Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By eroseber Date 2022-11-07 Time 20:54 Rev Time 0.00
Received By eroseber Date 2022-11-07 Time 20:54 Sent To  
Notes
2022-11-07 20:55:011. PLEASE SUBMIT FLOOR PLAN SKETCH SHOWING LOCATION OF
 ALL REPLACEMENT DOORS. FBC 107.2
 2. PLEASE SUBMIT SCHEDULE THAT CORRESPONDS TO FLOOR
 PLAN IDENTIFYING LOCATIONS OF EACH SPECIFIC REPLACEMENT
 DOOR. FBC 107.2
 3. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO
 THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR
 FBC B 1405.4.
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-11-30 Cont ID  
Sent By amhamilt Date 2022-11-30 Time 12:52 Rev Time 0.00
Received By amhamilt Date 2022-11-30 Time 12:52 Sent To  
Notes
2022-11-30 12:53:18THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE PROVIDE PHOTO OF EXISTING DOOR(S) TO BE REPLACED
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER