Plan Review Details - Permit 22100341
Plan Review Stops For Permit 22100341
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2023-07-12 Cont ID  
Sent By swelter Date 2023-07-12 Time 09:04 Rev Time 0.00
Received By swelter Date 2023-07-12 Time 09:05 Sent To  
Notes
2023-07-06 16:25:52PAID
  
 PUBLIC ART REQUIRED OPTION#2 .75% OF 1%
 CONTACT [email protected]
  
 ART ASSESSMENT FEE DUE NOW - MUST CONTACT
 [email protected] TO COMPLETE

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-22 Cont ID  
Sent By rmcphers Date 2023-06-22 Time 11:23 Rev Time 0.00
Received By rmcphers Date 2023-06-22 Time 11:22 Sent To  
Notes
2023-06-22 11:23:40REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS A-0.3 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-14 Cont ID  
Sent By rmcphers Date 2023-03-14 Time 13:14 Rev Time 0.00
Received By rmcphers Date 2023-03-14 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-21 Cont ID  
Sent By rmcphers Date 2022-12-21 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2022-12-21 Time 14:05 Sent To  
Notes
2022-12-21 14:14:03REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS A3.2.1, A5.2.2 DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rmcphers Date 2022-11-01 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2022-11-01 Time 13:11 Sent To  
Notes
2022-11-01 13:25:09REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW HOW DOOR (ST-19) FROM ROOM (S132)
 COMPLIES WITH THE POOL BARRIER REQUIREMENT - FBC
 454.1.3.1.9
  
 2) DRAWING S-2.2.9 NEEDS TO BE DIGITALLY/ELECTRONICALLY
 SIGNED BY THE DESIGNER.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-20 Cont ID  
Sent By jleahy Date 2023-03-20 Time 12:06 Rev Time 0.00
Received By jleahy Date 2023-03-20 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-24 Cont ID  
Sent By jleahy Date 2022-10-24 Time 09:27 Rev Time 0.00
Received By jleahy Date 2022-10-20 Time 12:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-13 Cont ID  
Sent By pleduc Date 2023-03-13 Time   Rev Time 0.00
Received By pleduc Date 2023-03-13 Time 12:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-12-22 Cont ID  
Sent By pleduc Date 2022-12-22 Time   Rev Time 0.00
Received By pleduc Date 2022-12-22 Time 10:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 10:17 Rev Time 0.00
Received By ccole Date 2023-01-03 Time 15:47 Sent To  
Notes
2023-01-04 10:18:41THE ARCHITECT HAS REQUESTED GAS INSTALLATIONS TO BE
 UNDER A SEPARATE PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By ccole Date 2022-10-31 Time 15:56 Rev Time 0.00
Received By ccole Date 2022-10-31 Time 15:56 Sent To  
Notes
2022-10-31 15:58:271ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100341
 10/31/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-2.2.1. A GAS METER IS SHOWN ON THE PLAN
 HOWEVER NO GAS PLANS HAVE BEEN SUBMITTED. PLEASE
 PROVIDE GAS PLANS IN COMPLIANCE WITH SEC. 107.3.5.1.5
 WPB. THE SUBMITTAL SHALL INCLUDE A RISER DIAGRAM,
 PIPING LAYOUT PLANS, EQUIPMENT AND APPLIANCE
 SPECIFICATIONS, VENTING AND COMBUSTION AIR DIAGRAMS AND
 CALCULATIONS.
 PLEASE NOTE THAT GAS FOR THE BUILDING CAN BE UNDER A
 SEPARATE PERMIT IF REQUESTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-12 Cont ID  
Sent By aoliver Date 2023-07-12 Time 10:03 Rev Time 0.00
Received By aoliver Date 2023-06-20 Time 11:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-28 Cont ID  
Sent By aoliver Date 2023-03-28 Time 10:50 Rev Time 0.00
Received By aoliver Date 2023-03-10 Time 14:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-23 Cont ID  
Sent By lmarchan Date 2023-01-23 Time 14:17 Rev Time 0.00
Received By lmarchan Date 2022-12-20 Time 08:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-07 Cont ID  
Sent By rmcphers Date 2022-12-07 Time 14:12 Rev Time 0.00
Received By rmcphers Date 2022-10-19 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-03-16 Cont ID  
Sent By medwards Date 2023-03-16 Time 09:20 Rev Time 0.00
Received By medwards Date 2023-03-16 Time 09:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-11-08 Cont ID  
Sent By medwards Date 2022-11-08 Time 05:57 Rev Time 0.00
Received By medwards Date 2022-11-08 Time 05:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-03-15 Cont ID  
Sent By ccole Date 2023-03-15 Time 13:49 Rev Time 0.00
Received By ccole Date 2023-03-15 Time 07:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 10:14 Rev Time 0.00
Received By ccole Date 2023-01-03 Time 15:47 Sent To  
Notes
2023-01-04 10:15:22PERMIT 22100341- REVISED PLUMBING PLANS DENIED.
 1/4/2023
  
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES FOR FURTHER CLARIFICATION.
  
  
 3) 2ND REQUEST. P-5.2.6: PROVIDE AN RPZ BACKFLOW
 PREVENTER FOR THE WATER LINE TO THE SPA EQUIPMENT- SEC.
 608.17.4.1 FBC P AND SECS. C, D, & E- WPB CROSS
 CONNECTION MANUAL. PLEASE PROVIDE EQUIPMENT SCHEDULES
 FOR BOTH THE SPA AND POOL BF PREVENTERS- SEC. 608.3 FBC
 P.
  
 4) 2ND REQUEST. SUBMIT REVISED SHEETS P-5.2.4 & P-6.2.1
 SHOWING THE DRAINAGE TO BE DECHLORINATED AND DISCHARGED
 TO STORM, OR PLACE A NOTE ON SHEET P-2.2.1 FOR
 CLARIFCATION.
 P-2.2.1: DETAIL P-6 FOR POOL AND SPA BACKWASH DRAINAGE
 IS REFERENCED ON THE PLAN. THE DETAIL IS 11/P-6.2.1
 WHICH WAS NOT PROVIDED BUT REVIEW OF THE MAIN PLUMBING
 PLANS SHOWS THE POOL BACKWASH DRAINING INTO THE
 SANITARY SYSTEM WHICH IS PROHIBITED PER SEC. 90-126 (5)
 WPB.
  
 6) 2ND REQUEST. THE RESPONSE NARRATIVE INDICATES THE
 BRIDGE ROOF DRAINAGE ON NEW SHEET P-2.1.4 WHICH WAS NOT
 UPLOADED FOR REVIEW.
 SHEETS P-2.2.3, P-2.2.5 & P-5.2.5: PLEASE PROVIDE A
 DIMENSIONED BRIDGE ROOF DRAINAGE PLAN THAT SHOWS THE
 LOCATIONS OF THE PRIMARY AND SECONDARY (OVERFLOW) ROOF
 DRAINS, RAINFALL RATE, AND GPM FLOW AT THE RD LOCATION-
 SEC. 1105.1 & 1106.1 FBC P. THE RESPONSE NARRATIVE
 INDICATES A THE ROOF DRAINAGE ON NEW SHEET P-2.1.4
 WHICH WAS NOT UPLOADED FOR REVIEW.
  
 7) 2ND REQUEST. MINIMUM REQUIRED APPLICATIONS FOR THE
 POTABLE WATER BACKFLOW PREVENTER AND GREASE INTERCEPTOR
 NOT PROVIDED. PLEASE NOTE THAT SEPARATE PERMITS ARE
 REQUIRED FOR THE POTABLE WATER BACKFLOW PREVENTER,
 GREASE INTERCEPTOR, IRRIGATION, IRRIGATION BACKFLOW,
 AND POOL. IF REQUESTED GAS CAN ALSO BE UNDER A SEPARATE
 PERMIT. DUE TO A CHANGE IN PROCESS, THE BACKFLOW AND
 GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED
 PRIOR TO APPROVAL OF THE PLUMBING REVISION. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected] . YOU
 WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS.
 YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT
 THE APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS AND EMAIL
 CORRESPONDENCE WITH THE ENGINEER.
  
 1) SHEETS A-1.2.1, P-2.2.1, P-5.2.4: MISSING FROM THE
 NEW PLUMBING FIXTURE CALCULATIONS AND APPARENTLY FROM
 THE PLAN IS THE REQUIRED SERVICE SINK. THE CALCULATIONS
 DO OMIT VITAL INFORMATION INCLUDING THE OCCUPANCY
 CLASSIFICATIONS AND OCCUPANT LOADS FOR EACH
 CLASSIFICATION, HOWEVER BASED ON THE PLANS AND TABLE
 403.1 IT APPEARS A COMPLIANT NUMBER OF WATER CLOSETS
 AND LAVATORIES HAVE BEEN PROVIDED FOR THE POOL, AND THE
 A AND B OCCUPANCIES. IT IS ACKNOWLEDGED THAT FUTURE
 BATHROOMS WILL UNDER THE RETAIL BUILD-OUT PERMIT.
  
 2) P-2.2.1 & P-5.2.4: 2ND REQUEST TO REVISE THESE
 SHEETS TO SHOW POOL WASTEWATER DISCHARGE DECHLORINATED
 AND DRAINED INTO THE STORM SYSTEM.
  
 3) P-5.2.4: RISER #14 SHOWN IN THE ISO IS NOT SHOWN ON
 RISER SHEETS P-5.2.2 OR P-5.2.3- SEC. 107.2.1 WPB.
  
 4) P-2.2.1 & P-5.2.4: THE 8-INCH MAIN BUILDING DRAIN
 LINE SHOWING 1622 DFU'S IS UNDERSIZED PER TABLE
 710.1(1) AT 1/8-INCH PER FT. SLOPE.
  
 5) P-5.2.6: THE EQUIPMENT SCHEDULES FOR THE STORAGE AND
 TANKLESS WATER HEATERS SHOWN ON THE ISO ARE NOT SHOWN
 ON SHEET P-6.2.2 AND NO INSTALLATION DETAILS PROVIDED
 SUCH AS THE DETAIL PROVIDED FOR THE APARTMENT UNITS ON
 P-6.2.1. THE DETAIL SHOULD SHOW THE MASTER THERMOSTATIC
 MIXING VALVE AND THE MEANS OF CONTROLLING EXPANSION-
 SECS. 607.1.1 & 607.3.
  
 6) P-5.2.6: NO INFO OR DETAILS PROVIDED FOR REQUIRED
 TEMPERED WATER DELIVERY AT LAVS, MASTER THERMOSTATIC
 MIXING VALVES AT WATER HEATERS TO LIMIT HOT WATER
 TEMPERATURE DELIVERY, AND NO HW PIPE INSULATION SPECS-
 SECS. 419.5, 607.1.1, 606.2.1, AND TABLE C403.2.10.
  
 7) P-5.2.6: THE LENGTHS OF HW FIXTURE SUPPLY PIPES TO
 THE LAVS IN GANG BATHROOM ARE EXCEEDING THE MAX 2FT.
 ALLOWABLE LENGTHS- TABLE C404.5.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS ST.
 WEST PALM BEACH, FL. 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By rwbrown Date 2022-10-25 Time 08:52 Rev Time 0.00
Received By ccole Date 2022-10-24 Time 08:42 Sent To  
Notes
2022-10-31 11:49:38PERMIT 22100341- REVISED PLUMBING PLANS DENIED.
 10/28/22
  
 COMMENTS.
  
 1) SHEET P-5.2.6: PLEASE REVISE THE RISER TO SHOW THE
 1-INCH COMMERCIAL SERVICE LINE RUN TO THE FUTURE RETAIL
 SPACE- SEC. 107.3.5.1.3 FBC P. SHOW A SHUT-OFF VALVE
 AND CAP WILL PROVIDED AT THE ENTRANCE TO THE RETAIL
 SPACE.
 2) P-5.2.6: PROVIDE CORRELATING TEXT FOR THE NUMBERED
 NOTES 1-4 ON THE RISER- SEC. 107.2.1 WPB.
  
  
 3) P-5.2.6: PROVIDE AN RPZ BACKFLOW PREVENTER FOR THE
 WATER LINE TO THE SPA EQUIPMENT- SEC. 608.17.4.1 FBC P
 AND SECS. C, D, & E- WPB CROSS CONNECTION MANUAL.
 PLEASE PROVIDE EQUIPMENT SCHEDULES FOR BOTH THE SPA AND
 POOL BF PREVENTERS- SEC. 608.3 FBC P.
  
 4) P-2.2.1: DETAIL P-6 FOR POOL AND SPA BACKWASH
 DRAINAGE IS REFERENCED ON THE PLAN. THE DETAIL IS
 11/P-6.2.1 WHICH WAS NOT PROVIDED BUT REVIEW OF THE
 MAIN PLUMBING PLANS SHOWS THE POOL BACKWASH DRAINING
 INTO THE SANITARY SYSTEM WHICH IS PROHIBITED PER SEC.
 90-126 (5) WPB. PLEASE NOTE THE FOLLOWING:
  
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED
 TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT O&M
 SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 5) P-2.2.2.1: PLEASE SHOW THE LOCATION OF THE FUTURE
 SANITARY DRAIN PIPING FOR THE RETAIL SPACE. THIS SPACE
 APPEARS TO BE ISOLATED FROM THE MAIN FLOOR. PLEASE
 CLARIFY IF PLUMBING FIXTURES FOR THE OCCUPANTS WILL BE
 PROVIDED IN ACCORDANCE WITH TABLE 403.1.
  
 6) SHEETS P-2.2.3, P-2.2.5 & P-5.2.5: PLEASE PROVIDE A
 DIMENSIONED BRIDGE ROOF DRAINAGE PLAN THAT SHOWS THE
 LOCATIONS OF THE PRIMARY AND SECONDARY (OVERFLOW) ROOF
 DRAINS, RAINFALL RATE, AND GPM FLOW AT THE RD LOCATION-
 SEC. 1105.1 & 1106.1 FBC P.
  
 7) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE POTABLE WATER BACKFLOW PREVENTER, GREASE
 INTERCEPTOR, IRRIGATION, IRRIGATION BACKFLOW, AND POOL.
 IF REQUESTED GAS CAN ALSO BE UNDER A SEPARATE PERMIT.
 DUE TO A CHANGE IN PROCESS, THE BACKFLOW AND GREASE
 INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO APPROVAL OF THE PLUMBING REVISION. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 8) SHEET- P-2.2.2.1: THE POOL IS UNDER SEPARATE PERMIT
 HOWEVER PLEASE SHOW THE LOCATIONS OF THE REQUIRED
 SANITARY FACILITIES AND PROVIDE PLUMBING FIXTURE
 CALCULATIONS PER TABLES 403.1, 403.6, AND SEC. 403.1.1
 FBC P. THE PLAN APPEARS TO SHOW THE BATHROOMS ON THE
 FIRST FLOOR ARE FOR OCCUPANTS OF THE POOL AND DECK, AND
 THE OCCUPANTS OF THE BUILDING- PLEASE CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS ST.
 WEST PALM BEACH, FL. 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 16:27 Rev Time 0.00
Received By ccole Date 2023-01-04 Time 16:27 Sent To  
Notes
2023-01-04 16:28:02A SEPARATE PERMIT AND PLAN SUBMITTAL ARE REQUIRED FOR
 INSTALLATION OF THE GREASE INTERCEPTOR.

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 16:28 Rev Time 0.00
Received By ccole Date 2023-01-04 Time 16:28 Sent To  
Notes
2023-01-04 16:28:58A SEPARATE PERMIT AND PLAN SUBMITTAL ARE REQUIRED FOR
 INSTALLATION OF THE IRRIGATION SYSTEM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-06-22 Cont ID  
Sent By rmcphers Date 2023-06-22 Time 11:24 Rev Time 0.00
Received By rmcphers Date 2023-06-22 Time 11:24 Sent To  
Notes
2023-06-22 11:24:32SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS A-0.3 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-14 Cont ID  
Sent By rmcphers Date 2023-03-14 Time 13:14 Rev Time 0.00
Received By rmcphers Date 2023-03-14 Time 13:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-21 Cont ID  
Sent By rmcphers Date 2022-12-21 Time 14:11 Rev Time 0.00
Received By rmcphers Date 2022-12-21 Time 14:11 Sent To  
Notes
2022-12-21 14:13:16SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS A3.2.1, A5.2.2 DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rmcphers Date 2022-11-01 Time 13:50 Rev Time 0.00
Received By rmcphers Date 2022-11-01 Time 13:50 Sent To  
Notes
2022-11-01 13:51:47SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S-2.2.9 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop Z ZONING
Rev No 4 Status F Date 2023-07-07 Cont ID  
Sent By cibaven Date 2023-07-07 Time 09:00 Rev Time 0.00
Received By cibaven Date 2023-07-07 Time 08:59 Sent To  
Notes
2023-07-07 09:00:30 
 1. PLEASE MAKE SURE TO ADD REVISIONS DATES TO PLANS
 WHEN RESUBMITTING.
 2. THE PROJECT IS REQUIRED TO COMPLY WITH THE ARTLIFE
 ORDINANCE, PLEASE RESPOND ON HOW THE PROJECT HAS
 COMPLIED.
 3. PLEASE CONFIRM THAT THE STREETLIGHTS PROPOSED COMPLY
 WITH DOWNTOWN LIGHT STANDARDS, AND IN WHICH DRAWING
 SHOWS.
 4. MECHANICAL EQUIPMENT ON ROOF SHALL BE SCREENED WITH
 A WALL OR SCREENING AS TALL AS THE EQUIPMENT.
 5. AN AERIAL EASEMENT SHALL BE APPROVED BY CITY
 COMMISSION BEFORE T.C.O.
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED PRIOR TO
 ISSUANCE OF FINAL CO:
 1. A MINOR SITE PLAN AMENDMENT APPLICATION WILL NEED TO
 BE SUBMITTED AND APPROVED BY THE PLANNING DIVISION
 PRIOR CO.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF ANY HARDSCAPE,
 LANDSCAPING AND IRRIGATION, AND ANY OTHER DECORATIVE
 ELEMENT INSTALLED WITHIN THE RIGHT OF WAY BY THIS
 PROJECT. APPROVAL OF A MAINTENANCE AGREEMENT BETWEEN
 THE CITY AND THE APPLICANT, SUCCESSORS AND ASSIGNS WILL
 BE REQUIRED BEFORE FINAL CO. THE PROPOSED LANDSCAPE
 ALONG DIXIE HIGHWAY WILL REQUIRE APPROVAL FROM FDOT AND
 A MAINTENANCE AGREEMENT.
 3. PROJECT WILL BE REQUIRED TO CONTRIBUTE TO A TRANSIT
 FEE EQUAL TO $10/MONTH PER EACH MICRO UNIT INCLUDED IN
 THE PROJECT. THE FIRST PAYMENT WILL BE DUE AT THE TIME
 OF FINAL CO.
  
 CLAUDIA D. IBAVEN
 CITY URBAN DESIGNER / ZONING AND PLANNING
 [email protected]
 561-822-1402
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-03-27 Cont ID  
Sent By cibaven Date 2023-03-27 Time 16:45 Rev Time 0.00
Received By cibaven Date 2023-03-27 Time 16:44 Sent To  
Notes
2023-03-27 16:45:17CLAUDIA D. IBAVEN
 CITY URBAN DESIGNER / PLANNING DIVISION
 [email protected]
 561-822-1402
  
 I HAVE REVIEWED PERMIT NO. 22100341 AND PROVIDE THE
 FOLLOWING COMMENTS:
 1) SHEETS L1-6-01 AND L1-6-02 SHOW THAT VEGETATED AREA
 REQUIRED IS NOT MET FOR THE PRIVATE OPEN SPACE NAMED
 POOL AREA. PLEASE REVISE PLANS TO MEET REQUIREMENT.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-01-23 Cont ID  
Sent By cibaven Date 2023-01-23 Time 13:50 Rev Time 0.00
Received By cibaven Date 2023-01-23 Time 13:50 Sent To  
Notes
2023-01-23 13:50:39ZONING AND PLANNING
 PROJECT: CIELO 740 N DIXIE HWY
 PERMIT NO. 22100341
 DATE: JANUARY 23, 2023
 CONTACT: CLAUDIA IBAVEN, CITY URBAN DESIGNER, AT
 561-822-1402 OR VIA [email protected].
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 AS NOTED IN PREVIOUS COMMENTS SOME FLOOR PLANS SHEETS
 INDICATE CHANGES TO WINDOWS AND DOORS. BELOW SOME
 QUESTIONS FROM RESPONSES RECEIVED.
  
 SHEET A-3.2.1
 WEST ELEVATION: IT WAS PREVIOUSLY MENTIONED THAT
 WINDOWS BETWEEN CERTAIN GRIDS ONLY CHANGED THEIR
 MULLIONS TO COMPLY WITH MECHANICAL VENTILATION
 REQUIREMENTS, ARE CHANGES ON ALL WINDOWS ON ALL FLOOR
 LEVELS OR CERTAIN FLOOR LEVELS? HAVE ANY OF THEM CHANGE
 IN SIZE?
 NORTH ELEVATION: THERE SEEMS TO BE A CHANGED IN THE
 WINDOW BELOW THE PEDESTRIAN BRIDGE, PLEASE CONFIRM AND
 EXPLAIN CHANGE.
  
 SHEET A-3.2.2
 EAST ELEVATION: IN ADDITION TO THE NANAWALL CHANGE, ON
 THE GROUND FLOOR BETWEEN GRIDS 12 AND 11 THERE SEEMS TO
 BE A CHANGE, IS THIS CHANGE ONLY REMOVING THE
 ???CONCRETE EYEBROW??? FROM THE WINDOW?
 SOUTH ELEVATION: PLEASE, CONFIRM IF NO CHANGES WERE
 MADE TO THE SOUTH ELEVATION.
  
 OTHER COMMENTS:
 HAS ANY OF THE MATERIALS LISTED IN THE ELEVATION LEGEND
 CHANGED FROM WHAT WAS ORIGINALLY APPROVED BY DAC?
  
 ARE ANY CHANGES IN GRADING, PAVING AND DRAINAGE PLANS
 AFFECTING OPEN SPACE AREAS AND POTENTIALLY CHANGE
 LANDSCAPE SHEETS AND CALCULATIONS FOR REQUIRED FOR OPEN
 SPACE, VEGETATED AREA, AND TREE CANOPY AS SEEN ON SHEET
 APPROVED 050- L-1-6-01 OPEN SPACE DIAGRAM IN MASTER
 PERMIT?
  
 PLEASE CONFIRM THAT MECHANICAL EQUIPMENT ON ROOF IS
 SCREENED WITH A WALL OR SCREENING AS TALL AS THE
 EQUIPMENT.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-05 Cont ID  
Sent By ckimmerl Date 2022-12-05 Time 10:21 Rev Time 0.00
Received By aaponte Date 2022-12-05 Time 10:21 Sent To  
Notes
2022-12-05 10:23:12PLEASE INCLUDE A NARRATIVE OF THE CHANGES PROPOSED.
 PLEASE EXPLAIN WHAT ARE THA CHANGES ON THE WINDOWS AND
 HOW IT AFFECTS THE ELEVATION.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.