Plan Review Details - Permit 22100740
Plan Review Stops For Permit 22100740
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2023-06-23 Cont ID  
Sent By cpuell Date 2023-06-23 Time 10:19 Rev Time 0.00
Received By cpuell Date 2023-06-23 Time 10:19 Sent To  
Notes
2023-06-23 10:20:43THIS PERMIT IS FOR THE SOUTH BUILDING ONLY WITH THE
 ADDRESS OF 2160 N TAMARIND AVE. RECEIVED PRELIMINARY
 LETTER FROM THE COUNTY 74434316100030090
 74434316100030101 AND 74434316100030110 WILL MERGE INTO
 74434316100030090. PRIMARY ADDRESS FOR THE PARCEL WILL
 BE 2160 N TAMARIND AVE, THE FOLLOWING ADDRESSES HAVE
 ALSO BEEN APPROVED 2190 N TAMARIND AVE 2160 N TAMARIND
 AVE 200 201 202 300 301 302 2202 N TAMARIND AVE 2212 N
 TAMARIND AVE 2224 N TAMARIND AVE 2236 N TAMARIND AVE
 2190 N TAMARIND AVE AND 2202 N TAMARIND AVE 200 201 202
 300 301 302. APPLICANT INFORMED PLANS AND APPLICATIONS
 FORMS NEED TO BE UPDATED WITH THE PRIMARY ADDRESS 2160
 N TAMARIND AVE.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By cpuell Date 2023-05-02 Time 13:08 Rev Time 0.00
Received By cpuell Date 2023-05-02 Time 13:08 Sent To  
Notes
2023-05-02 13:08:52NOBODY HAS CONTACTED ADDRESSING TO ADDRESS THE ADDRESS
 ISSUES. PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By cpuell Date 2023-01-17 Time 08:05 Rev Time 0.00
Received By cpuell Date 2023-01-17 Time 08:05 Sent To  
Notes
2023-01-17 08:15:15PROJECT ENCOMPASSES MULTIPLE PARCELS 74434316100030101
 74434316100030090 AND 74434316100030110, A UNITY OF
 TITLE OR REPLAT NEEDS TO BE APPLIED FOR TO CREATE A
 SINGLE PARCEL. YOU WILL NEED TO CONTACT VINCE NOEL
 [email protected] OR CALL 561-494-1040 TO START THE UNITY
 OF TITLE/ REPLAT PROCEDURE. CURRENTLY THERE ARE THREE
 SEPARATE PROPERTY CONTROL NUMBER (PCN) FOR THE TWO
 UNITS, YOU WILL NEED TO GO FILL OUT PALM BEACH COUNTYS
 PARCEL COMBINATION REQUEST FORM WHICH CAN BE FOUND AT
 THIS LINK
 HTTPS://WWW.PBCGOV.ORG/PAPA/DEPARTMENTS/GIS.HTM, THEY
 WILL ISSUE YOU WITH A UNIFIED PARCEL CONTROL NUMBER
 (PCN). WHEN YOU CONTACT THE PROPERTY APPRAISERS YOU
 NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED PCN.
 ONCE YOU HAVE RECEIVED THE PRELIMINARY LETTER PLEASE
 CONTACT [email protected] OR CALL 561-805-6659 TO BE
 ISSUED AN ADDRESS.
  
 IN JANUARY 2022 YOU WERE INFORMED IN PPRC REVIEW THAT
 YOU NEED TO CONTACT ME PER ROBERT BROWNS BUILDING
 REVIEW. ADDRESSES NEED TO BE ESTABLISHED FOR THE
 PROJECT, INCLUDING SEPARATE ADDRESSES FOR BUILDINGS A
 AND B AND EACH INDIVIDUAL UNIT ALONG WITH COMMON AREAS
 SUCH AS THE GYM. PLEASE PROVIDE A SITE PLAN SHOWING THE
 PRIMARY ENTRANCE TO BUILDINGS A AND B AND PLEASE
 INDICATE THE ENTRANCES TO THE UNITS. CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2023-02-23 Cont ID  
Sent By swelter Date 2023-02-23 Time 11:53 Rev Time 0.00
Received By swelter Date 2023-02-23 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-07-10 Cont ID  
Sent By rmcphers Date 2023-07-10 Time 10:24 Rev Time 0.00
Received By rmcphers Date 2023-07-10 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-21 Cont ID  
Sent By rmcphers Date 2023-06-21 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2023-06-21 Time 14:09 Sent To  
Notes
2023-06-21 14:11:47NEW 3 STORY MULTI FAMILY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS 10.00, 10.1, 10.2 - PLEASE SHOW THE CLEAR
 FLOOR SPACE FOR THE BATH TUB - FBC FHA REQUIREMENT 7
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-01 Cont ID  
Sent By rmcphers Date 2023-05-01 Time 13:54 Rev Time 0.00
Received By rmcphers Date 2023-05-01 Time 13:50 Sent To  
Notes
2023-05-01 13:54:05NEW 3 STORY MULTI FAMILY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS AS LISTED ON THE DRAWINGS.
  
 2) PLEASE PROVIDE THE FOLLOWING ACUSTICAL TEST REPORTS
 FOR THE UNIT FLOORING - - THE FOLLOWING ACOUSTICAL TEST
 REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 3) ITEMS SUCH AS FLOORING ACOUSTICAL TEST REPORTS,
 WINDOW/DOOR/ROOFING SYSTEM PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1
  
 4) FYI - SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, RETAINING WALL, BARBEQUE HUT, PARKING LOT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By rmcphers Date 2023-01-23 Time 10:29 Rev Time 0.00
Received By rmcphers Date 2023-01-20 Time 15:37 Sent To  
Notes
2023-01-23 09:56:03NEW 3 STORY MULTI FAMILY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS AS LISTED ON THE DRAWINGS.
  
 2) SOME DRAWINGS SUCH AS A-1.0A AND LS-1 SHOW ASCE 7-10
 USED FOR WIND DESIGN - SHOULD BE ASCE 7-16
  
 3) PLEASE SHOW THE GUARD AT THE ROOF HATCH - FBC 1015.7
 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW
  
 4) FIRE RATED ENTRY DOOS NEED TO SHOW THAT SELF CLOSING
 AND LATCHING IS REQUIRED - FBC 716.5.9 DOOR CLOSING.
 FIRE DOORS SHALL BE LATCHING AND SELF- OR
 AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS SECTION.
  
 5) PLEASE SHOW THE STAIR HANDRAIL EXTENSIONS AT THE
 BOTTOM TO SLOPE PER FBC 1014.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 6) THE WALK IN CLOSET DOOR IN THE MASTER BED ROOM
 REQUIRES A 32 INCH CLEAR OPENING - FBC FHA REQUIREMENT
 3 (2)
  
 7) PLEASE PROVIDE THE FOLLOWING ACUSTICAL TEST REPORTS
 FOR THE UNIT FLOORING - - THE FOLLOWING ACOUSTICAL TEST
 REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 8) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, RETAINING WALL, BARBEQUE HUT, PARKING LOT.
  
 9) ITEMS SUCH AS FLOORING ACOUSTICAL TEST REPORTS,
 WINDOW/DOOR/ROOFING SYSTEM PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-06-22 Cont ID  
Sent By jleahy Date 2023-06-22 Time 15:03 Rev Time 0.00
Received By jleahy Date 2023-06-22 Time 15:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-08 Cont ID  
Sent By jleahy Date 2023-05-08 Time 16:37 Rev Time 0.00
Received By jleahy Date 2023-05-08 Time 16:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-27 Cont ID  
Sent By jleahy Date 2023-01-27 Time 15:11 Rev Time 0.00
Received By jleahy Date 2023-01-27 Time 15:01 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-05-08 Cont ID  
Sent By jleahy Date 2023-05-08 Time 16:37 Rev Time 0.00
Received By jleahy Date 2023-05-08 Time 16:37 Sent To  
Notes
2023-05-08 16:38:53VOICE/DATA AND TV AS PER PLANS. JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2023-07-13 Cont ID  
Sent By cseifer Date 2023-07-13 Time 09:26 Rev Time 0.00
Received By cseifer Date 2023-07-13 Time 09:26 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2023-06-23 Cont ID  
Sent By cseifer Date 2023-06-23 Time 14:05 Rev Time 0.00
Received By cseifer Date 2023-06-23 Time 14:05 Sent To  
Notes
2023-06-23 14:05:50UNDER FORMAL ENGINEERING REVIEW SUBMITTAL.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-05-04 Cont ID  
Sent By lquinone Date 2023-05-04 Time 11:09 Rev Time 0.00
Received By lquinone Date 2023-05-04 Time 11:09 Sent To  
Notes
2023-05-04 11:09:54UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By rrossano Date 2023-01-17 Time   Rev Time  
Received By rrossano Date 2023-01-17 Time   Sent To  
Notes
2023-01-17 12:00:15UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-07-12 Cont ID  
Sent By pleduc Date 2023-07-12 Time   Rev Time 0.00
Received By pleduc Date 2023-07-12 Time 11:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-06-21 Cont ID  
Sent By pleduc Date 2023-06-21 Time   Rev Time 0.00
Received By pleduc Date 2023-06-21 Time 12:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-01 Cont ID  
Sent By pleduc Date 2023-05-01 Time   Rev Time 0.00
Received By pleduc Date 2023-05-01 Time 14:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-18 Cont ID  
Sent By cwalker Date 2023-01-18 Time   Rev Time  
Received By cwalker Date 2023-01-18 Time   Sent To  
Notes
2023-01-18 13:43:48FIRE PROVISO COMMENTS:
  
