32.008 DESIGN OF FIRE ALARMS, SIGNALING SYSTEMS,
 AND CONTROL SYSTEMS.
 (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE
 PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS,
 ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE
 SIGNALING OF EMERGENCY CONDITIONS. ITEMS TO BE
 CONSIDERED IN THE DESIGN OR ANALYSIS OF FIRE ALARM AND
 DETECTION SYSTEMS ARE, AS APPLICABLE TO THE PARTICULAR
 PROJECT: OCCUPANCY AND CLASSIFICATION, MONITORING,
 CONTROL AND COMMUNICATION, CABLING AND SUPERVISION
 REQUIREMENTS, INSTALLATION REQUIREMENTS,
 INTEROPERABILITY AND PERFORMANCE REQUIREMENTS.
 (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE
 FLORIDA BUILDING CODE, THE FLORIDA FIRE PREVENTION
 CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY HAVING
 JURISDICTION. THE FLORIDA BUILDING CODE AND THE FLORIDA
 FIRE PREVENTION CODE ARE INCORPORATED BY REFERENCE IN
 RULE 61G15-18.011, F.A.C.
 (3) FOR ENGINEERING DOCUMENTS PERTAINING TO FIRE
 PROTECTION SYSTEMS EXEMPTED BY THE THRESHOLD
 REQUIREMENTS FOR MANDATORY USE OF PROFESSIONAL
 ENGINEERING SERVICES, THE ENGINEER OF RECORD SHALL
 DETERMINE THE LEVEL OF DETAIL SHOWN ON PLANS FOR A FIRE
 PROTECTION SYSTEM. ALL SUCH PLANS SHALL INCLUDE A
 DISCLAIMER STATING THE FIRE PROTECTION SYSTEM IS EXEMPT
 FROM PROFESSIONAL ENGINEERING SERVICES AND SHALL
 PROVIDE A CLEAR UNDERSTANDING OF THE MINIMUM SYSTEM
 REQUIREMENTS EXPECTED TO BE INSTALLED BY THE CONTRACTOR
 AND PERMITTED BY THE AUTHORITY HAVING JURISDICTION
 (AHJ). IN THE EVENT THE ENGINEER OF RECORD PROVIDES
 MORE INFORMATION AND DIRECTION THAN IS MINIMALLY
 REQUIRED, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE
 TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH
 APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING
 PRINCIPLES.
 (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND
 DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS
 SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION
 WHEN APPLICABLE:
 (A) THE DOCUMENTS SHALL BE CLEAR, WITH A SYMBOLS
 LEGEND, SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND
 NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS. THE
 DOCUMENTS SHALL INDICATE LOCATIONS WHERE FIRE RATINGS
 ARE REQUIRED AS DETERMINED BY THE SYSTEM???S
 SURVIVABILITY REQUIREMENTS, AND SHALL IDENTIFY THE
 GENERAL OCCUPANCY OF THE PROTECTED PROPERTY AND EACH
 ROOM AND AREA UNLESS IT IS CLEAR FROM FEATURES SHOWN.
 (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND
 CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND
 SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS
 INCLUDE ELEVATOR CONTROLS, SMOKE CONTROL SYSTEMS,
 DAMPERS, DOOR RELEASE, ANY OTHER SYSTEMS OR ELEMENTS
 DIRECTLY OR INDIRECTLY CONTROLLED OR MONITORED.
 (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL
 NOTIFICATION DEVICES.
 (D) IDENTIFY THE CLASS OF CIRCUITS AS LISTED IN NFPA
 72, WHICH IS CONTAINED WITHIN AND INCORPORATED INTO THE
 FLORIDA FIRE PREVENTION CODE.
 (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND
 CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY
 SIGNALS BEING MONITORED OR ANNUNCIATED.
 (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR
 ADDRESSABLE, AND INDICATE ALL ZONING.
 (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED
 PROTECTIVE FEATURES.
 (H) IDENTIFY AND LOCATE SYSTEM DEVICES THAT ARE SUBJECT
 TO ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR
 THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY
 OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR.
 (I) THE DOCUMENTS SHALL INCLUDE A SITE PLAN OF THE
 IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE
 OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE
 THE STRUCTURE.
 (J) IN BUILDINGS WHERE SMOKE DETECTION WILL BE
 OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE
 ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND
 DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE
 OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A
 PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH
 AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE
 ENGINEERING DESIGN DOCUMENTS.
 (K) FOR FIRE DETECTION SYSTEMS UTILIZING SMOKE
 DETECTION IN SITUATIONS WHERE SMOKE STRATIFICATION IS
 ANTICIPATED, THE DESIGN SHALL PROVIDE THE NECESSARY
 CRITERIA TO MITIGATE THE DETECTION PROBLEMS.
 (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA
 SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR
 STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING
 JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE
 FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING
 CODE.
 (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO
 PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED
 EVACUATION FOR ALL HIGH-RISE BUILDINGS OR
 MULTI-TENANTED PROPERTIES AS DEFINED IN SECTION 2 OF
 THE FLORIDA BUILDING CODE, BUILDING.
 (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS,
 CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND
 BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE
 PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND
 INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED
 TO OPERATE THE SYSTEMS AS INTENDED OVER TIME.
 (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO
 SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED
 WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS)
 CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL
 BE COMPLETED USING THE EQUIPMENT MANUFACTURER???S DATA
 AND APPLICABLE NFPA 72 PROCEDURES.
 (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (7) WHEN THE ENGINEER OF RECORD DETERMINES THAT SPECIAL
 REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE
 UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE
 REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (8) NO LATER THAN 90 DAYS PRIOR TO DECEMBER 31, 2026,
 THE BOARD SHALL REVIEW AND AMEND, MODIFY, OR SUNSET
 THIS RULE IF IT DETERMINES THIS RULE CREATES BARRIERS
 TO ENTRY FOR PRIVATE BUSINESS COMPETITION, IS
 DUPLICATIVE, OUTDATED, OBSOLETE, OVERLY BURDENSOME, OR
 IMPOSES EXCESSIVE COSTS. FAILURE BY THE BOARD TO ACT IN
 ACCORDANCE WITH THIS PROVISION WILL RESULT IN THE
 EXPIRATION OF THIS RULE ON DECEMBER 31, 2026.
 RULEMAKING AUTHORITY 471.008, 471.033(2) FS. LAW
 IMPLEMENTED 471.033 FS. HISTORY???NEW 5-19-93, FORMERLY
 21H-32.008, AMENDED 3-26-09, 3-28-17, 7-25-19, 3-23-22.
  
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTATION
 PER THE F.A.C.
  
  
  
 3) THERE ARE INDICATIONS OF SMOKE DETECTORS IN THE
 LIVING UNITS.
  
 PER NFPA 101 CH 30 , NEW APARTMENTS
  
 30.3.4.5* SMOKE ALARMS. SMOKE ALARMS SHALL BE INSTALLED
 IN ACCOR DANCE WITH 9.6.2.10 IN EVERY SLEEPING AREA,
 OUTSIDE EVERY SLEEPING AREA
 IN THE IMMEDIATE VICINITY OF THE BEDROOMS, AND ON ALL
 LEVELS OF THE
 DWELLING UNIT, INCLUDING BASEMENTS.
  
 9.6.2.10.9* IN NEW CONSTRUCTION, WHERE TWO OR MORE
 SMOKE ALARMS ARE
 REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR
 SIMILAR AREA, THEY
 SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM
 SHALL CAUSE THE
 ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT,
 SUITE OF ROOMS, OR
 SIMILAR AREA TO SOUND, UNLESS OTHERWISE PERMITTED BY
 ONE OF THE
 FOLLOWING:
 (1) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY WHERE
 PERMITTED BY
 ANOTHER SECTION OF THIS CODE.
 (2) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY TO
 CONFIGURATIONS
 THAT PROVIDE EQUIVALENT DISTRIBUTION OF THE ALARM
 SIGNAL
  
 9.6.2.10.10 THE ALARMS DESCRIBED IN 9.6.2.10.9 SHALL
 SOUND ONLY WITHIN
 AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR SIMILAR
 AREA AND SHALL NOT
 ACTUATE THE BUILDING FIRE ALARM SYSTEM, UNLESS
 OTHERWISE PERMITTED BY
 THE AUTHORITY HAVING JURISDICTION.
 9.6.2.10.11 SMOKE ALARMS SHALL BE PERMITTED TO BE
 CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM FOR THE PURPOSE OF
 ANNUNCIATION IN ACCORDANCE
 WITH NFPA 72.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEGMENT
  
  
  
 4) THERE ARE INDICATIONS OF SMOKE DETECTORS LOCATED IN
 HALLWAYS NEAR BATHROOM DOORS.
  
