Plan Review Details - Permit 22100607
Plan Review Stops For Permit 22100607
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By cpuell Date 2022-12-07 Time 14:52 Rev Time 0.00
Received By cpuell Date 2022-12-07 Time 14:52 Sent To  
Notes
2022-12-07 14:52:38WORK IS FOR THE NORTH BLDG ONLY

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-10-20 Cont ID  
Sent By cpuell Date 2022-10-20 Time 07:26 Rev Time 0.00
Received By cpuell Date 2022-10-20 Time 07:26 Sent To  
Notes
2022-10-20 07:27:09TWO BUILDINGS ON THE PROPERTY, IS THE WORK FOR THE
 NORTH OR SOUTH BUILDING? PLEASE RESPONDL TO
 [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-07-05 Cont ID  
Sent By jgomez Date 2023-07-05 Time 09:31 Rev Time 0.00
Received By jgomez Date 2023-07-05 Time 09:30 Sent To  
Notes
2023-07-05 09:37:35ROOFING FIFTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100607
 415 31ST ST
  
 ORIGINAL COMMENT:
 1-ENGINEER'S LETTER SUBMITTED IS FOR "STRUCTURAL
 INVESTIGATION OF EXISTING SHINGLE ROOF SYSTEM TO BE
 REPLACED WITH ASPHALTIC SHINGLE AT THE RESIDENCE BELOW
 415 31ST STREET, WEST PALM BEACH, FLORIDA 33404".
 A) THE ENGINEER REPORT DOESN'T PROVIDE THE REQUESTED
 INFORMATION FOR THE ROOF TO WALL CONNECTIONS. THE ROOF
 TO WALL CONNECTIONS SHALL BE IMPROVED AS REQUIRED BY
 SEC. 706.8 FBC-EXISTING BUILDING. ENGINEER TO READ SEC.
 706.8 FBC-EXISTING BUILDING AND PROVIDE REQUIRED
 INFORMATION. SPECIFY STRAPS AS REQUIRED.
 NOTE: BUILDING WAS BUILT IN 1926. ROOF TO WALL
 CONNECTIONS NEED TO MEET OR EXCEED CURRENT CODE
 STANDARDS.
  
  
  
 PREVIOUS COMMENT:
 1- ROOF TO WALL CONNECTION INSPECTION AND CERTIFICATION
 FROM ANDRE BIGATAO, P.E. SUBMITTED NEED TO BE MORE
 SPECIFIC AND PROVIDE MORE INFORMATION.
  
 A)ENGINEER NEEDS TO SPECIFY THE DATE OF INSPECTION, WHO
 MADE THE INSPECTION, HOW THE ROOF WAS ACCESSED TO VIEW
 THE CONNECTIONS OF THE HIP RAFTER ("KING JACK") TO THE
 HIP GIRDER WITH STRAPS HAVING AT LEAST FOUR FASTENERS
 ON EACH END AND ON EACH CORNER OF THE BUILDING. PROVIDE
 PHOTOS SHOWING THE CONNECTIONS.
 SEC. 706.8.1FBC-EXISTING BUILDING. SEC. 107.2.1.2 CITY
 AMENDMENTS.
 (LETTER SUBMITTED WAS REVIEWED WITH BUILDING OFFICIAL).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 B) ENGINEER INSPECTION LETTER STATES "OUR INSPECTION
 REVEALED THE ROOF TO WALL CONNECTION IS USED FOR THE
 ROOF CONNECTION AT THIS PROPERTY HAVE A MINIMUM OF 4
 FASTERS PER STRAP AND COMPLY WITH 2020 FLORIDA BUILDING
 CODE 7TH EDITION, SECTION 706.8.1 FOR EXISTING
 BUILDINGS."
 THIS STATEMENT ONLY SPECIFIES 4 FASTENERS PER STRAP. IT
 DOESN'T SPECIFY FOUR FASTENERS ON EACH END OF THE STRAP
 AS REQUIRED BY SEC. 706.8.1FBC-EXISTING BUILDING.
 CLARIFY AS REQUIRED AND PROVIDE PHOTOS SHOWING THE
 CONNECTIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 PHOTOS SHOWING THE CONNECTIONS WEERE NOT PROVIDED.
  
