Plan Review Details - Permit 22100325
Plan Review Stops For Permit 22100325
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-15 Cont ID  
Sent By rwbrown Date 2022-11-15 Time 06:17 Rev Time 0.00
Received By rwbrown Date 2022-11-14 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-11-08 Time   Rev Time 0.00
Received By aoliver Date 2022-11-07 Time 16:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-15 Cont ID  
Sent By rwbrown Date 2022-11-15 Time 06:17 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By ccole Date 2022-11-08 Time 10:36 Rev Time 0.00
Received By ccole Date 2022-11-07 Time 16:13 Sent To  
Notes
2022-11-08 10:37:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100940
 11/8/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A FIRESTOPPING ASSEMBLY FOR THE PIPE
 PENETRATION THROUGH THE FIRE-RATED CONCRETE FLOOR- SEC.
 403.1 FBC EXISTING BUILDING & SEC. 315.1 FBC PLUMBING.
 PLEASE NOTE THAT SEC. 315.1 REFERENCES SEC. 714 FBC
 BUILDING CODE. PLEASE REVIEW THE FIRESTOPPING FOLLOWING
 METHODS IN THE CODE AND PROVIDE A UL APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN, OR IDENTIFY
 ON THE PLAN THEY TYPE OF ASSEMBLY TO BE INSTALLED AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 A) SEC. 714.5.1 EXCEPTION 1: THE ANNULAR SPACE BETWEEN
 THE FLOOR AND THE CAST IRON PIPE CAN BE SEALED WITH
 MATERIALS THAT PREVENT THE PASSAGE OF FLAME AND HOT
 GASES SUFFICIENT TO IGNITE COTTON WASTE WHEN SUBJECTED
 TO ASTM E119 OR UL 263.
 B) SEC. 714.5.1 EXCEPTION 2: THE ANNUAL SPACE CAN BE
 SEALED WITH CONCRETE, GROUT, OR MORTAR THE FULL
 THICKNESS OF THE FLOOR REQUIRED TO MAINTAIN THE
 FIRE-RESISTANCE RATING.
 C) SEC. 714.5.1.: THE THROUGH PENETRATION CAN BE
 PROTECTED USING SYSTEMS INSTALLED AS TESTED IN THE
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
 D) SEC. 714.5.1.2: THROUGH PENETRATIONS SHALL BE
 PROTECTED BY AN APPROVED THROUGH-PENETRATION FIRESTOP
 SYSTEM INSTALLED AND TESTED IN ACCORDANCE WITH ASTM
 E814 OR UL 1479, WITH A MINIMUM POSITIVE PRESSURE
 DIFFERENTIAL OF 0.01 INCH OF WATER (2.49 PA). THE
 SYSTEM SHALL HAVE AN F RATING/T RATING OF NOT LESS THAN
 1 HOUR BUT NOT LESS THAN THE REQUIRED RATING OF THE
 FLOOR PENETRATED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-11-17 Cont ID  
Sent By shill Date 2022-11-17 Time 11:09 Rev Time 0.00
Received By shill Date 2022-11-17 Time 11:08 Sent To  
Notes
2022-11-17 11:09:33INSPECTIONS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-11-08 Cont ID  
Sent By ccole Date 2022-11-08 Time 10:37 Rev Time 0.00
Received By ccole Date 2022-11-07 Time 16:13 Sent To  
Notes
***NONE***