 (1) DOOR LOCKING ARRANGEMENTS SHALL COMPLY WITH LIFE
 SAFETY CODE, NFPA 30.2.2.2
  
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-14 Cont ID  
Sent By aoliver Date 2023-07-14 Time 08:23 Rev Time 0.00
Received By aoliver Date 2023-07-07 Time 17:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-30 Cont ID  
Sent By cmontell Date 2023-06-30 Time 12:26 Rev Time 0.00
Received By cmontell Date 2023-06-30 Time 12:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-11 Cont ID  
Sent By lmarchan Date 2023-05-11 Time 08:37 Rev Time 0.00
Received By lmarchan Date 2023-04-28 Time 17:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-23 Cont ID  
Sent By aoliver Date 2023-02-23 Time 12:34 Rev Time 0.00
Received By aoliver Date 2023-01-13 Time 15:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-13 Time 15:43 Sent To  
Notes
2023-07-13 15:44:037/13/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By rmcphers Date 2023-01-23 Time 10:42 Rev Time 0.00
Received By rmcphers Date 2023-01-23 Time 10:42 Sent To  
Notes
2023-01-23 10:44:16PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-06-30 Cont ID  
Sent By cmontell Date 2023-06-30 Time 12:26 Rev Time 0.00
Received By cmontell Date 2023-06-30 Time 12:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-05-08 Cont ID  
Sent By medwards Date 2023-05-08 Time 08:49 Rev Time 0.00
Received By medwards Date 2023-05-08 Time 08:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-18 Cont ID  
Sent By medwards Date 2023-01-18 Time 09:39 Rev Time 0.00
Received By medwards Date 2023-01-18 Time 09:39 Sent To  
Notes
2023-01-18 09:39:421ST REVIEW FMC
 PERMIT: 22100740
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1 AND AC CALCULATIONS GYM: PLEASE CORRECT
 THE O/A CALCULATIONS FOR THE GYM THE RA RATE SHOULD BE
 CALCULATED AT .18 AND NOT .06. OCCUPANCY CLASSIFICATION
 IS GYM, STADIUM, ARENA PLAY AREA. FMC TABLE 403.3.1.1
  
 2) SHEET M-1: PLEASE SHOW THAT THE OUTDOOR AIR INTAKE
 TERMINATION LOCATIONS SHALL MEET THE REQUIREMENTS OF
 FMC 401.4.
  
 3) SHEET M-2: PROVIDE DETAILS FOR THE GUARD PROTECTION
 REQUIRED FOR THE EQUIPMENT ON THE ROOF. FMC 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2023-07-12 Cont ID  
Sent By ccole Date 2023-07-12 Time 07:47 Rev Time 0.00
Received By ccole Date 2023-07-12 Time 07:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2023-06-20 Cont ID  
Sent By ccole Date 2023-06-20 Time 13:48 Rev Time 0.00
Received By ccole Date 2023-06-20 Time 11:24 Sent To  
Notes
2023-06-20 13:50:034TH REVIEW FBC-2020 PLUMBING
 PERMIT- 22100740
 6/20/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED. 4TH REQUEST FOR THE
 BACKFLOW PERMIT APPLICATION TO BE SUBMITTED. PLEASE
 COMMENT #1 BELOW AND IF YOU DON'T UNDERSTAND WHAT IS
 REQUIRED PLEASE CONTACT ME ASAP.
  
 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT
 APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER-
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS.
  
