| 2022-10-27 14:51:49 | RESIDENTIAL R(3) REVISION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | |
| | REVISION#22100334 |
| | 6205 WASHINGTON RD |
| | |
| | ORIGINAL BUILDING PROVISO: |
| | 1- OK. |
| | 2- OK. |
| | 3- OK. |
| | 4- OK. |
| | 5- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 6- SOFFIT CONSTRUCTION DETAIL ON WALL SECTIONS: |
| | ENGINEER TO SPECIFY TYPE OF METAL PLASTER BASE FOR |
| | CEILINGS SHOWING COMPLIANCE WITH TABLE 3 OF ASTM C1063. |
| | NOTE: ALSO, PROVIDE DETAIL/SPECIFICATIONS FOR CEILING |
| | CONSTRUCTION AT NEW MASTER LANAI. |
| | |
| | RESPONSE: |
| | UNABLE TO VERIFY COMPLIANCE WITH TABLE 3 OF ASTM C1063. |
| | ENGINEER DOESN'T SPECIFY TYPE OF METAL PLASTER BASE. |
| | ENGINEER TO SEE TABLE 3 AND PROVIDE REQUIRED |
| | INFORMATION BASED ON THE FRAMING MEMBER SPACING. |
| | |
| | 7- OK. |
| | 8- OK. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL FOR: |
| | |
| | ORIGINAL COMMENT: |
| | A)EXTERIOR DOORS. JELD-WEN FLORIDA PRODUCT APPROVAL |
| | FL16708-R13 IS INCOMPLETE. NEED INSTALLATION |
| | INSTRUCTIONS DRAWINGS. |
| | |
| | RESPONSE: |
| | NEW DOOR ON FLORIDA PRODUCT APPROVAL FL21133.31 |
| | SUBMITTED DOESN'T MEET THE DESIGN PRESSURES CALCULATED |
| | BY THE ENGINEER OF RECORD. NEED PRODUCT APPROVAL THAT |
| | MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES. |
| | |
| | ORIGINAL COMMENT: |
| | B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO VERIFY PRESSURES. |
| | |
| | RESPONSE: |
| | NO SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | C)ROOF TILE. OK. REVISED TO METAL ROOF. ROOFING PRODUCT |
| | APPROVALS REVIEWED UNDER SEPARATE ROOFING PERMIT |
| | 22060713. |
| | |
| | ORIGINAL COMMENT: |
| | 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS. |
| | |
| | 11- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | |
| | NEW COMMENT: |
| | G) ENERGY CALCULATIONS SUBMITTED WERE NOT SIGNED BY THE |
| | ENGINEER OF RECORD AS DONE ON THE ORIGINAL SUBMITTAL. |
| | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | |
| | ORIGINAL COMMENTS: |
| | A)OK. |
| | B) OK. |
| | |
| | ORIGINAL COMMENT: |
| | C)DOORS ORIENTATION DOESN'T MATCH PLANS. |
| | |
| | RESPONSE: |
| | ORIENTATION OF DOORS WAS REVISED BUT BASED ON EXTERIOR |
| | ELEVATIONS THE MASTER BEDROOM DOOR IS A GLAZED DOOR. |
| | THIS DOOR NEEDS TO BE UNDER THE GLAZING AREA. REVISE AS |
| | REQUIRED. SEC. R405.5.3.3 FBC-ENERGY CONSERVATION. |
| | |
| | ORIGINAL COMMENT: |
| | D)REVISE WINDOWS INFORMATION ON PAGE 4. WINDOWS |
| | ORIENTATION, MATERIAL, AND OVERHANG DEPTH AND |
| | SEPARATION TO MATCH PLANS. |
| | |
| | RESPONSE: |
| | WINDOWS OVERHANG DEPTH DOESN'T MATCH PLANS. SEC. |
| | R405.5.3.3 FBC-ENERGY CONSERVATION. SEE ELEVATIONS. |
| | NOTE: THERE IS A NOTE FOR AWNING ON THE FLOOR PLAN BUT |
| | AWNINGS SHALL NOT BE CONSIDERED AS OVERHANGS. |
| | |
| | ORIGINAL COMMENT: |
| | E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | F)OK. |
| | |
| | NEW COMMENT: |
| | G) ENERGY CALCULATIONS SUBMITTED WERE NOT SIGNED BY THE |
| | ENGINEER OF RECORD. |
| | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |