Plan Review Details - Permit 22100624
Plan Review Stops For Permit 22100624
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 12:59 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-31 Cont ID  
Sent By jwitmer Date 2023-01-31 Time 15:49 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-14 Cont ID  
Sent By jwitmer Date 2022-12-14 Time 11:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-12-14 11:25:07WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22100624
 ADD: 2000 PRESIDENTIAL WAY # 1501
 CONT: DFM LTD CO
 TEL: 561-308-9799
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. DEC. 14TH/2022
 ACTION: DENIED
  
 1) THE PROPOSED FLOOR PLAN MATER BATH INDICATES THE
 REMOVAL OF TUB AND CONVERT TO SHOWER.
 1A) COMPLIED, 8X12 HOLE IN SLAB FOR DRAIN.
  
 1B) 2ND REQUEST. CONCRETE INFILL HAS NOT BEEN A TESTED
 ASSEMBLY, PLEASE SUBMIT A TESTED THROUGH PENETRATION
 FIRESTOP SYSTEM INSTALLED IN ACCORDANCE WITH ASTM E814
 OR UL 1479. THE SYSTEM SHALL HAVE AN F RATING / T
 RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR PENETRATED.
 ALSO SHEET 7 OF 7. THROUGH-PENETRATIONS FIRESTOP
 SYSTEMS (HORIZONTAL ASSEMBLIES). IF A NEW FLOOR
 PENETRATION IS MADE FOR THE FUTURE SHOWER DRAIN, THEN
 YOU NEED TO SHOW COMPLIANCE WITH THE 2020 FBC-B SECTION
 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS SHALL BE
 PROTECTED BY A THROUGH PENETRATION FIRESTOP SYSTEM
 INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL 1479. THE
 SYSTEM SHALL HAVE AN F RATING / T RATING OF NOT LESS
 THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED RATING OF
 THE FLOOR PENETRATED.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2022-11-29 Time   Rev Time  
Received By   Date 2022-11-29 Time   Sent To  
Notes
2022-11-29 13:06:19WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22100624
 ADD: 2000 PRESIDENTIAL WAY # 1501
 CONT: DFM LTD CO
 TEL: 561-308-9799
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 29/2022
 ACTION: DENIED
 1) THE PROPOSED FLOOR PLAN MATER BATH INDICATES THE
 REMOVAL OF TUB AND CONVERT TO SHOWER.
 1A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1B) ALSO SHEET 4 OF 4. THROUGH-PENETRATIONS FIRESTOP
 SYSTEMS (HORIZONTAL ASSEMBLIES). IF A NEW FLOOR
 PENETRATION IS MADE FOR THE FUTURE SHOWER DRAIN, THEN
 YOU NEED TO SHOW COMPLIANCE WITH THE 2020 FBC-B SECTION
 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS SHALL BE
 PROTECTED BY A THROUGH PENETRATION FIRESTOP SYSTEM
 INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL 1479. THE
 SYSTEM SHALL HAVE AN F RATING / T RATING OF NOT LESS
 THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED RATING OF
 THE FLOOR PENETRATED.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-11-02 Cont ID  
Sent By jleahy Date 2022-11-02 Time 16:27 Rev Time 0.00
Received By jleahy Date 2022-11-02 Time 16:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-18 Cont ID  
Sent By cwalker Date 2023-01-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-01-18 08:49:35FIRE PROVISO COMMENT:
  
 ANY MODIFICATIONS TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE PERFORMED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-18 Cont ID  
Sent By cwalker Date 2022-10-18 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-10-18 11:01:22FIRE PROVISO COMMENT:
  
 ANY MODIFICATIONS TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE PERFORMED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-01-31 Time   Rev Time 0.00
Received By aoliver Date 2023-01-17 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-12-14 Time   Rev Time 0.00
Received By rmcdouga Date 2022-12-13 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-11-29 Time   Rev Time 0.00
Received By cdecoeur Date 2022-10-17 Time 06:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-10-26 Cont ID  
Sent By ccole Date 2022-10-26 Time 15:38 Rev Time 0.00
Received By ccole Date 2022-10-26 Time 15:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-19 Cont ID  
Sent By mpeterso Date 2023-01-19 Time 11:10 Rev Time 0.00
Received By mpeterso Date 2023-01-19 Time 11:09 Sent To  
Notes
2023-01-19 11:11:001/19/23 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-13 Cont ID  
Sent By rmcdouga Date 2022-12-13 Time 15:18 Rev Time 0.00
Received By rmcdouga Date 2022-12-13 Time 15:18 Sent To  
Notes
2022-12-13 15:27:23SIGNED AND SEALED PLANS SENT TO STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By rwbrown Date 2022-11-16 Time 05:39 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
2022-11-16 05:40:50 
 SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]