 1) SHEETS A10.0, A10.1 & A10.2- DETAIL 3: THE REQUIRED
 30X48-INCH CLEAR FLOOR SPACE DIAGRAM FOR THE BATHTUB
 SHOWING A PERPENDICULAR APPROACH IN THE TYPE A BATHROOM
 WAS REMOVED FROM THE CORRECTED PLAN. THIS REQUIRED
 CLEAR FLOOR SPACE ALSO SERVES AS THE MANEUVERABLE
 CLEARANCE BEYOND THE ARC OF THE INSWINGING DOOR- REFER
 TO EXAMPLE A BATHROOM ON PAGE 7.36 OF THE FHDA MANUAL
 AND CORRECT THE DETAIL.
  
 2) A10.0, A10.2: PLEASE REMOVE THE ROOM DIMENSIONS FROM
 THE GENERIC FHDA BATHROOM FLOOR PLAN EXAMPLES OR CHANGE
 THE DIMENSIONS TO MATCH WITH THE SITE SPECIFC FLOOR
 PLAN DIMESNIONS- SEC. 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-05-02 Cont ID  
Sent By ccole Date 2023-05-02 Time 08:25 Rev Time 0.00
Received By ccole Date 2023-05-01 Time 14:52 Sent To  
Notes
2023-05-02 08:27:123RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22100740
 5/2/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT
 APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER-
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEETS A1.0 & A05.3: THE LOCATION OF THE ENLARGED
 3-BEDROOM UNIT FLOOR PLAN ON A05.3 DOES NOT MATCH THE
 LOCATION SHOWN ON THE A1.0. PLEASE SHOW THE ACCESSIBLE
 ROUTE INTO THE ADA COMPLIANT UNIT- SECS. 206.1,
 206.2.4, 206.4 FBC ACC.
  
 3) SHEET A10.1: CORRECT CLEAR FLOOR SPACES IN DETAIL 2
 TO SHOW A FORWARD APPROACH TO THE LAVATORY EXTENDING
 UNDER THE UNIT, AND A PARALLEL APPROACH TO THE BATHTUB
 IN ACCORDANCE WITH SECS. 606.2 AND 607.2 FBC.
  
 4) A10.1: PLEASE DETAIL THE REQUIRED GRAB BAR AT THE
 BATHTUB HEAD END WALL- SEC. 607.4.2.3 FBC ACC.
  
 5) P-3 & P-4: THE PVC WATER HEATER DRAIN LINES IN THE
 AC CLOSET PLENUM ENCLOSURES ARE NOT PERMITTED PER SEC
 602.2.1 FBC M. PVC IS COMBUSTIBLE MATERIAL AND CAN BE
 USED OUTSIDE OF THE ENCLOSURES. PLEASE SELECT A DRAIN
 MATERIAL THAT MEETS COMPLIANCE SUCH AS COPPER.
  
 5A) P-4: THE PLAN DOES NOT SHOW THE WATER HEATER DRAIN
 PAN LINE RUNS AND DISCHARGE LOCATIONS FOR UNITS B-3 &
 C-3- SECS. 504.7.1 & 504.7.2 FBC P.
  
 6) P-5: PLEASE CORRECT THE NOTE FROM THE FBC RES. CODE
 INDICATING NON-RECIRCULATED HOT WATER SHALL NOT EXCEED
 100 FT. REFER TO SEC. 607.2 FBC P- THE LONGEST
 ALLOWANBLE DISTANCE IS 50 FT.
  
 7) P-6: A NEW WATER HEATER NOTE INDICATES A TEMPERATURE
 LIMITING DEVICE SHALL BE PROVIDED HOWEVER NO DEVICE IS
 SHOWN. PLEASE SHOW THE LOCATION OF THE DEVICE AND
 PIPING CONNECTIONS- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-02-17 Cont ID  
Sent By ccole Date 2023-02-17 Time 12:03 Rev Time 0.00
Received By ccole Date 2023-02-17 Time 08:57 Sent To  
Notes
2023-02-17 12:03:55FBC-2020 PLUMBING
 PERMIT- 22100740
 2/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING
 ITEMS SHOWN ON THE PLANS:
 * POTABLE WATER SERVICE BACKFLOW PREVENTER.
 * FIRE LINE BACKFLOW PREVENTER.
 * IRRIGATION SYSTEM
 * IRRIGATION BACKFLOW PREVENTER
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEET A-1.0A: PLEASE REFER TO SEC. 233 FBC
 ACCESSIBILITY. BASED ON SECS. 233.3.1 & 233.3.1.1 A
 MINIMUM OF ONE OF THE EIGHT DWELLING UNITS SHALL BE
 DESIGNED WITH COMMUNICATION AND MOBILITY FEATURES IN
 COMPLIANCE WITH SECS. 809.2 & 809.4.
 PLEASE NOTE THE EXCEPTION UNDER 233.3.1 WHICH COULD BE
 APPLICABLE TO THE ENTIRE NEIGHBORHOOD RENAISSANCE
 PROJECT AS A WHOLE:
  
 EXCEPTION: WHERE FACILITIES CONTAIN 15 OR FEWER
 RESIDENTIAL DWELLING UNITS, THE REQUIREMENTS OF
 233.3.1.1 AND 233.3.1.2 SHALL APPLY TO THE TOTAL NUMBER
 OF RESIDENTIAL DWELLING UNITS THAT ARE CONSTRUCTED
 UNDER A SINGLE CONTRACT, OR ARE DEVELOPED AS A WHOLE,
 WHETHER OR NOT LOCATED ON A COMMON SITE.
  
 CONCERNING THE PLUMBING REVIEW, THE BATHROOM IN THE
 UNIT THAT MUST MEET COMPLIANCE SHALL BE DESIGNED IN
 ACCORDANCE WITH 809.4. SEC. 809.4 REFERS THE DESIGNER
 TO SECS. 603-610 FOR TOILET AND BATHING FIXTURE
 INSTALLATIONS. BECAUSE 809.2 REQUIRES THE SELECTED UNIT
 TO BE ON AN ACCESSIBLE ROUTE IT APPEARS THE UNIT
 MEETING COMPLIANCE SHALL BE ON THE GROUND FLOOR. PLEASE
 PROVIDE AN ENLARGED DRAWING OF THE SELECTED UNIT
 INDICATING COMPLIANCE WITH THE FOLLOWING LIST OF FBC
 ACC COMPLIANCES:
  
 A) SEC. 603.2.1: PROVIDE A TURNING SPACE IN THE
 BATHROOM COMPLYING WITH SEC. 304.
 B) SEC. 603.3 SHOW THE HEIGHT OF THE MIRROR AT THE
 LAVATORY TO BE INSTALLED WITH THE REFLECTIVE SURFACE 40
 INCHES MAXIMUM FOR THE FINISHED FLOOR.
 C) SEC. 604.3: CLEARANCE AROUND THE WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURE PERPENDICULAR
 FOR THE REAR WALL. PROVIDE A 60 IN. WIDE X 56 IN. CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE WATER
 CLOSETS. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
 LOCATED WITHIN THE REQUIRED CLEARANCE, HOWEVER THERE IS
 AN EXCEPTION WHICH ALLOWS A LAVATORY SHALL BE PERMITTED
 ON THE REAR WALL 18 INCHES MINIMUM FROM THE
 D) SEC. 606.2: A 30 INCHES X 48 INCHES CLEAR FLOOR
 SPACE POSITIONED FOR A FORWARD APPROACH IS REQUIRED FOR
 THE LAVATORY. KNEE AND TOE CLEARANCES ARE REQUIRED
 HOWEVER PLEASE NOTE EXCEPTION 3 A, B, & C WHICH ALLOWS
 FOR REMOVABLE CABINETRY AT THE LAVATORY.
 E) SEC. 604.2: SHOW THE CENTERLINE OF THE WATER CLOSET
 TO BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE
 SIDE WALL.
 F) SEC. 604.4 EXCEPTION 2: SHOW THE HEIGHT OF THE WATER
 CLOSET 15 INCHES MINIMUM AND INCHES MAXIMUM FROM THE
 FINISHED FLOOR.
 G) SEC. 604.5 EXCEPTION 2: SHOW LOCATIONS, LENGTHS, AND
 MOUNTING HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS-
 SECS. 604.5 & 609.4, FIGURES 604.5.1 & 604.5.2, OR
 PROVIDE REINFORCEMENT LOCATIONS FOR FUTURE
 INSTALLATIONS PER EXCEPTION 2
 H) SEC. 604.7: SHOW THE CENTERLINE OF THE TOILET PAPER
 DISPENSER TO BE LOCATED 7 INCHES MINIMUM TO 9 INCHES
 MAXIMUM FROM THE FRONT OF THE WATER CLOSET TO THE
 CENTERLINE OF THE DISPENSER.
 I) SEC. 606.3: SHOW THE HEIGHT OF THE LAVATORY SINK RIM
 OR COUNTER SURFACE TO BE MAXIMUM 34 INCHES FROM THE
 FINISHED FLOOR UNLESS MEETING EXCEPTION 2 WHICH ALLOWS
 THE HEIGHT TO BE 29-36 INCHES WHERE THE PLUMBING ROUGH
 IN LOCATIONS ALLOW FOR A SINK AT A HEIGHT OF 29 INCHES.
 J) SEC. 607.2: SHOW THE CLEAR FLOOR SPACE FOR THE
 BATHTUB TO EXTEND THE LENGTH OF THE BATHTUB AND 30
 INCHES WIDE MINIMUM. A LAVATORY COMPLYING WITH SEC. 606
 IS PERMITTED AT THE CONTROL END OF THE CLEARANCE.
 K) SEC. 607.3: SHOW EITHER A PERMANENT SEAT AT THE HEAD
 OF THE TUB OR A REMOVABLE SEAT SHALL BE PROVIDED.
 PLEASE SEE SECS. 607.4.1- 607.4.2.3.
 L) SEC. 607.4: SHOW GRAB LOCATIONS IN COMPLIANCE WITH
 SEC. 607.4.1- 607.4.1.2 UNLESS INSTALLING
 REINFORCEMENTS IN ACCORDANCE WITH EXCEPTION 2.
 M) SEC. 607.5: SHOW THE BATHTUB CONTROLS LOCATION.
  
