Plan Review Details - Permit 22100273
| Plan Review Stops For Permit 22100273 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-16 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-16 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2022-11-16 10:37:33 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: 3-D RENDERINGS ARE NOT AN ACCEPTABLE MEDIUM FOR | | | PLAN REVIEW OR PUBLIC RECORD STORAGE. | | | | | | 1. PROVIDE AN EXISTING FLOOR PLAN OF THE ENTIRE | | | STRUCTURE. INDICATE AREA OF PROP-OSED WORK. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 2. PROVIDE A PROPOSED FLOOR PLAN. INDICATE AREA OF NEW | | | WORK. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 3. PROVIDE CONSTRUCTION DRAWINGS WITH DEMENSIONS OF | | | SHOWER ENCLOSURE, AREA AROUND WATER CLOSET AND GENERAL | | | ROOM DEMENSIONS. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-10-31 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-31 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-31 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2022-10-31 15:00:05 | ELECTRIC REVIEW FAILED | | | 1) PLEASE PROVIDE AN ELECTRICAL PLAN FOR REVIEW. FBC | | | 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-16 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-17 |
Time |
07:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-18 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-18 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-18 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2022-10-18 12:21:59 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.2.1 - IS THE LANDRY SINK AND | | | WASHER NEW CONNECTIONS, OR EXISTING? IF THEY ARE NEW, | | | THEN PLEASE PROVIDE A PLUMBING RISER SHOWING THE PROPER | | | DRAIN, WASTED AND VENT CONNECTIONS. | | | | | | 2. 2017 WPB AMENDS 107.2.1 - SHOW AN EXISTING FLOOR | | | PLAN AND A NEW FLOOR PLAN FOR CONTRAST TO DETERMINE THE | | | SCOPE OF WORK. IF THIS BATHROOM IS IN A NEW SPACE, | | | PLEASE DETAIL THE WIDTH MEASUREMENTS OF THE BATHROOM. | | | THE DRAWINGS SEEMS TO INDICATE THAT EACH FIXTURE MAY | | | NOT HAVE THE MINIMUM CLEARANCE FOR EACH. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | REFERENCED CODES: | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-16 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-16 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2022-11-16 10:29:03 | 1ST SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | | | | 1.THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD | | | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN | | | SHEETS UNDER THEIR AUTHORITY. | | | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, SECTION 107.2.1. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-10-20 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-10-20 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2022-10-20 15:49:41 | 10/20/22 FAILED | | | | | | PLEASE PROVIDE A SCOPE OF WORK. IF YOU ARE PROPOSING | | | THE ADDITION OF A BAHROOM THAT WOULD INCREASE THE | | | BUILDING FOOTPRINT, YOU NEE TO SHOW THE IMPROVEMENT ON | | | A SURVEY. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 |
|
|
|