 PREVIOUS COMMENT:
 C)CLARIFY WHY SUBMITTING SUB-PERMIT APPLICATION FOR
 ROOF TO WALL CONNECTIONS IF ENGINEER ROOF TO WALL
 CONNECTION INSPECTION AND CERTIFICATION IS STATING THAT
 THE EXISTING STRAPS COMPLY WITH 2020 FLORIDA BUILDING
 CODE.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-21 Cont ID  
Sent By jgomez Date 2023-06-21 Time 11:13 Rev Time 0.00
Received By jgomez Date 2023-06-20 Time 17:18 Sent To  
Notes
2023-06-21 11:13:52ROOFING FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100607
 415 31ST ST
  
 PREVIOUS COMMENT:
 1-ENGINEER'S LETTER SUBMITTED IS FOR "STRUCTURAL
 INVESTIGATION OF EXISTING SHINGLE ROOF SYSTEM TO BE
 REPLACED WITH ASPHALTIC SHINGLE AT THE RESIDENCE BELOW
 415 31ST STREET, WEST PALM BEACH, FLORIDA 33404".
 A) THE ENGINEER REPORT DOESN'T PROVIDE THE REQUESTED
 INFORMATION FOR THE ROOF TO WALL CONNECTIONS. THE ROOF
 TO WALL CONNECTIONS SHALL BE IMPROVED AS REQUIRED BY
 SEC. 706.8 FBC-EXISTING BUILDING. ENGINEER TO READ SEC.
 706.8 FBC-EXISTING BUILDING AND PROVIDE REQUIRED
 INFORMATION. SPECIFY STRAPS AS REQUIRED.
 NOTE: BUILDING WAS BUILT IN 1926. ROOF TO WALL
 CONNECTIONS NEED TO MEET OR EXCEED CURRENT CODE
 STANDARDS.
  
 RESPONSE:
 ROOF TO WALL CONNECTION INSPECTION AND CERTIFICATION
 FROM ANDRE BIGATAO, P.E. SUBMITTED NEED TO BE MORE
 SPECIFIC AND PROVIDE MORE INFORMATION.
  
 A)ENGINEER NEEDS TO SPECIFY THE DATE OF INSPECTION, WHO
 MADE THE INSPECTION, HOW THE ROOF WAS ACCESSED TO VIEW
 THE CONNECTIONS OF THE HIP RAFTER ("KING JACK") TO THE
 HIP GIRDER WITH STRAPS HAVING AT LEAST FOUR FASTENERS
 ON EACH END AND ON EACH CORNER OF THE BUILDING. PROVIDE
 PHOTOS SHOWING THE CONNECTIONS.
 SEC. 706.8.1FBC-EXISTING BUILDING. SEC. 107.2.1.2 CITY
 AMENDMENTS.
 (LETTER SUBMITTED WAS REVIEWED WITH BUILDING OFFICIAL).
  
 B) ENGINEER INSPECTION LETTER STATES "OUR INSPECTION
 REVEALED THE ROOF TO WALL CONNECTION IS USED FOR THE
 ROOF CONNECTION AT THIS PROPERTY HAVE A MINIMUM OF 4
 FASTERS PER STRAP AND COMPLY WITH 2020 FLORIDA BUILDING
 CODE 7TH EDITION, SECTION 706.8.1 FOR EXISTING
 BUILDINGS."
 THIS STATEMENT ONLY SPECIFIES 4 FASTENERS PER STRAP. IT
 DOESN'T SPECIFY FOUR FASTENERS ON EACH END OF THE STRAP
 AS REQUIRED BY SEC. 706.8.1FBC-EXISTING BUILDING.
 CLARIFY AS REQUIRED AND PROVIDE PHOTOS SHOWING THE
 CONNECTIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 C)CLARIFY WHY SUBMITTING SUB-PERMIT APPLICATION FOR
 ROOF TO WALL CONNECTIONS IF ENGINEER ROOF TO WALL
 CONNECTION INSPECTION AND CERTIFICATION IS STATING THAT
 THE EXISTING STRAPS COMPLY WITH 2020 FLORIDA BUILDING
 CODE.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-05-30 Cont ID  
Sent By jgomez Date 2023-05-30 Time 17:40 Rev Time 0.00
Received By jgomez Date 2023-05-30 Time 16:07 Sent To  
Notes
2023-05-30 17:40:40ROOFING THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100607
 415 31ST ST
  
