| Plan Review Stops For Permit 22100341 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
P |
Date |
2023-07-12 |
|
|
Cont ID |
|
| Sent By |
swelter |
Date |
2023-07-12 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
swelter |
Date |
2023-07-12 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2023-06-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-22 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-22 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2023-06-22 11:23:40 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS A-0.3 DOES NOT SHOW AS DIGITALLY SIGNED IN | | | ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-14 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-14 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-12-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-21 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-21 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2022-12-21 14:14:03 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS A3.2.1, A5.2.2 DOES NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-01 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-01 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2022-11-01 13:25:09 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW HOW DOOR (ST-19) FROM ROOM (S132) | | | COMPLIES WITH THE POOL BARRIER REQUIREMENT - FBC | | | 454.1.3.1.9 | | | | | | 2) DRAWING S-2.2.9 NEEDS TO BE DIGITALLY/ELECTRONICALLY | | | SIGNED BY THE DESIGNER. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-03-20 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-03-20 |
Time |
12:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-10-24 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-10-20 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-13 |
Time |
12:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-12-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-12-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-12-22 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2023-01-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-04 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-03 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2023-01-04 10:18:41 | THE ARCHITECT HAS REQUESTED GAS INSTALLATIONS TO BE | | | UNDER A SEPARATE PERMIT. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-10-31 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-31 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2022-10-31 15:58:27 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 22100341 | | | 10/31/22 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-2.2.1. A GAS METER IS SHOWN ON THE PLAN | | | HOWEVER NO GAS PLANS HAVE BEEN SUBMITTED. PLEASE | | | PROVIDE GAS PLANS IN COMPLIANCE WITH SEC. 107.3.5.1.5 | | | WPB. THE SUBMITTAL SHALL INCLUDE A RISER DIAGRAM, | | | PIPING LAYOUT PLANS, EQUIPMENT AND APPLIANCE | | | SPECIFICATIONS, VENTING AND COMBUSTION AIR DIAGRAMS AND | | | CALCULATIONS. | | | PLEASE NOTE THAT GAS FOR THE BUILDING CAN BE UNDER A | | | SEPARATE PERMIT IF REQUESTED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-07-12 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-07-12 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-06-20 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-03-28 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-03-28 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-10 |
Time |
14:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-01-23 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-01-23 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-12-20 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-07 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-19 |
Time |
14:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-16 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-16 |
Time |
09:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-08 |
Time |
05:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-08 |
Time |
05:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-15 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-15 |