  
 3) SHEET A-10.1: PLEASE SHOW THE CLEAR FLOOR DIAGRAMS
 FOR THE BATHTUBS AS SHOWN ON PAGE 7.53 FHHA MANUAL. IT
 APPEARS THE BATHROOMS ARE DESIGNED AS SPEC A TYPES
 BECAUSE SPEC B REQUIRES A 30X48-INCH CLEAR FLOOR SPACE
 PARALLEL TO THE TUB AND FLUSH WITH THE CONTROL WALL.
  
 4) A-10.1: REFER TO PAGES 6.3- 6.9 OF THE FHDA MANUAL
 AND SHOW THE MINIMUM HEIGHT OF THE WATER CLOSET AND
 BATHTUB REINFORCEMENTS WILL BE 38-INCHES MINIMUM FROM
 THE FINISHED FLOORS.
  
 5) P-1: BASED ON TABLE 403.1 PLUMBING FIXTURES WILL BE
 REQUIRED IN THE GYM-RECREATIONAL SEPARATE TENANT SPACE
 SHOWN ON THE FLOOR PLANS. PLEASE REVISE THE DRAWINGS TO
 SHOW THE LOCATION OF THE UNDERGROUND BUILDING DRAIN IN
 THE SPACE, THE DRAIN RUN TO POINT OF CONNECTION TO THE
 SEWER, EXTERIOR AND INTERIOR CLEANOUT LOCATIONS, AND
 INTERIOR CAP FOR FUTURE ACCESS- SEC. 107.2.1 WPB.
  
 6) P-6: THE PLANS DO NOT SHOW THE WATER HEATER DRAIN
 PAN LINE RUNS AND DISCHARGE LOCATIONS. PLEASE PROVIDE
 DETAILS IN COMPLIANCE WITH SECS. 504.7.1 & 504.7.2 FBC
 P.
  
 7) P-6: PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 WATER HEATERS SHOWING THE MAKES AND MODELS, GALLON
 SIZES, AND EFFICIENCY RATINGS TO MATCH WITH THE DATA
 LISTED ON THE SUBMITTED ENERGY COMPLIANCE FORMS- TABLE
 C404.2 FBC EC. THE WATER HEATERS SPECIFICATIONS CAN BE
 DEFERRED SUBMITTALS IF PREFERRED- SEE SEC. 107.3.4.1
 WPB.
  
 8) P-2: PLEASE PROVIDE A STORM DRAIN ISOMETRIC DRAWING
 SHOWING THE VERTICAL AND HORIZONTAL PIPING RUNS AND
 SIZES FROM THE ROOF DRAINS TO DISCHARGE LOCATIONS- SEC.
 107.3.5.1.3 (7) WPB, AND SECS. 1101.2, 1106.2 & 1106.3
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-18 Cont ID  
Sent By jesmith Date 2023-01-18 Time 13:39 Rev Time 0.00
Received By jesmith Date 2023-01-17 Time 16:26 Sent To  
Notes
2023-01-18 13:37:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FHA=FAIR HOUSING ACT DESIGN MANUAL
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22100740 2212 N TAMARIND AVE
  
 A SEPARATE PERMIT FOR THE BACKFLOW PREVENTER IS
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A
 SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE
 SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED.
 AFTER YOU HAVE THE PERMIT GENERATED, PLEASE NOTIFY ME
 AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS
 EXAMINER AT [email protected] AND RYAN BROWN, CHIEF
 PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH
 THE PERMIT NUMBER.
  
  
 1. A01: OCCUPANCY IS NOTED AS MIXED USE-COMMERCIAL/R-2
 RESIDENTIAL. BUILDING "A" FIRST FLOOR NOTES ONE (1) 3
 BEDROOM APARTMENT AND RETAIL WITH 1,144 SQ. FT. FBC
 303.4 SHOWS THIS SPACE AS ASSEMBLY GROUP A-3 GYMNASIUM.
 PLEASE PROVIDE OCCUPANT LOAD AND MINIMUM PLUMBING
 FIXTURES AS WOULD BE REQUIRED IN ACCORDANCE WITH FBC PL
 403.1 AND TABLE 403.1 FOR THIS SPACE. INCLUDE ANY
 ACCESSIBILITY REQUIREMENTS IN ACCORDANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6.
  
  
 2. PLAN SHEET A10 BATHROOM: SPECIFY AND PROVIDE WALL
 REINFORCEMENT FOR GRAB BARS IN THE BATHROOMS FOR WATER
 CLOSET AND BATHTUB; COMPLY WITH FHA CHAPTERS 6 AND 7B.
  
  
 3. PLAN SHEET P05/GENERAL PLUMBING NOTES: NOTE CALLS
 FOR ADDING A RECIRCULATING PUMP TO WATER HEATER.
 DRAWINGS DO NOT INDICATE RECIRCULATED HOT WATER. PLEASE
 CLARIFY. IF RECIRCULATING SYSTEMS ARE REQUIRED, PROVIDE
 PLANS, PUMP SPECIFICATION/SCHEDULE AND DETAIL.
  
  
 4.PLAN SHEET P06/WATER HEATER DETAIL/WATER HEATER
 NOTES:
 ***A) NOTE AT DETAIL INDICATES T&P RELIEF VALVE
 DISCHARGE TO THE EMERGENCY PAN; PAN DRAIN TO EXTERIOR
 TERMINATING MINIMUM 12 INCHES FROM BUILDING. PLEASE
 CLARIFY; WILL THIS BE A DEDICATED LINE TO POINT OF
 TERMINATION OR CONNECT TO A COMMON DRAIN DISCHARGING TO
 POINT OF TERMINATION. PLEASE NOTE AND SHOW ROUTING AND
 SIZE ON PLAN.
 ***B) NOTE REQUIRES TEMPERATURE LIMITING DEVICE
 CONFORMING TO ASSE 1070 AT ALL LAVATORIES AND HAND
 SINKS. FBC RES AND FBC PL CODES DO NOT REQUIRE THIS
 (SEE FBC PL 419.5). HOWEVER, PER FBC RES P2601.1 AND
 FBC PL 607.1.1, 613.1, A TEMPERATURE-ACTUATED MIXING
 VALVE COMPLYING WITH ASSE 1017 IS REQUIRED AT THE WATER
 HEATER.
  
  
 5. PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE AND A
 WATER HEATER EQUIPMENT SCHEDULE ON THE PLUMBING PLANS.
 FBC RES P2601.1, WPB FBC 107.2.1, WPB FBC
 107.3.5.1.3(2)(5), FBC PL CHAPTER 4, CHAPTER 5.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2023-06-21 Cont ID  
Sent By rmcphers Date 2023-06-21 Time 14:12 Rev Time 0.00
Received By rmcphers Date 2023-06-21 Time 14:12 Sent To  
Notes
2023-06-21 14:12:32ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2023-05-01 Cont ID  
Sent By rmcphers Date 2023-05-01 Time 13:54 Rev Time 0.00
Received By rmcphers Date 2023-05-01 Time 13:54 Sent To  
Notes
2023-05-01 13:55:48SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By rmcphers Date 2023-01-23 Time 10:44 Rev Time 0.00
Received By rmcphers Date 2023-01-23 Time 10:44 Sent To  
Notes
2023-01-23 10:44:57SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-07-10 Cont ID  
Sent By rmcphers Date 2023-07-10 Time 10:25 Rev Time 0.00
Received By rmcphers Date 2023-07-10 Time 10:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-21 Cont ID  
Sent By rmcphers Date 2023-06-21 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2023-06-21 Time 14:48 Sent To  
Notes
2023-06-20 11:34:15PLUMBING DIGITAL SIGNATURES PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-01 Cont ID  
Sent By rmcphers Date 2023-05-01 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2023-05-01 Time 14:05 Sent To  
Notes
2023-05-01 14:12:08SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE CIVIL DRAWINGS FROM RICHARD REIKENIS P.E. DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-23 Cont ID  
Sent By rmcphers Date 2023-01-23 Time 11:01 Rev Time 0.00
Received By rmcphers Date 2023-01-23 Time 10:58 Sent To  
Notes
2023-01-18 09:40:37MECHANICAL DIGITAL SIGNATURES APPROVED ME
  
2023-01-18 08:57:14DIGITAL SIGNATURES FOR PLUMBING PLANS ARE APPROVED. JS

Review Stop Z ZONING
Rev No 4 Status P Date 2023-06-22 Cont ID  
Sent By jlswaby Date 2023-06-22 Time 17:14 Rev Time 0.00
Received By jlswaby Date 2023-06-22 Time 17:13 Sent To  
Notes
2023-06-22 17:14:00REVIEWED BY:
  
 JERMAINE SWABY
 SENIOR PLANNER
 561-822-1431
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-05-17 Cont ID  
Sent By Vbroglia Date 2023-05-16 Time 17:25 Rev Time 0.00
Received By jlswaby Date 2023-05-17 Time 09:13 Sent To  
Notes
2023-05-16 17:24:41PLEASE TO REVIEW THE ELEVATION DIMENSIONS.
  
 CONDITION OF C.O
  
 SEPARATE PERMIT REQUIRED FOR:
 FENCE/WALL, AWNINGS, SIGNS, PARKING LOT, GENERATOR,
 MECHANICAL/AC/POOL EQUIPMENT, DUMPSTER ENCLOSURE,
 IRRIGATION, LANDSCAPE, OTHER. IF APPLICABLE
  
  
 JERMAINE SWABY
 SENIOR PLANNER
 [email protected]
 561-822-1431

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By jswaby Date 2023-05-10 Time   Rev Time 0.00
Received By   Date 2023-05-10 Time   Sent To  
Notes
2023-05-10 15:51:54REFER TO PREVIOUS COMMENT.
  
 AS PER THE SITE PLAN APPROVAL LETTER ISSUED FOR ISPR
 CASE NO. 21???14, PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT THE HEIGHT OF THE BUILDING SHALL BE REVISED SUCH
 THAT THE TOP OF THE ROOF SHALL NOT EXCEED 30 FEET, AS
 MEASURED FROM THE AVERAGE ELEVATION OF THE FINISHED
 GRADE OF THE STRUCTURE TO THE HIGHEST POINT OF THE
 TOP OF THE STRUCTURE OF A FLAT ROOF.

Review Stop Z ZONING
Rev No 1 Status F Date 2023-02-21 Cont ID  
Sent By JRoach Date 2023-02-21 Time 14:29 Rev Time 0.00
Received By jlswaby Date 2023-05-05 Time 15:01 Sent To  
Notes
2023-02-21 14:32:00AS PER THE SITE PLAN APPROVAL LETTER ISSUED FOR ISPR
 CASE NO. 21-14, PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT THE HEIGHT OF THE BUILDING SHALL BE REVISED SUCH
 THAT THE TOP OF THE ROOF SHALL NOT EXCEED 30 FEET, AS
 MEASURED FROM THE ???AVERAGE ELEVATION OF THE FINISHED
 GRADE OF THE STRUCTURE??? TO THE HIGHEST POINT OF THE
 TOP OF THE STRUCTURE OF A FLAT ROOF; ADDITIONAL HEIGHT
 FOR THE PARAPET SHALL BE PERMITTED IN ACCORDANCE WITH
 SEC. 94-306(A) OF THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 PLEASE BE AWARE OF ALL OF THE OTHER CONDITIONS OF
 APPROVAL ASSOCIATED WITH ISPR 21-14 AND THEIR
 RESPECTIVE TIMEFRAMES.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  