| 2022-10-25 16:32:30 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22100496 |
| | 10/25/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A BASIC FLOOR OR SITE PLAN SHOWING THE |
| | LOCATIONS OF ALL THE GAS-FIRED APPLIANCES- SEC. 107.2.1 |
| | WPB. PLEASE NOTE THE APPROVED REMODELING PLANS UNDER |
| | PERMIT 21100750 DID NOT SHOW THE FIREPLACE, THE GRILL, |
| | AND ONLY ONE OF THE TWO TANKLESS WATER HEATERS. |
| | |
| | 2) THE $8500.00 PERMIT VALUE IS LOW BASED ON THE SCOPE |
| | OF THE PROJECT AND APPLIANCES LISTED ABOVE THAT WERE |
| | NOT INCLUDED IN THE MASTER. PLEASE NOTE THAT PERMIT |
| | VALUE IS BASED ON LABOR, MATERIALS, EQUIPMENT AND |
| | APPLIANCES- SEC. 109.3 WPB. |
| | |
| | 3) GAS RISER: A SEPARATE PERMIT IS REQUIRED FOR THE |
| | GENERATOR. PLEASE INDICATE IT AS ???FUTURE GENERATOR??? |
| | ON THE DRAWING AND SHOW A SHUT OFF VALVE AND GAS-TIGHT |
| | CAP WILL BE INSTALLED AT THE OUTLET- SEC. 107.2.1 WPB |
| | AND SEC. G2415.15 FBC RES. |
| | |
| | 4) GAS RISER: TO HELP EXPEDITE THE REVIEW PLEASE |
| | PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM |
| | THE METER TO THE MOST REMOTE OUTLET- SEC G2413.4.1 FBC |
| | RES. IT APPEARS TO BE 190 FT. |
| | |
| | 5) GAS RISER: PROVIDE THE EHD OF THE CSST- TABLE |
| | 402.4(17) FBC FG. |
| | |
| | 6) GAS RISER: PLEASE NOTE THAT THE SPACE BETWEEN THE |
| | SLEEVE AND CSST PIPING WILL BE SEALED AT THE ISLAND AND |
| | THE OPPOSITE END WILL BE VENTED TO THE OUTDOORS- SEC. |
| | G2415.8.1 FBC RES. |
| | |
| | 7) GAS FIREPLACE: PLEASE SUBMIT MANUFACTURER???S |
| | SPECIFICATIONS THAT INCLUDE THE LISTING NUMBER OF THE |
| | UNIT- SECS. G2435 & G2436 FBC RES. |
| | |
| | A) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW |
| | THE AIR WILL BE PROVIDED- SEC. G2407.1 FBC RES. |
| | |
| | B) PROVIDE A VENTING DIAGRAM SHOWING THE TYPE AND SIZE |
| | OF VENT FLUE AND THE TERMINATION LOCATION- SEC. G2427.1 |
| | FBC RES. |
| | |
| | 8) TANKLESS WATER HEATERS: ON THE FLOOR OR SITE PLAN |
| | PLEASE SHOW THE CLEARANCES DISTANCES FROM THE WATER |
| | HEATERS TO OPERABLE OPENINGS AND AIR INTAKES INTO THE |
| | BUILDING- SECS. G2427.8 & G2448.1 FBC RES. |
| | |
| | 9) GAS BBQ: ON THE FLOOR OR SITE PLAN PLEASE SHOW THE |
| | LOCATION OF THE UNIT TO VERIFY IT WILL NOT BE IN AN |
| | ENCLOSED SPACE WITHOUT INSTALLATION OF A HOOD AND |
| | EXHAUST SYSTEM- REFER TO THE MANUFACTURER???S |
| | SPECIFICATIONS AND INSTALLATION GUIDELINES- SEC. |
| | G2447.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |