Plan Review Details - Permit 22100465
Plan Review Stops For Permit 22100465
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-11-22 Cont ID  
Sent By rmcphers Date 2022-11-22 Time 11:06 Rev Time 0.00
Received By rmcphers Date 2022-11-22 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By shill Date 2022-11-16 Time 18:23 Rev Time 0.00
Received By shill Date 2022-11-16 Time 18:23 Sent To  
Notes
2022-11-16 18:31:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, SCOPE OF THIS PERMIT IS NOT CLEAR. THE
 APPLICATION IS FOR UNDERLAYMENT. IS IT THE INTENT TO
 PERMIT THE FLOORING UNDER A SEPARATE PERMIT?
  
 2. FBC 109, VALUE APPEARS LOW. PROVIDE A COST
 BREAKDOWN.
  
 3. TO ADDRESS COMMENTS -
  
 IF THE SCOPE IS TO INCLUDE FLOORING, UPLOAD A NEW
 APPLICATION WITH REVISED SCOPE OF WORK AND REVISED
 VALUE.
  
 IF THE SCOPE DOES NOT INCLUDE FLOORING, ONLY
 UNDERLAYMENT, UPLOAD A RESPONSE LETTER OF EXPLANATION.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-26 Cont ID  
Sent By pleduc Date 2022-10-26 Time   Rev Time 0.00
Received By pleduc Date 2022-10-26 Time 10:13 Sent To  
Notes
2022-10-26 10:14:59FIRE PROVISO:
  
 PROVIDE FLOORING SPEC SHEETS FOR FIRE INSPECTOR
 VERIFICATION/CONFIRMATION ON FIRE INSPECTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By pleduc Date 2022-10-25 Time   Rev Time 0.00
Received By pleduc Date 2022-10-25 Time 16:08 Sent To  
Notes
2022-10-20 10:49:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR SILENCER UNDERLAYMENT, BUT NO SPEC SHEET NOR A
 PRODUCT NAME FOR THE ACTUAL PROPOSED LAMINATE FLOORING.
  
 LAMINATE FLOORING IS MANUFACTURED AROUND THE WORLD BUT
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE LAMIANTE
 FLOORING PRODUCT NAME AND THE PRODUCT SPEC SHEETS
 INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-22 Cont ID  
Sent By rmcphers Date 2022-11-22 Time 11:06 Rev Time 0.00
Received By rmcphers Date 2022-11-21 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-16 Cont ID  
Sent By shill Date 2022-11-16 Time 18:31 Rev Time 0.00
Received By shill Date 2022-10-12 Time 18:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-11-16 Cont ID  
Sent By shill Date 2022-11-16 Time 18:31 Rev Time 0.00
Received By shill Date 2022-11-16 Time 18:31 Sent To  
Notes
***NONE***