Plan Review Details - Permit 22100245
Plan Review Stops For Permit 22100245
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2023-01-05 Cont ID  
Sent By cpuell Date 2023-01-05 Time 14:36 Rev Time 0.00
Received By cpuell Date 2023-01-05 Time 14:36 Sent To  
Notes
2023-01-05 14:37:03ADDITIONAL PERMITS APPLIED FOR 22120832, 22120833,
 22120834, 22120835, 22120836, 22120837,22120838,
 22120839, 22120840, 22120841 & 22120842

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2022-12-05 Cont ID  
Sent By cpuell Date 2022-12-05 Time 12:15 Rev Time 0.00
Received By cpuell Date 2022-12-05 Time 12:15 Sent To  
Notes
2022-12-05 12:17:50THE ROW PERMIT APPLICATION UPLOADED HAS NOTHING TO DO
 WITH A FENCE PERMIT, A RIGHT OF WAY PERMIT IF AN
 ENGINERING PERMIT AND IS APPLIED FOR DIFFERENTLY THAN A
 FENCE PERMIT. SEPARATE PERMITS ARE REQUIRED FOR EACH
 PARCEL, PLEASE PROVIDE THE PERMIT NUMBERS FOR ALL THE
 PARCELS APPLIED FOR TO [email protected] OR CALL
 561-805-6659

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-11-30 Cont ID  
Sent By cpuell Date 2022-11-30 Time 10:41 Rev Time 0.00
Received By cpuell Date 2022-11-30 Time 10:41 Sent To  
Notes
2022-11-30 10:45:25PLEASE PROVIDE A COPY OF THE LEVEL 3 SPECIAL REVIEW
 SITE PLAN ADDRESSING THE PARCELS ON THE SITE. PLEASE
 RESPOND TO [email protected] OR CALL 561-805-6659

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-10-13 Cont ID  
Sent By cpuell Date 2022-10-13 Time 10:13 Rev Time 0.00
Received By cpuell Date 2022-10-13 Time 10:13 Sent To  
Notes
2022-10-13 10:26:00PLEASE PROVIDE A SITE PLAN SHOWING THE PARCEL AFFECTED
 BY THIS WORK, THE APPLICATION LISTS 2501 PINEWOOD AVE
 HOWEVER THE PARCEL SPACE AND THE PLANS. I DO SEE IN THE
 SKETCH SURVEY DOCUMENTS THAT WAS PROVIDED THAT MULTIPLE
 ADDRESSES AND PARCELS ARE LISTED. A UNITY OF TITLE WILL
 BE NEEDED YOU WILL NEED TO CONTACT VINCE NOEL
 [email protected] OR CALL 561-494-1040 TO START THE UNITY
 OF TITLE PROCEDURE. ONCE THE UNITY OF TITLE IS
 RECORDED, YOU WILL NEED TO GO FILL OUT PALM BEACH
 COUNTY???S PARCEL COMBINATION REQUEST FORM WHICH CAN BE
 FOUND AT THIS LINK
 HTTPS://WWW.PBCGOV.ORG/PAPA/DEPARTMENTS/GIS.HTM, THEY
 WILL ISSUE YOU WITH A UNIFIED PARCEL CONTROL NUMBER
 (PCN). WHEN YOU CONTACT THE PROPERTY APPRAISERS YOU
 NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED PCN.
 ONCE YOU HAVE RECEIVED THE PRELIMINARY LETTER PLEASE
 CONTACT [email protected] OR CALL 561-805-6659 TO BE
 ISSUED AN ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-04-19 Cont ID  
Sent By rmcphers Date 2023-04-19 Time 07:39 Rev Time 0.00
Received By rmcphers Date 2023-04-19 Time 07:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-04-17 Cont ID  
Sent By rmcphers Date 2023-04-17 Time 13:03 Rev Time 0.00
Received By rmcphers Date 2023-04-17 Time 13:03 Sent To  
Notes
2023-04-17 13:07:22SOIL IMPROVEMENTS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING SP200 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED
 IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-21 Cont ID  
Sent By rmcphers Date 2023-03-21 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2023-03-21 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-01 Cont ID  
Sent By rmcphers Date 2022-12-01 Time 14:55 Rev Time 0.00
Received By rmcphers Date 2022-12-01 Time 14:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 13:44 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 13:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2023-04-20 Cont ID  
Sent By lquinone Date 2023-04-20 Time 19:49 Rev Time 0.00
Received By lquinone Date 2023-04-20 Time 19:48 Sent To  
Notes
2023-04-20 19:52:06PASSED WITH PROVISO: WORK WITHIN ROW SHALL NOT COMMENCE
 UNTIL ROW PERMIT APPLICATION HAVE BEEN APPROVED BY
 CITY.
  