  
 NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOF TO
 WALL CONNECTIONS. THIS WORK CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSESSES
 THE PROPER LICENSE TO PERFORM THIS WORK.
  
  
 PREVIOUS COMMENT FROM PRIOR PLAN REVIEWER:
 1. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED/REVISED SUBMITTED
 ENGINEER'S STRUCTURAL INVESTIGATION LETTER TO PROVIDE
 EXISTING ROOF-TO-WALL LOAD PATH CONNECTION ANALYSIS
 SHOWING COMPLIANCE WITH WIND LOADS IN TABLE 706.8.1 &
 VALIDATED BY A LICENSED FLORIDA DESIGN PROFESSIONAL.
 SECOND REQUEST.
  
 RESPOSNE:
 ENGINEER'S LETTER SUBMITTED IS FOR "STRUCTURAL
 INVESTIGATION OF EXISTING SHINGLE ROOF SYSTEM TO BE
 REPLACED WITH ASPHALTIC SHINGLE AT THE RESIDENCE BELOW
 415 31ST STREET, WEST PALM BEACH, FLORIDA 33404".
  
 A) THE ENGINEER REPORT DOESN'T PROVIDE THE REQUESTED
 INFORMATION FOR THE ROOF TO WALL CONNECTIONS. THE ROOF
 TO WALL CONNECTIONS SHALL BE IMPROVED AS REQUIRED BY
 SEC. 706.8 FBC-EXISTING BUILDING. ENGINEER TO READ SEC.
 706.8 FBC-EXISTING BUILDING AND PROVIDE REQUIRED
 INFORMATION. SPECIFY STRAPS AS REQUIRED.
 NOTE: BUILDING WAS BUILT IN 1926. ROOF TO WALL
 CONNECTIONS NEED TO MEET OR EXCEED CURRENT CODE
 STANDARDS.
  
 B) THE ADDRESS SPECIFIED ON THE ENGINEER'S LETTER IS
 INCORRECT. THE CORRECT ZIP CODE IS 33407 NOT 33404.
 REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C)ENGINEER'S DIGITAL SIGNATURE COMMENTS:
 (1) REPORT SUBMITTED HAVE AN ENGINEER'S SELF CERTIFIED
 DIGITAL SIGNATURE. ENGINEER CAN NOT SELF CERTIFY THE
 DIGITAL SIGNATURE. THIRD PARTY CERTIFICATION IS
 REQUIRED BY FAC 61G15-23.004. (NOTE: ENGINEER TO
 CONTACT THE BOARD OF ENGINEER'S FOR SELF CERTIFIED
 DIGITAL SIGNATURE QUESTIONS).
 NOTE: PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH
 VERIFIABLE DIGITAL SIGNATURE.
  
 (2) ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH
 THE REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH
 THE TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/... AND REVISE DIGITAL SIGNATURE AS REQUIRED.
  
 SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-24 Cont ID  
Sent By jbrooks Date 2023-04-24 Time 13:05 Rev Time 0.00
Received By jbrooks Date 2023-04-24 Time 08:07 Sent To  
Notes
2023-04-24 13:05:55JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED/REVISED SUBMITTED
 ENGINEER???S STRUCTURAL INVESTIGATION LETTER TO PROVIDE
 EXISTING ROOF-TO-WALL LOAD PATH CONNECTION ANALYSIS
 SHOWING COMPLIANCE WITH WIND LOADS IN TABLE 706.8.1 &
 VALIDATED BY A LICENSED FLORIDA DESIGN PROFESSIONAL.
 SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-20 Cont ID  
Sent By jbrooks Date 2022-10-20 Time 09:55 Rev Time 0.00
Received By jbrooks Date 2022-10-20 Time 07:54 Sent To  
Notes
2022-10-20 09:55:21JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL
 SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH
 NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS.
 PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT
 INDICATE ON ROOF DRAWING/SKETCH).
 2. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-04-24 Cont ID  
Sent By fmittner Date 2023-04-24 Time 14:05 Rev Time 0.00
Received By fmittner Date 2023-04-24 Time 14:00 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By amhamilt Date 2022-12-07 Time 14:21 Rev Time 0.00
Received By amhamilt Date 2022-12-07 Time 14:21 Sent To  
Notes
2022-12-07 14:22:06VERIFIED EXISTING ROOF MATERIAL SHINGLE
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By amhamilt Date 2022-11-17 Time 12:04 Rev Time 0.00
Received By amhamilt Date 2022-11-17 Time 12:04 Sent To  
Notes
2022-11-17 12:05:01THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE VERIFY THAT EXISTING ROOFING MATERIAL IS
 SHINGLE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-07-05 Cont ID  
Sent By jgomez Date 2023-07-05 Time 09:39 Rev Time 0.00
Received By jgomez Date 2023-07-05 Time 09:30 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-21 Cont ID  
Sent By jgomez Date 2023-06-21 Time 11:20 Rev Time 0.00
Received By jgomez Date 2023-06-14 Time 10:24 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-30 Cont ID  
Sent By jgomez Date 2023-05-30 Time 17:49 Rev Time 0.00
Received By jgomez Date 2023-05-24 Time 12:07 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-25 Cont ID  
Sent By aoliver Date 2023-04-25 Time 07:52 Rev Time 0.00
Received By aoliver Date 2023-04-14 Time 08:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-18 Cont ID  
Sent By lmarchan Date 2022-11-18 Time 13:04 Rev Time 0.00
Received By lmarchan Date 2022-10-19 Time 06:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-21 Cont ID  
Sent By jgomez Date 2023-06-21 Time 11:16 Rev Time 0.00
Received By jgomez Date 2023-06-21 Time 11:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-30 Cont ID  
Sent By jgomez Date 2023-05-30 Time 17:48 Rev Time 0.00
Received By jgomez Date 2023-05-30 Time 17:48 Sent To  
Notes
2023-05-30 17:49:37SIGNATURE REVIEW:
  
 1-ENGINEER'S DIGITAL SIGNATURE COMMENTS:
 A) REPORT SUBMITTED HAVE AN ENGINEER'S SELF CERTIFIED
 DIGITAL SIGNATURE. ENGINEER CAN NOT SELF CERTIFY THE
 DIGITAL SIGNATURE. THIRD PARTY CERTIFICATION IS
 REQUIRED BY FAC 61G15-23.004. (NOTE: ENGINEER TO
 CONTACT THE BOARD OF ENGINEER'S FOR SELF CERTIFIED
 DIGITAL SIGNATURE QUESTIONS).
 NOTE: PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH
 VERIFIABLE DIGITAL SIGNATURE.
  
 B) ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/.... AND REVISE DIGITAL SIGNATURE AS REQUIRED.
  
 SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-24 Cont ID  
Sent By jbrooks Date 2023-04-24 Time 13:04 Rev Time 0.00
Received By jbrooks Date 2023-04-24 Time 13:04 Sent To  
Notes
2023-04-24 13:04:45JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 PENDING REVISED ENGINEER???S LETTER
 SUBMITTED SIGNED AND SEALED ENGINEER???S LETTER CAN NOT
 BE THIRD PARTY VERIFIED.
 FS 668.003. NOTICE: FLORIDA PROFESSIONAL ENGINEERS MAY
 NOT SELF CERTIFY DIGITAL SIGNATURES AND SEALS. PLEASE
 UPLOAD A VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO
 PROJECTDOX
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  