Time |
07:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-01-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-04 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-03 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2023-01-04 10:15:22 | PERMIT 22100341- REVISED PLUMBING PLANS DENIED. | | | 1/4/2023 | | | | | | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW | | | WITH ADDITIONAL NOTES FOR FURTHER CLARIFICATION. | | | | | | | | | 3) 2ND REQUEST. P-5.2.6: PROVIDE AN RPZ BACKFLOW | | | PREVENTER FOR THE WATER LINE TO THE SPA EQUIPMENT- SEC. | | | 608.17.4.1 FBC P AND SECS. C, D, & E- WPB CROSS | | | CONNECTION MANUAL. PLEASE PROVIDE EQUIPMENT SCHEDULES | | | FOR BOTH THE SPA AND POOL BF PREVENTERS- SEC. 608.3 FBC | | | P. | | | | | | 4) 2ND REQUEST. SUBMIT REVISED SHEETS P-5.2.4 & P-6.2.1 | | | SHOWING THE DRAINAGE TO BE DECHLORINATED AND DISCHARGED | | | TO STORM, OR PLACE A NOTE ON SHEET P-2.2.1 FOR | | | CLARIFCATION. | | | P-2.2.1: DETAIL P-6 FOR POOL AND SPA BACKWASH DRAINAGE | | | IS REFERENCED ON THE PLAN. THE DETAIL IS 11/P-6.2.1 | | | WHICH WAS NOT PROVIDED BUT REVIEW OF THE MAIN PLUMBING | | | PLANS SHOWS THE POOL BACKWASH DRAINING INTO THE | | | SANITARY SYSTEM WHICH IS PROHIBITED PER SEC. 90-126 (5) | | | WPB. | | | | | | 6) 2ND REQUEST. THE RESPONSE NARRATIVE INDICATES THE | | | BRIDGE ROOF DRAINAGE ON NEW SHEET P-2.1.4 WHICH WAS NOT | | | UPLOADED FOR REVIEW. | | | SHEETS P-2.2.3, P-2.2.5 & P-5.2.5: PLEASE PROVIDE A | | | DIMENSIONED BRIDGE ROOF DRAINAGE PLAN THAT SHOWS THE | | | LOCATIONS OF THE PRIMARY AND SECONDARY (OVERFLOW) ROOF | | | DRAINS, RAINFALL RATE, AND GPM FLOW AT THE RD LOCATION- | | | SEC. 1105.1 & 1106.1 FBC P. THE RESPONSE NARRATIVE | | | INDICATES A THE ROOF DRAINAGE ON NEW SHEET P-2.1.4 | | | WHICH WAS NOT UPLOADED FOR REVIEW. | | | | | | 7) 2ND REQUEST. MINIMUM REQUIRED APPLICATIONS FOR THE | | | POTABLE WATER BACKFLOW PREVENTER AND GREASE INTERCEPTOR | | | NOT PROVIDED. PLEASE NOTE THAT SEPARATE PERMITS ARE | | | REQUIRED FOR THE POTABLE WATER BACKFLOW PREVENTER, | | | GREASE INTERCEPTOR, IRRIGATION, IRRIGATION BACKFLOW, | | | AND POOL. IF REQUESTED GAS CAN ALSO BE UNDER A SEPARATE | | | PERMIT. DUE TO A CHANGE IN PROCESS, THE BACKFLOW AND | | | GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED | | | PRIOR TO APPROVAL OF THE PLUMBING REVISION. YOU CAN | | | SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO | | | NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED | | | PERMIT APPLICATION TO [email protected] . YOU | | | WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. | | | YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT | | | THE APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND | | | THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. | | | AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA | | | EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. | | | | | | NEW COMMENTS BASED ON RESUBMITTED PLANS AND EMAIL | | | CORRESPONDENCE WITH THE ENGINEER. | | | | | | 1) SHEETS A-1.2.1, P-2.2.1, P-5.2.4: MISSING FROM THE | | | NEW PLUMBING FIXTURE CALCULATIONS AND APPARENTLY FROM | | | THE PLAN IS THE REQUIRED SERVICE SINK. THE CALCULATIONS | | | DO OMIT VITAL INFORMATION INCLUDING THE OCCUPANCY | | | CLASSIFICATIONS AND OCCUPANT LOADS FOR EACH | | | CLASSIFICATION, HOWEVER BASED ON THE PLANS AND TABLE | | | 403.1 IT APPEARS A COMPLIANT NUMBER OF WATER CLOSETS | | | AND LAVATORIES HAVE BEEN PROVIDED FOR THE POOL, AND THE | | | A AND B OCCUPANCIES. IT IS ACKNOWLEDGED THAT FUTURE | | | BATHROOMS WILL UNDER THE RETAIL BUILD-OUT PERMIT. | | | | | | 2) P-2.2.1 & P-5.2.4: 2ND REQUEST TO REVISE THESE | | | SHEETS TO SHOW POOL WASTEWATER DISCHARGE DECHLORINATED | | | AND DRAINED INTO THE STORM SYSTEM. | | | | | | 3) P-5.2.4: RISER #14 SHOWN IN THE ISO IS NOT SHOWN ON | | | RISER SHEETS P-5.2.2 OR P-5.2.3- SEC. 107.2.1 WPB. | | | | | | 4) P-2.2.1 & P-5.2.4: THE 8-INCH MAIN BUILDING DRAIN | | | LINE SHOWING 1622 DFU'S IS UNDERSIZED PER TABLE | | | 710.1(1) AT 1/8-INCH PER FT. SLOPE. | | | | | | 5) P-5.2.6: THE