Plan Review Details - Permit 22100412
Plan Review Stops For Permit 22100412
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-01 Cont ID  
Sent By rmcphers Date 2022-12-01 Time 12:41 Rev Time 0.00
Received By rmcphers Date 2022-12-01 Time 12:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-11-22 Cont ID  
Sent By rmcphers Date 2022-11-22 Time 11:31 Rev Time 0.00
Received By rmcphers Date 2022-11-22 Time 11:31 Sent To  
Notes
2022-11-22 11:31:59STAIR REPLACEMENT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE HANDRAIL EXTENSION AT THE TOP TO
 CONTINUE IN THE SAME DIRECTION AS THE STAIR (ONE SIDE
 DOES THE OTHER SIDE IS SHOWN TURNING) FBC 1014.6
 HANDRAIL EXTENSIONS.THE EXTENSIONS OF HANDRAILS SHALL
 BE IN THE SAME DIRECTION OF THE FLIGHTS OF STAIRS AT
 STAIRWAYS AND THE RAMP RUNS AT RAMPS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By rmcphers Date 2022-11-08 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2022-11-08 Time 10:39 Sent To  
Notes
2022-11-08 10:55:59STAIR REPLACEMENT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF
 THE STAIR.
  
 2) PLEASE SHOW THE HANDRAIL EXTENSION AT THE TOP TO
 CONTINUE IN THE SAME DIRECTION AS THE STAIR (ONE SIDE
 DOES THE OTHER SIDE IS SHOWN TURNING) FBC 1014.6
 HANDRAIL EXTENSIONS.THE EXTENSIONS OF HANDRAILS SHALL
 BE IN THE SAME DIRECTION OF THE FLIGHTS OF STAIRS AT
 STAIRWAYS AND THE RAMP RUNS AT RAMPS.
  
 3) IF A WALKING PATH IS UNDER THE STAIR PLEASE SHOW
 COMPLIANCE WITH FBC ACCESSIBILITY 307.4 VERTICAL
 CLEARANCE.
 VERTICAL CLEARANCE SHALL BE 80 INCHES (2030 MM) HIGH
 MINIMUM. GUARDRAILS OR OTHER BARRIERS SHALL BE PROVIDED
 WHERE THE VERTICAL CLEARANCE IS LESS THAN 80 INCHES
 (2030 MM) HIGH. THE LEADING EDGE OF SUCH GUARDRAIL OR
 BARRIER SHALL BE LOCATED 27 INCHES (685 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-11-30 Cont ID  
Sent By pleduc Date 2022-11-30 Time   Rev Time 0.00
Received By pleduc Date 2022-11-30 Time 12:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-18 Cont ID  
Sent By pleduc Date 2022-11-18 Time   Rev Time 0.00
Received By pleduc Date 2022-11-18 Time 11:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By pleduc Date 2022-10-17 Time   Rev Time 0.00
Received By pleduc Date 2022-10-17 Time 15:34 Sent To  
Notes
2022-10-17 15:36:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF AN EXIT STARIWAY AT THE
 PROVIDED ADDRESS BUT THERE IS NOT SITE PLAN SHOWING THE
 LOCATION AND/OR ORIENATION TO THE BUILDING.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE A SITE PLAN
 SHOWING THE LOCATION OF THE STAIR.
  
  
 2) THERE IS NO INDICATION OF THE EXISTING STAIR
 DIMENSIONS.
  
 PLEASE PROVIDE THE EXISTING STAIR DIMENSIONS INDICATING
 THAT THESE NEW STAIRS MEET OR EXCEED THE EXISTING
 STAIRS.
  
 OR PROVIDE A LIFE SAFETY PLAN INDICATING THE OCCUPANCY
 LOAD OF THE 2ND FLOOR AND THAT THESE NEW STAIRS MEETS
 OR EXCEEDS THE EXITING REQUIREMENTS OF NFPA 101 CH
 12/13.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-10-20 Cont ID  
Sent By fmittner Date 2022-10-20 Time 10:58 Rev Time 0.00
Received By fmittner Date 2022-10-20 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-02 Cont ID  
Sent By dbattles Date 2022-12-02 Time 09:08 Rev Time 0.00
Received By dbattles Date 2022-11-29 Time 09:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-22 Cont ID  
Sent By rmcphers Date 2022-11-22 Time 11:34 Rev Time 0.00
Received By rmcphers Date 2022-11-17 Time 07:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-08 Cont ID  
Sent By rmcphers Date 2022-11-08 Time 10:58 Rev Time 0.00
Received By rmcphers Date 2022-10-14 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-01 Cont ID  
Sent By rmcphers Date 2022-12-01 Time 12:41 Rev Time 0.00
Received By rmcphers Date 2022-12-01 Time 12:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-22 Cont ID  
Sent By rmcphers Date 2022-11-22 Time 11:34 Rev Time 0.00
Received By rmcphers Date 2022-11-22 Time 11:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-08 Cont ID  
Sent By rmcphers Date 2022-11-08 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2022-11-08 Time 10:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-12-01 Cont ID  
Sent By ckimmerl Date 2022-12-01 Time 16:56 Rev Time 0.00
Received By ckimmerl Date 2022-12-01 Time 16:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-11-21 Cont ID  
Sent By ckimmerl Date 2022-11-21 Time 08:42 Rev Time 0.00
Received By ckimmerl Date 2022-11-21 Time 08:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By ckimmerl Date 2022-11-08 Time 09:04 Rev Time 0.00
Received By ckimmerl Date 2022-11-08 Time 09:02 Sent To  
Notes
2022-11-08 09:04:181. ZONING CANNOT PASS REVIEW DUE TO LACK OF SURVEY AND
 SITE PLAN INDICATING WHERE THE STAIR IS LOCATED ON THE
 PREMISES.
  
 - PLEASE PROVIDE BOTH A SURVEY AND SITE PLAN.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected] 822-1426