 9.6.2.10.6* SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT
 BE INSTALLED
 WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM A DOOR TO
 A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIM ITY TO SUCH LOCATIONS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE DIMENSION.
  
  
  
 5) THERE ARE INDICATIONS OF SMOKE DETECTORS IN THE
 COMMON AREA THAT IS LOCATED NEAR A COOKING APPLIANCE.
  
 9.6.2.10.4* UNLESS OTHERWISE PROVIDED IN 9.6.2.10.6,
 SMOKE ALARMS AND
 SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN AN AREA
 OF EXCLUSION DETER MINED BY A 10 FT (3.0 M) RADIAL
 DISTANCE ALONG A HORIZONTAL FLOW PATH
 FROM A STATIONARY OR FIXED COOKING APPLIANCE, UNLESS
 LISTED FOR INSTALLATION
 IN CLOSE PROXIMITY TO COOKING APPLIANCES. SMOKE ALARMS
 AND SMOKE
 DETECTORS INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT
 (6.1 M) ALONG A HORI ZONTAL FLOW PATH FROM A STATIONARY
 OR FIXED COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR USE
 PHOTOELECTRIC DETECTION
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE DIMENSION.
  
  
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-13 Cont ID  
Sent By vbroglia Date 2023-07-13 Time 15:29 Rev Time 0.00
Received By vbroglia Date 2023-07-07 Time 17:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-30 Cont ID  
Sent By aoliver Date 2023-06-30 Time 11:19 Rev Time 0.00
Received By aoliver Date 2023-06-09 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-06 Cont ID  
Sent By lmarchan Date 2023-02-06 Time 08:28 Rev Time 0.00
Received By lmarchan Date 2022-11-03 Time 14:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-13 Time 15:46 Sent To  
Notes
2023-07-13 15:46:487/13/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-12-15 Cont ID  
Sent By rmcphers Date 2022-12-15 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2022-12-15 Time 14:37 Sent To  
Notes
2022-12-15 14:38:11PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-06-27 Cont ID  
Sent By cmontell Date 2023-06-27 Time 13:49 Rev Time 0.00
Received By cmontell Date 2023-06-27 Time 13:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-15 Cont ID  
Sent By medwards Date 2022-12-15 Time 08:44 Rev Time 0.00
Received By medwards Date 2022-12-15 Time 08:44 Sent To  
Notes
2022-12-15 08:44:571ST REVIEW FMC
 PERMIT: 22100751
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THAT THE CONDENSING UNITS AND ROOF
 HATCH ARE A MINIMUM OF 10 FEET FROM THE ROOFS EDGE OR
 PROVIDE THE REQUIRED GUARDS. FMC 304.11
  
 2) PLEASE SHOW THAT ALL 3 BEDROOM MECHANICAL UNITS WILL
 PROVIDE THE REQUIRED 60 CFMS OF OUTDOOR AIR. FMC TABLE
 403.3.1.1
  
 3) THE FULLY SEALED DOORS SHOWN ON SHEET M-1 AND M-2
 NEED TO BE SHOWN ON THE DOOR SCHEDULE ON SHEET A-08.
 FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-12 Cont ID  
Sent By ccole Date 2023-07-12 Time 15:20 Rev Time 0.00
Received By ccole Date 2023-07-12 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-06-14 Cont ID  
Sent By ccole Date 2023-06-14 Time 11:19 Rev Time 0.00
Received By ccole Date 2023-06-13 Time 17:04 Sent To  
Notes
2023-06-14 11:19:43 
 3RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22100751
 6/14/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED. 3RD REQUEST FOR THE
 POTABLE WATER BACKFLOW PERMIT APPLICATION TO BE
 SUBMITTED. IF YOU DON'T UNDERSTAND WHAT IS REQUIRED
 PLEASE CONTACT ME.
  
 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT
 APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER-
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEET A-10.1 DETAIL 2: PLEASE SHOW THE WIDTH
 MEASUREMENT OF THE WATER CLOSET CLEAR FLOOR SPACE AS
 REQUIRED BY SEC. 604.3 FBC ACC.
  
 3) A10.0, A10.2: THE REQUIRED 30X48-INCH CLEAR FLOOR
 SPACE DIAGRAM FOR THE BATHTUB SHOWING A PERPENDICULAR
 APPROACH IN THE TYPE A BATHROOM WAS REMOVED. THIS
 REQUIRED CLEAR FLOOR SPACE ALSO SERVES AS THE
 MANEUVERABLE CLEARANCE BEYOND THE ARC OF THE INSWINGING
 DOOR- REFER TO EXAMPLE A BATHROOM ON PAGE 7.36 OF THE
 FHDA MANUAL.
  
 4) A10.0, A10.2: PLEASE REMOVE THE ROOM DIMENSIONS FORM
 THE GENERIC FHDA FLOOR PLANS TO AVOID CONFLICT WITH THE
 DIMENSIONS SHOWN ON THE SITE SPECIFIC FLOOR PLANS- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-21 Cont ID  
Sent By ccole Date 2022-12-21 Time 16:37 Rev Time 0.00
Received By ccole Date 2022-12-15 Time 11:09 Sent To  
Notes
2022-12-21 16:41:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100751
 12/16/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING
 ITEMS SHOWN ON THE PLANS:
 * POTABLE WATER SERVICE BACKFLOW PREVENTER.
 * FIRE LINE BACKFLOW PREVENTER.
 * IRRIGATION SYSTEM
 * IRRIGATION BACKFLOW PREVENTER
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEET A-1.0: PLEASE REFER TO SEC. 233 FBC
 ACCESSIBILITY. BASED ON SECS. 233.3.1 & 233.3.1.1 A
 MINIMUM OF ONE OF THE TWELVE DWELLING UNITS SHALL BE
 DESIGNED WITH COMMUNICATION AND MOBILITY FEATURES IN
 COMPLIANCE WITH SECS. 809.2 & 809.4.
 CONCERNING THE PLUMBING REVIEW, THE BATHROOM IN THE
 UNIT THAT MUST MEET COMPLIANCE SHALL BE DESIGNED IN
 ACCORDANCE WITH 809.4. SEC. 809.4 REFERS THE DESIGNER
 TO SECS. 603-610 FOR TOILET AND BATHING FIXTURE
 INSTALLATIONS. BECAUSE 809.2 REQUIRES THE SELECTED UNIT
 TO BE ON AN ACCESSIBLE ROUTE IT APPEARS THE UNIT
 MEETING COMPLIANCE SHALL BE ON THE GROUND FLOOR. PLEASE
 PROVIDE AN ENLARGED DRAWING OF THE SELECTED UNIT
 INDICATING COMPLIANCE WITH THE FOLLOWING LIST OF FBC
 ACC COMPLIANCES:
  
 A) SEC. 603.2.1: PROVIDE A TURNING SPACE IN THE
 BATHROOM COMPLYING WITH SEC. 304.
  
 B) SEC. 603.3 SHOW THE HEIGHT OF THE MIRROR AT THE
 LAVATORY TO BE INSTALLED WITH THE REFLECTIVE SURFACE 40
 INCHES MAXIMUM FOR THE FINISHED FLOOR.
  
 C) SEC. 604.3: CLEARANCE AROUND THE WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURE PERPENDICULAR
 FOR THE REAR WALL. PROVIDE A 60 IN. WIDE X 56 IN. CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE WATER
 CLOSETS. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
 LOCATED WITHIN THE REQUIRED CLEARANCE, HOWEVER THERE IS
 AN EXCEPTION WHICH ALLOWS A LAVATORY TO BE INSTALLED ON
 THE REAR WALL 18 INCHES MINIMUM FROM THE WATER CLOSER
 CENTERLINE WHERE THE CLEARANCE AT THE WATER CLOSET IS
 66 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 D) SEC. 606.2: A 30 INCHES X 48 INCHES CLEAR FLOOR
 SPACE POSITIONED FOR A FORWARD APPROACH IS REQUIRED FOR
 THE LAVATORY. KNEE AND TOE CLEARANCES ARE REQUIRED
 HOWEVER PLEASE NOTE EXCEPTION 3 A, B, & C WHICH ALLOWS
 FOR REMOVABLE CABINETRY AT THE LAVATORY.
  
 E) SEC. 604.2: SHOW THE CENTERLINE OF THE WATER CLOSET
 TO BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE
 SIDE WALL.
  
 F) SEC. 604.4 EXCEPTION 2: SHOW THE HEIGHT OF THE WATER
 CLOSET SEAT 15 INCHES MINIMUM AND 19 INCHES MAXIMUM
 FROM THE FINISHED FLOOR.
  
 G) SEC. 604.5 EXCEPTION 2: SHOW LOCATIONS, LENGTHS, AND
 MOUNTING HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS-
 SECS. 604.5 & 609.4, FIGURES 604.5.1 & 604.5.2, OR
 PROVIDE REINFORCEMENT LOCATIONS FOR FUTURE
 INSTALLATIONS PER EXCEPTION 2.
  
 H) SEC. 604.7: SHOW THE CENTERLINE OF THE TOILET PAPER
 DISPENSER TO BE LOCATED 7 INCHES MINIMUM TO 9 INCHES
 MAXIMUM FROM THE FRONT OF THE WATER CLOSET TO THE
 CENTERLINE OF THE DISPENSER.
  
 I) SEC. 606.3: SHOW THE HEIGHT OF THE LAVATORY SINK RIM
 OR COUNTER SURFACE TO BE MAXIMUM 34 INCHES FROM THE
 FINISHED FLOOR UNLESS MEETING EXCEPTION 2 WHICH ALLOWS
 THE HEIGHT TO BE 29-36 INCHES WHERE THE PLUMBING ROUGH
 IN LOCATIONS ALLOW FOR A SINK AT A HEIGHT OF 29 INCHES.
  
 J) SEC. 607.2: SHOW THE CLEAR FLOOR SPACE FOR THE
 BATHTUB TO EXTEND THE LENGTH OF THE BATHTUB AND 30
 INCHES WIDE MINIMUM. A LAVATORY COMPLYING WITH SEC. 606
 IS PERMITTED AT THE CONTROL END OF THE CLEARANCE.
  
 K) SEC. 607.3: SHOW EITHER A PERMANENT SEAT AT THE HEAD
 OF THE TUB OR A REMOVABLE SEAT SHALL BE PROVIDED.
 PLEASE SEE SECS. 607.4.1- 607.4.2.3.
  
 L) SEC. 607.4: SHOW GRAB LOCATIONS IN COMPLIANCE WITH
 SEC. 607.4.1- 607.4.1.2 UNLESS INSTALLING
 REINFORCEMENTS IN ACCORDANCE WITH EXCEPTION 2.
  
 M) SEC. 607.5: SHOW THE BATHTUB CONTROLS LOCATION.
  
 3) SHEET A-10: PLEASE REFER TO PAGES 7.36 & 7.65 OF THE
 FHDA MANUAL AND REVISE THE DIAGRAM TO SHOW THE CLEAR
 FLOOR SPACE DIAGRAMS AND DIMENSIONS INSIDE THE BATH
 FLOOR PLAN DRAWING- SEC. 107.2.1 WPB.
  
 4) A-10: REFER TO PAGES 6.3- 6.9 AND SHOW GRAB BAR
 REINFORCEMENT LOCATIONS WITH DIMENSIONS AT THE TOILET
 AND BATHTUB.
  
 5) P-6: THE PLANS DO NOT SHOW THE WATER HEATER DRAIN
 PAN LINE RUNS AND DISCHARGE LOCATIONS. PLEASE PROVIDE
 DETAILS IN COMPLIANCE WITH SECS. 504.7.1 & 504.7.2 FBC
 P.
  
 6) P-6: PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 WATER HEATERS SHOWING THE MAKES AND MODELS, GALLON
 SIZES, AND EFFICIENCY RATINGS TO MATCH WITH THE DATA
 LISTED ON THE SUBMITTED ENERGY COMPLIANCE FORMS- TABLE
 C404.2 FBC EC. THE WATER HEATERS SPECIFICATIONS CAN BE
 DEFERRED SUBMITTALS IF PREFERRED- SEE SEC. 107.3.4.1
 WPB.
  
 7) P-2: PLEASE PROVIDE A STORM DRAIN ISOMETRIC DRAWING
 SHOWING THE VERTICAL AND HORIZONTAL PIPING RUNS AND
 SIZES FROM THE ROOF DRAINS TO DISCHARGE LOCATIONS- SEC.
 107.3.5.1.3 (7) WPB, AND SECS. 1101.2, 1106.2 & 1106.3
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2023-06-16 Cont ID  
Sent By rmcphers Date 2023-06-16 Time 10:56 Rev Time 0.00
Received By rmcphers Date 2023-06-16 Time 10:56 Sent To  
Notes
2023-06-16 10:56:24ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-12-15 Cont ID  
Sent By rmcphers Date 2022-12-15 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2022-12-15 Time 14:37 Sent To  
Notes
2022-12-15 14:37:20SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-10 Cont ID  
Sent By rmcphers Date 2023-07-10 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2023-07-10 Time 12:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-14 Cont ID  
Sent By mpeterso Date 2023-06-14 Time 11:59 Rev Time 0.00
Received By mpeterso Date 2023-06-14 Time 11:59 Sent To  
Notes
2023-06-14 11:59:52ALL PLANS PASSED SIGNATURE REVIEW. MP
2023-06-14 11:20:12PLUMBING SIGNATURES PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-12-15 Cont ID  
Sent By rmcphers Date 2022-12-15 Time 15:42 Rev Time 0.00
Received By rmcphers Date 2022-12-15 Time 15:42 Sent To  
Notes
2022-12-15 15:48:51SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE PROVIDED SURVEY DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2022-12-15 08:45:40MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2023-07-13 Cont ID  
Sent By jswaby Date 2023-07-13 Time 15:29 Rev Time 0.00
Received By vbroglia Date 2023-07-13 Time 15:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-06-22 Cont ID  
Sent By jswaby Date 2023-06-22 Time 16:53 Rev Time 0.00
Received By jlswaby Date 2023-06-22 Time 16:51 Sent To  
Notes
2023-06-22 16:53:35PER PREVIOUS COMMENTS.
  
 ZONING PROVISOS:
  
 1. DURING CONSTRUCTION:
  
 1.1. THE PROPERTY OWNER AND CONTRACTOR SHALL MAKE
 ARRANGEMENTS FOR PARKING OF CONTRACTOR VEHICLES TO
 MINIMIZE THE IMPACT ON ALL NEIGHBORING PROPERTIES.
  
 1.2. THE PROPERTY OWNER AND CONTRACTOR SHALL PROTECT
 ALL NEIGHBORING PROPERTY, INCLUDING VEHICLES, FROM
 DAMAGE OR DIRT CAUSED BY THE CONSTRUCTION, AND SHALL
 NOTIFY THE OCCUPANTS OF NEIGHBORING PROPERTIES ABOUT
 ALL STAGES OF CONSTRUCTION THAT MAY AFFECT THE USE OF
 THEIR PROPERTY.
  
 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING
 TREES, A TREE ALTERATION PERMIT SHALL BE OBTAINED FROM
 THE DEVELOPMENT SERVICES DEPARTMENT PLANNING DIVISION.
  
 3. IF APPLICABLE, THE DEVELOPER, ITS SUCCESSORS AND
 ASSIGNS SHALL BE RESPONSIBLE FOR THE PERMITTING AND
 INSTALLATION OF ANY STREET TREES, TREE GRATES, AND
 RIGHT-OF-WAY LANDSCAPING AND IRRIGATION THAT MAY BE
 APPROVED WITH THIS PETITION. ALL PERMITS SHALL BE
 OBTAINED PRIOR TO COMMENCEMENT OF CONSTRUCTION OF SUCH
 IMPROVEMENTS.
  
 4. IF APPLICABLE, THE DEVELOPER, ITS SUCCESSORS AND
 ASSIGNS SHALL BE RESPONSIBLE FOR THE MAINTENANCE OF THE
 ROAD RIGHT-OF-WAY LANDSCAPING, TREE GRATES AND
 IRRIGATION ADJACENT TO THE PROPERTY THAT MAY BE
 APPROVED WITH THIS PETITION. A MAINTENANCE AGREEMENT
 WITH THE CITY SHALL BE EXECUTED PRIOR TO THE ISSUANCE
 OF A CERTIFICATE OF OCCUPANCY.
  
 5. IF APPLICABLE, ANY REQUIRED EASEMENTS (I.E.
 DRAINAGE, UTILITIES, PUBLIC ACCESS, OUTFALL, ETC.)
 SHALL BE PROVIDED VIA PLAT OR SEPARATE LEGAL
 INSTRUMENT.
  
 6. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY.
  
 7. PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY:
  
 7.1. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE
 WITH ALL APPLICABLE STATUTES, REGULATIONS, AND THE
 CITYS POLICIES AND PROCEDURES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
  
 JERMAINE SWABY
 SENIOR PLANNER
 561-822-1431
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2023-02-03 Cont ID  
Sent By jroach Date 2023-02-03 Time 08:36 Rev Time 0.00
Received By jroach Date 2023-02-03 Time 08:26 Sent To  
Notes
2023-02-03 08:36:35ZONING PROVISOS:
  
 1. DURING CONSTRUCTION:
  
 1.1. THE PROPERTY OWNER AND CONTRACTOR SHALL MAKE
 ARRANGEMENTS FOR PARKING OF CONTRACTOR VEHICLES TO
 MINIMIZE THE IMPACT ON ALL NEIGHBORING PROPERTIES.
  
 1.2. THE PROPERTY OWNER AND CONTRACTOR SHALL PROTECT
 ALL NEIGHBORING PROPERTY, INCLUDING VEHICLES, FROM
 DAMAGE OR DIRT CAUSED BY THE CONSTRUCTION, AND SHALL
 NOTIFY THE OCCUPANTS OF NEIGHBORING PROPERTIES ABOUT
 ALL STAGES OF CONSTRUCTION THAT MAY AFFECT THE USE OF
 THEIR PROPERTY.
  
 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING
 TREES, A TREE ALTERATION PERMIT SHALL BE OBTAINED FROM
 THE DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING
 DIVISION.
  
 3. IF APPLICABLE, THE DEVELOPER, ITS SUCCESSORS AND
 ASSIGNS SHALL BE RESPONSIBLE FOR THE PERMITTING AND
 INSTALLATION OF ANY STREET TREES, TREE GRATES, AND
 RIGHT-OF-WAY LANDSCAPING AND IRRIGATION THAT MAY BE
 APPROVED WITH THIS PETITION. ALL PERMITS SHALL BE
 OBTAINED PRIOR TO COMMENCEMENT OF CONSTRUCTION OF SUCH
 IMPROVEMENTS.
  
 4. IF APPLICABLE, THE DEVELOPER, ITS SUCCESSORS AND
 ASSIGNS SHALL BE RESPONSIBLE FOR THE MAINTENANCE OF THE
 ROAD RIGHT-OF-WAY LANDSCAPING, TREE GRATES AND
 IRRIGATION ADJACENT TO THE PROPERTY THAT MAY BE
 APPROVED WITH THIS PETITION. A MAINTENANCE AGREEMENT
 WITH THE CITY SHALL BE EXECUTED PRIOR TO THE ISSUANCE
 OF A CERTIFICATE OF OCCUPANCY.
  
 5. IF APPLICABLE, ANY REQUIRED EASEMENTS (I.E.
 DRAINAGE, UTILITIES, PUBLIC ACCESS, OUTFALL, ETC.)
 SHALL BE PROVIDED VIA PLAT OR SEPARATE LEGAL
 INSTRUMENT.
  
 6. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY.
  
 7. PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY:
  
 7.1. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE
 WITH ALL APPLICABLE STATUTES, REGULATIONS, AND THE
 CITY???S POLICIES AND PROCEDURES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  