EQUIPMENT SCHEDULES FOR THE STORAGE AND | | | TANKLESS WATER HEATERS SHOWN ON THE ISO ARE NOT SHOWN | | | ON SHEET P-6.2.2 AND NO INSTALLATION DETAILS PROVIDED | | | SUCH AS THE DETAIL PROVIDED FOR THE APARTMENT UNITS ON | | | P-6.2.1. THE DETAIL SHOULD SHOW THE MASTER THERMOSTATIC | | | MIXING VALVE AND THE MEANS OF CONTROLLING EXPANSION- | | | SECS. 607.1.1 & 607.3. | | | | | | 6) P-5.2.6: NO INFO OR DETAILS PROVIDED FOR REQUIRED | | | TEMPERED WATER DELIVERY AT LAVS, MASTER THERMOSTATIC | | | MIXING VALVES AT WATER HEATERS TO LIMIT HOT WATER | | | TEMPERATURE DELIVERY, AND NO HW PIPE INSULATION SPECS- | | | SECS. 419.5, 607.1.1, 606.2.1, AND TABLE C403.2.10. | | | | | | 7) P-5.2.6: THE LENGTHS OF HW FIXTURE SUPPLY PIPES TO | | | THE LAVS IN GANG BATHROOM ARE EXCEEDING THE MAX 2FT. | | | ALLOWABLE LENGTHS- TABLE C404.5.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS ST. | | | WEST PALM BEACH, FL. 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-25 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-25 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-24 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2022-10-31 11:49:38 | PERMIT 22100341- REVISED PLUMBING PLANS DENIED. | | | 10/28/22 | | | | | | COMMENTS. | | | | | | 1) SHEET P-5.2.6: PLEASE REVISE THE RISER TO SHOW THE | | | 1-INCH COMMERCIAL SERVICE LINE RUN TO THE FUTURE RETAIL | | | SPACE- SEC. 107.3.5.1.3 FBC P. SHOW A SHUT-OFF VALVE | | | AND CAP WILL PROVIDED AT THE ENTRANCE TO THE RETAIL | | | SPACE. | | | 2) P-5.2.6: PROVIDE CORRELATING TEXT FOR THE NUMBERED | | | NOTES 1-4 ON THE RISER- SEC. 107.2.1 WPB. | | | | | | | | | 3) P-5.2.6: PROVIDE AN RPZ BACKFLOW PREVENTER FOR THE | | | WATER LINE TO THE SPA EQUIPMENT- SEC. 608.17.4.1 FBC P | | | AND SECS. C, D, & E- WPB CROSS CONNECTION MANUAL. | | | PLEASE PROVIDE EQUIPMENT SCHEDULES FOR BOTH THE SPA AND | | | POOL BF PREVENTERS- SEC. 608.3 FBC P. | | | | | | 4) P-2.2.1: DETAIL P-6 FOR POOL AND SPA BACKWASH | | | DRAINAGE IS REFERENCED ON THE PLAN. THE DETAIL IS | | | 11/P-6.2.1 WHICH WAS NOT PROVIDED BUT REVIEW OF THE | | | MAIN PLUMBING PLANS SHOWS THE POOL BACKWASH DRAINING | | | INTO THE SANITARY SYSTEM WHICH IS PROHIBITED PER SEC. | | | 90-126 (5) WPB. PLEASE NOTE THE FOLLOWING: | | | | | | SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY | | | SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES | | | DEPARTMENT. | | | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY | | | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED | | | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM | | | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S | | | SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW | | | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL | | | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: | | | THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO | | | KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE | | | INLET). | | | NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE | | | INLET TO DISCHARGE EFFLUENT. | | | WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED | | | TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS | | | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. | | | DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING | | | PROPERTY. | | | FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT O&M | | | SUPERINTENDENT STEPHON HARRIS AT [email protected] OR | | | 561-822-2168. | | | FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE | | | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE | | | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) | | | 822-2062 OR [email protected]. | | | | | | 5) P-2.2.2.1: PLEASE SHOW THE LOCATION OF THE FUTURE | | | SANITARY DRAIN PIPING FOR THE RETAIL SPACE. THIS SPACE | | | APPEARS TO BE ISOLATED FROM THE MAIN FLOOR. PLEASE | | | CLARIFY IF PLUMBING FIXTURES FOR THE OCCUPANTS WILL BE | | | PROVIDED IN ACCORDANCE WITH TABLE 403.1. | | | | | | 6) SHEETS P-2.2.3, P-2.2.5 & P-5.2.5: PLEASE PROVIDE A | | | DIMENSIONED BRIDGE ROOF DRAINAGE PLAN THAT SHOWS THE | | | LOCATIONS OF THE PRIMARY AND SECONDARY (OVERFLOW) ROOF | | | DRAINS, RAINFALL RATE, AND GPM FLOW AT THE RD LOCATION- | | | SEC. 1105.1 & 1106.1 FBC P. | | | | | | 7) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR | | | THE POTABLE WATER BACKFLOW PREVENTER, GREASE | | | INTERCEPTOR, IRRIGATION, IRRIGATION BACKFLOW, AND POOL. | | | IF REQUESTED GAS CAN ALSO BE UNDER A SEPARATE PERMIT. | | | DUE TO A CHANGE IN PROCESS, THE BACKFLOW AND GREASE | | | INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR | | | TO APPROVAL OF THE PLUMBING REVISION. YOU CAN SUBMIT AN | | | APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A | | | CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT | | | APPLICATION TO [email protected] . YOU WILL | | | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU | | | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE | | | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT | | | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER | | | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL | | | AND I WILL CHANGE THE REVIEW STATUS TO PASS. | | | | | | 8) SHEET- P-2.2.2.1: THE POOL IS UNDER SEPARATE PERMIT | | | HOWEVER PLEASE SHOW THE LOCATIONS OF THE REQUIRED | | | SANITARY FACILITIES AND PROVIDE PLUMBING FIXTURE | | | CALCULATIONS PER TABLES 403.1, 403.6, AND SEC. 403.1.1 | | | FBC P. THE PLAN APPEARS TO SHOW THE BATHROOMS ON THE | | | FIRST FLOOR ARE FOR OCCUPANTS OF THE POOL AND DECK, AND | | | THE OCCUPANTS OF THE BUILDING- PLEASE CLARIFY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS ST. | | | WEST PALM BEACH, FL. 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2023-01-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-04 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-04 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2023-01-04 16:28:02 | A SEPARATE PERMIT AND PLAN SUBMITTAL ARE REQUIRED FOR | | | INSTALLATION OF THE GREASE INTERCEPTOR. |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2023-01-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-04 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-04 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2023-01-04 16:28:58 | A SEPARATE PERMIT AND PLAN SUBMITTAL ARE REQUIRED FOR | | | INSTALLATION OF THE IRRIGATION SYSTEM. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2023-06-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-22 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-22 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2023-06-22 11:24:32 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS A-0.3 DOES NOT SHOW AS DIGITALLY SIGNED IN | | | ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-14 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-14 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-12-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-21 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-21 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2022-12-21 14:13:16 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS A3.2.1, A5.2.2 DOES NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-01 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-01 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2022-11-01 13:51:47 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING S-2.2.9 DOES NOT SHOW AS DIGITALLY SIGNED IN | | | ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
2023-07-07 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
2023-07-07 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2023-07-07 09:00:30 | | | | 1. PLEASE MAKE SURE TO ADD REVISIONS DATES TO PLANS | | | WHEN RESUBMITTING. | | | 2. THE PROJECT IS REQUIRED TO COMPLY WITH THE ARTLIFE | | | ORDINANCE, PLEASE RESPOND ON HOW THE PROJECT HAS | | | COMPLIED. | | | 3. PLEASE CONFIRM THAT THE STREETLIGHTS PROPOSED COMPLY | | | WITH DOWNTOWN LIGHT STANDARDS, AND IN WHICH DRAWING | | | SHOWS. | | | 4. MECHANICAL EQUIPMENT ON ROOF SHALL BE SCREENED WITH | | | A WALL OR SCREENING AS TALL AS THE EQUIPMENT. | | | 5. AN AERIAL EASEMENT SHALL BE APPROVED BY CITY | | | COMMISSION BEFORE T.C.O. | | | | | | THE FOLLOWING ITEMS SHALL BE ADDRESSED PRIOR TO | | | ISSUANCE OF FINAL CO: | | | 1. A MINOR SITE PLAN AMENDMENT APPLICATION WILL NEED TO | | | BE SUBMITTED AND APPROVED BY THE PLANNING DIVISION | | | PRIOR CO. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF ANY HARDSCAPE, | | | LANDSCAPING AND IRRIGATION, AND ANY OTHER DECORATIVE | | | ELEMENT INSTALLED WITHIN THE RIGHT OF WAY BY THIS | | | PROJECT. APPROVAL OF A MAINTENANCE AGREEMENT BETWEEN | | | THE CITY AND THE APPLICANT, SUCCESSORS AND ASSIGNS WILL | | | BE REQUIRED BEFORE FINAL CO. THE PROPOSED LANDSCAPE | | | ALONG DIXIE HIGHWAY WILL REQUIRE APPROVAL FROM FDOT AND | | | A MAINTENANCE AGREEMENT. | | | 3. PROJECT WILL BE REQUIRED TO CONTRIBUTE TO A TRANSIT | | | FEE EQUAL TO $10/MONTH PER EACH MICRO UNIT INCLUDED IN | | | THE PROJECT. THE FIRST PAYMENT WILL BE DUE AT THE TIME | | | OF FINAL CO. | | | | | | CLAUDIA D. IBAVEN | | | CITY URBAN DESIGNER / ZONING AND PLANNING | | | [email protected] | | | 561-822-1402 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
2023-03-27 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
2023-03-27 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2023-03-27 16:45:17 | CLAUDIA D. IBAVEN | | | CITY URBAN DESIGNER / PLANNING DIVISION | | | [email protected] | | | 561-822-1402 | | | | | | I HAVE REVIEWED PERMIT NO. 22100341 AND PROVIDE THE | | | FOLLOWING COMMENTS: | | | 1) SHEETS L1-6-01 AND L1-6-02 SHOW THAT VEGETATED AREA | | | REQUIRED IS NOT MET FOR THE PRIVATE OPEN SPACE NAMED | | | POOL AREA. PLEASE REVISE PLANS TO MEET REQUIREMENT. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-01-23 |
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
2023-01-23 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
2023-01-23 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2023-01-23 13:50:39 | ZONING AND PLANNING | | | PROJECT: CIELO 740 N DIXIE HWY | | | PERMIT NO. 22100341 | | | DATE: JANUARY 23, 2023 | | | CONTACT: CLAUDIA IBAVEN, CITY URBAN DESIGNER, AT | | | 561-822-1402 OR VIA [email protected]. | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | AS NOTED IN PREVIOUS COMMENTS SOME FLOOR PLANS SHEETS | | | INDICATE CHANGES TO WINDOWS AND DOORS. BELOW SOME | | | QUESTIONS FROM RESPONSES RECEIVED. | | | | | | SHEET A-3.2.1 | | | WEST ELEVATION: IT WAS PREVIOUSLY MENTIONED THAT | | | WINDOWS BETWEEN CERTAIN GRIDS ONLY CHANGED THEIR | | | MULLIONS TO COMPLY WITH MECHANICAL VENTILATION | | | REQUIREMENTS, ARE CHANGES ON ALL WINDOWS ON ALL FLOOR | | | LEVELS OR CERTAIN FLOOR LEVELS? HAVE ANY OF THEM CHANGE | | | IN SIZE? | | | NORTH ELEVATION: THERE SEEMS TO BE A CHANGED IN THE | | | WINDOW BELOW THE PEDESTRIAN BRIDGE, PLEASE CONFIRM AND | | | EXPLAIN CHANGE. | | | | | | SHEET A-3.2.2 | | | EAST ELEVATION: IN ADDITION TO THE NANAWALL CHANGE, ON | | | THE GROUND FLOOR BETWEEN GRIDS 12 AND 11 THERE SEEMS TO | | | BE A CHANGE, IS THIS CHANGE ONLY REMOVING THE | | | ???CONCRETE EYEBROW??? FROM THE WINDOW? | | | SOUTH ELEVATION: PLEASE, CONFIRM IF NO CHANGES WERE | | | MADE TO THE SOUTH ELEVATION. | | | | | | OTHER COMMENTS: | | | HAS ANY OF THE MATERIALS LISTED IN THE ELEVATION LEGEND | | | CHANGED FROM WHAT WAS ORIGINALLY APPROVED BY DAC? | | | | | | ARE ANY CHANGES IN GRADING, PAVING AND DRAINAGE PLANS | | | AFFECTING OPEN SPACE AREAS AND POTENTIALLY CHANGE | | | LANDSCAPE SHEETS AND CALCULATIONS FOR REQUIRED FOR OPEN | | | SPACE, VEGETATED AREA, AND TREE CANOPY AS SEEN ON SHEET | | | APPROVED 050- L-1-6-01 OPEN SPACE DIAGRAM IN MASTER | | | PERMIT? | | | | | | PLEASE CONFIRM THAT MECHANICAL EQUIPMENT ON ROOF IS | | | SCREENED WITH A WALL OR SCREENING AS TALL AS THE | | | EQUIPMENT. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2022-12-05 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2022-12-05 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2022-12-05 10:23:12 | PLEASE INCLUDE A NARRATIVE OF THE CHANGES PROPOSED. | | | PLEASE EXPLAIN WHAT ARE THA CHANGES ON THE WINDOWS AND | | | HOW IT AFFECTS THE ELEVATION. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|