Plan Review Details - Permit 22100569
Plan Review Stops For Permit 22100569
Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-12-21 Cont ID  
Sent By rwbrown Date 2022-12-21 Time 07:11 Rev Time 0.00
Received By rwbrown Date 2022-12-21 Time 07:11 Sent To  
Notes
2022-12-21 07:36:312ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 THIS REVIEW GOES ALONG WITH REVISION 22090996
  
 1. ----
  
 2. COMMENT NOT ADDRESSED ---
 2017 WPB AMENDS 107.2.1 - THE GENERATOR YOU'VE ADDED
 SHOWS A BTU VALUE OF 10K. A 10K BTU GENERATOR SEEMS
 UNUSUAL. CAN YOU PLEASE SHOW ME THE SPECIFICATIONS FOR
 THE GENERATOR.
  
 3. COMMENT NOT ADDRESSED ---
 PLEASE ADDRESS COMMENTS ON REVISION 22090996 AS WELL.
  
 4. 2020 FRC G2413.3 (402.3) - YOU'VE SUPPLIED A SIZING
 CHART THAT IS FOR CSST, BUT THE GAS LINE IS POLY. ALSO,
 THAT CHART IS A 5 PSI CHART WITH A 3.5 PSI DROP, WHICH
 IS NOT HEARD OF IN RESIDENTIAL. PLEASE SHOW THE YOU ARE
 GOING TO HAVE A 5 PSI METER BY SUBMITTING A LETTER FROM
 FPU. ALSO, ON YOUR DRAWING, YOU'VE SHOWN THE LINE FOR
 THE 221K LOAD AT .5 PSI. THE SIZING IS OFF. THE LOADS
 ARE OFF. TANKLESS WATER HEATERS ARE LIMITED TO 199K
 BTU. TOO MANY INACCURACIES TO REVIEW THIS PLAN.
  
 THIS IS NOT A COMPLETE REVIEW UNTIL THE REVISION IS
 ADDRESSED AND THE DRAWING IS CORRECTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rwbrown Date 2022-11-01 Time 06:23 Rev Time 0.00
Received By rwbrown Date 2022-11-01 Time 06:23 Sent To  
Notes
2022-11-01 06:29:561ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 THIS REVIEW GOES ALONG WITH REVISION 22090996
  
 1. 2017 WPB AMENDS 107.2.1 - THE PLANS YOU'VE SUBMITTED
 DO NOT SHOW THE DESCRIBED "DOUBLE OVENS" ON THE
 ISOMETRIC.
  
 2. 2017 WPB AMENDS 107.2.1 - THE GENERATOR YOU'VE ADDED
 SHOWS A BTU VALUE OF 10K. A 10K BTU GENERATOR SEEMS
 UNUSUAL. CAN YOU PLEASE SHOW ME THE SPECIFICATIONS FOR
 THE GENERATOR.
  
 3. PLEASE ADDRESS COMMENTS ON REVISION 22090996 AS
 WELL.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-22 Cont ID  
Sent By aoliver Date 2022-12-22 Time 13:51 Rev Time 0.00
Received By aoliver Date 2022-12-20 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rwbrown Date 2022-11-01 Time 06:31 Rev Time 0.00
Received By shill Date 2022-10-27 Time 10:01 Sent To  
Notes
2022-11-01 08:26:31[email protected]
  
 THIS IS A DIGITAL PROJECT. DO NOT SUBMIT PAPER PLANS AS
 IT CAUSES CONFUSION. ALL PLANS SHOULD BE UPLOADED TO
 PROJECTDOX AND REVIEWED THERE.
 TO RESOLVE THE DIGITAL SIGNATURE ISSUE, PLEASE HAVE THE
 ARCHITECT CREATE A DIGITAL SIGNATURE AND DIGITALLY SIGN
 THE PLANS. IF HE NEEDS ASSISTANCE PLEASE HAVE HIM
 CONTACT ME VIA EMAIL. ALSO REFER TO THE EMAIL THAT I
 SENT TO [email protected].
  
 BECAUSE THE SEAL IMAGE IS ILLEGIBLE, THE TITLE BLOCK
 FOR THE ARCHITECT DOES NOT COMPLY WITH FLORIDA STATUTE
 481, THE PRINTED NAME AND LICENSE NUMBER OF THE
 ARCHITECT IS TO BE ON EACH PAGE.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-12-21 Cont ID  
Sent By rwbrown Date 2022-12-21 Time 07:03 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-11-01 Cont ID  
Sent By rwbrown Date 2022-11-01 Time 06:23 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-03-02 Cont ID  
Sent By shill Date 2023-03-02 Time 08:36 Rev Time 0.00
Received By shill Date 2023-03-02 Time 08:36 Sent To  
Notes
2023-03-02 08:38:38DO NOT SUBMIT PAPER PLANS. ARCHITECT'S SEAL IS
 ILLEGIBLE SO DOES NOT COMPLY WITH FLORIDA STATUTE 481
 (PRINTED NAME TO BE ON THE PLAN). ARCHITECT IS TO
 PROVIDE A DIGITALLY SIGNED PLAN WHEN RESUBMITTING. IF
 ARCHITECT NEEDS ASSISTANCE WITH CREATING A DIGITAL
 SIGNATURE AND APPLYING TO THE PDF, PLEASE HAVE
 ARCHITECT CONTACT ME FOR ASSISTANCE - [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-21 Cont ID  
Sent By pvalenti Date 2022-12-21 Time 16:40 Rev Time 0.00
Received By pvalenti Date 2022-12-21 Time 16:40 Sent To  
Notes
2022-12-21 16:44:15PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY PAPER SUBMITTAL SHEET P.8
 (ISOMETRIC GAS PIPING) HAND SIGNED/SEALED BY ARCHITECT.
 SUBMITTAL ROUTED TO STORAGE BIN.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rwbrown Date 2022-11-01 Time 06:30 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
2022-11-01 06:31:51IF SIGNED BY A REGISTERED ARCHITECT, A WET SEAL CANNOT
 BE ACCEPTED ON DIGITAL PLANS. THE DIGITAL PLANS MUST BE
 ELECTRONICALLY SEALED.
  
 ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.