| 2022-11-08 10:37:11 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22100940 |
| | 11/8/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A FIRESTOPPING ASSEMBLY FOR THE PIPE |
| | PENETRATION THROUGH THE FIRE-RATED CONCRETE FLOOR- SEC. |
| | 403.1 FBC EXISTING BUILDING & SEC. 315.1 FBC PLUMBING. |
| | PLEASE NOTE THAT SEC. 315.1 REFERENCES SEC. 714 FBC |
| | BUILDING CODE. PLEASE REVIEW THE FIRESTOPPING FOLLOWING |
| | METHODS IN THE CODE AND PROVIDE A UL APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN, OR IDENTIFY |
| | ON THE PLAN THEY TYPE OF ASSEMBLY TO BE INSTALLED AND |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS. |
| | |
| | A) SEC. 714.5.1 EXCEPTION 1: THE ANNULAR SPACE BETWEEN |
| | THE FLOOR AND THE CAST IRON PIPE CAN BE SEALED WITH |
| | MATERIALS THAT PREVENT THE PASSAGE OF FLAME AND HOT |
| | GASES SUFFICIENT TO IGNITE COTTON WASTE WHEN SUBJECTED |
| | TO ASTM E119 OR UL 263. |
| | B) SEC. 714.5.1 EXCEPTION 2: THE ANNUAL SPACE CAN BE |
| | SEALED WITH CONCRETE, GROUT, OR MORTAR THE FULL |
| | THICKNESS OF THE FLOOR REQUIRED TO MAINTAIN THE |
| | FIRE-RESISTANCE RATING. |
| | C) SEC. 714.5.1.: THE THROUGH PENETRATION CAN BE |
| | PROTECTED USING SYSTEMS INSTALLED AS TESTED IN THE |
| | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. |
| | D) SEC. 714.5.1.2: THROUGH PENETRATIONS SHALL BE |
| | PROTECTED BY AN APPROVED THROUGH-PENETRATION FIRESTOP |
| | SYSTEM INSTALLED AND TESTED IN ACCORDANCE WITH ASTM |
| | E814 OR UL 1479, WITH A MINIMUM POSITIVE PRESSURE |
| | DIFFERENTIAL OF 0.01 INCH OF WATER (2.49 PA). THE |
| | SYSTEM SHALL HAVE AN F RATING/T RATING OF NOT LESS THAN |
| | 1 HOUR BUT NOT LESS THAN THE REQUIRED RATING OF THE |
| | FLOOR PENETRATED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |