| 2022-12-21 07:36:31 | 2ND GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | THIS REVIEW GOES ALONG WITH REVISION 22090996 |
| | |
| | 1. ---- |
| | |
| | 2. COMMENT NOT ADDRESSED --- |
| | 2017 WPB AMENDS 107.2.1 - THE GENERATOR YOU'VE ADDED |
| | SHOWS A BTU VALUE OF 10K. A 10K BTU GENERATOR SEEMS |
| | UNUSUAL. CAN YOU PLEASE SHOW ME THE SPECIFICATIONS FOR |
| | THE GENERATOR. |
| | |
| | 3. COMMENT NOT ADDRESSED --- |
| | PLEASE ADDRESS COMMENTS ON REVISION 22090996 AS WELL. |
| | |
| | 4. 2020 FRC G2413.3 (402.3) - YOU'VE SUPPLIED A SIZING |
| | CHART THAT IS FOR CSST, BUT THE GAS LINE IS POLY. ALSO, |
| | THAT CHART IS A 5 PSI CHART WITH A 3.5 PSI DROP, WHICH |
| | IS NOT HEARD OF IN RESIDENTIAL. PLEASE SHOW THE YOU ARE |
| | GOING TO HAVE A 5 PSI METER BY SUBMITTING A LETTER FROM |
| | FPU. ALSO, ON YOUR DRAWING, YOU'VE SHOWN THE LINE FOR |
| | THE 221K LOAD AT .5 PSI. THE SIZING IS OFF. THE LOADS |
| | ARE OFF. TANKLESS WATER HEATERS ARE LIMITED TO 199K |
| | BTU. TOO MANY INACCURACIES TO REVIEW THIS PLAN. |
| | |
| | THIS IS NOT A COMPLETE REVIEW UNTIL THE REVISION IS |
| | ADDRESSED AND THE DRAWING IS CORRECTED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |