Plan Review Details - Permit 22100531
Plan Review Stops For Permit 22100531
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By eroseber Date 2023-05-09 Time 18:16 Rev Time 0.00
Received By eroseber Date 2023-05-09 Time 18:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-22 Cont ID  
Sent By eroseber Date 2023-03-22 Time 09:14 Rev Time 0.00
Received By eroseber Date 2023-03-22 Time 09:14 Sent To  
Notes
2023-03-22 09:15:15PLAN REVIEWER: ED ROSEBERRY PX2909
 EMAIL: [email protected]
 PH: 772-359-3502
  
 1. PLEASE SUBMIT FLOOR PLAN AND SCHEDULE SHOWING
 LOCATION, MRH, AND WALL ZONE FOR REPLACEMENT
 FENESTRATION. FBC 107.2
 2. PLEASE SUBMIT FBC/NOA FOR ALL REPLACEMENT
 FENESTRATION, WITH SPECIFIC MODELS, SIZES, AND DESIGN
 PRESSURE TABLES HIGHLIGHTED. FBC 107.2
 3. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO
 THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR
 FBC B 1405.4. ***NOTE*** THIS IS NOT USUALLY INCLUDED
 IN FBC/NOA. COMPLIANCE MUST BE SHOWN SEPARATELY.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By eroseber Date 2023-05-09 Time 18:18 Rev Time 0.00
Received By eroseber Date 2023-04-20 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-22 Cont ID  
Sent By eroseber Date 2023-03-22 Time 09:16 Rev Time 0.00
Received By eroseber Date 2023-02-28 Time 11:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-22 Cont ID  
Sent By eroseber Date 2023-03-22 Time 09:15 Rev Time 0.00
Received By eroseber Date 2023-03-22 Time 09:15 Sent To  
Notes
***NONE***