 THANKS,
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2023-03-20 Cont ID  
Sent By rrossano Date 2023-03-20 Time   Rev Time 0.00
Received By rrossano Date 2023-03-20 Time   Sent To  
Notes
2023-03-20 09:34:27PASSED WITH PROVISO: WORK WITHIN ROW SHALL NOT COMMENCE
 UNTIL ROW PERMIT APPLICATIONS HAVE BEEN APPROVED BY
 CITY.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2023-03-13 Cont ID  
Sent By rrossano Date 2023-03-13 Time   Rev Time 0.00
Received By rrossano Date 2023-03-13 Time   Sent To  
Notes
2023-03-13 12:36:03PASSED WITH PROVISO: OBTAIN PERMIT FOR WORK IN ROW.
  
 THANKS,
  
 RICK ROSSANO, SENIOR PROJECT COORD.
 WPB ENG. SERVICES DEPT., 561-494-1098, FAX:
 561-494-1116 [email protected]
  
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-12-13 Cont ID  
Sent By rrossano Date 2022-12-13 Time   Rev Time 0.00
Received By rrossano Date 2022-12-13 Time   Sent To  
Notes
2022-12-13 15:22:40SITE PLAN STILL UNDER REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-12-02 Cont ID  
Sent By rrossano Date 2022-12-02 Time   Rev Time 0.00
Received By rrossano Date 2022-12-02 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-04-13 Cont ID  
Sent By pleduc Date 2023-04-13 Time   Rev Time 0.00
Received By pleduc Date 2023-04-13 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By pleduc Date 2022-11-28 Time   Rev Time 0.00
Received By pleduc Date 2022-11-28 Time 10:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-11 Cont ID  
Sent By pleduc Date 2022-10-11 Time   Rev Time 0.00
Received By pleduc Date 2022-10-11 Time 11:51 Sent To  
Notes
2022-10-11 15:43:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) A DETAILED LIFE SAFETY REVIEW COULD NOT BE COMPLETED
 DUE TO NO PROPOSED OCCUPANCY LIFE SAFETY PLANS WERE
 ATTACHED.
  
 NEW WALLS OR NEW COLUMNS MAY AFFECT PROPOSED EXTING,
 EXIT TRAVEL PATHS AND TRAVEL DISTANCES.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN IN THE RELATED AREAS.
  
 FYI - SHOULD THE LIFE SAFETY PLANS NOT BE AFFECTED AT
 THIS TIME AND/OR WILL BE ADDRESSED ON FUTURE SUBMITTALS
 PLEASE PROVIDE A DETAILED NOTE OF ACKNOWLEDGMENT BY THE
 DESIGNER OR EOR.
  
  
 1A) THERE IS NO INDICATION OF WHAT IS EXISTING AND WHAT
 IS NEW.
  
 FOR CLARITY, PLEASE PROVIDE DETAILS OF EXISTING AND
 NEW.
  
 FYI - SHOULD THE EXISTING/NEW NOT AFFECT LIFE SAFETY
 PLAN AT THIS TIME AND/OR WILL BE ADDRESSED ON FUTURE
 SUBMITTALS PLEASE PROVIDE A DETAILED NOTE OF
 ACKNOWLEDGMENT BY THE DESIGNER OR EOR.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-05-08 Cont ID  
Sent By lmarchan Date 2023-05-08 Time 15:54 Rev Time 0.00
Received By lmarchan Date 2023-04-12 Time 09:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-04 Cont ID  
Sent By lmarchan Date 2023-04-04 Time 12:45 Rev Time 0.00
Received By lmarchan Date 2023-03-16 Time 06:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-11 Cont ID  
Sent By lmarchan Date 2023-01-11 Time 11:14 Rev Time 0.00
Received By lmarchan Date 2022-12-05 Time 07:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-02 Cont ID  
Sent By lmarchan Date 2022-12-02 Time 12:31 Rev Time 0.00
Received By lmarchan Date 2022-11-23 Time 08:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-21 Cont ID  
Sent By asangele Date 2022-11-21 Time 11:58 Rev Time 0.00
Received By asangele Date 2022-11-21 Time 11:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-04-19 Cont ID  
Sent By rmcphers Date 2023-04-19 Time 07:39 Rev Time 0.00
Received By rmcphers Date 2023-04-19 Time 07:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-04-17 Cont ID  
Sent By rmcphers Date 2023-04-17 Time 13:08 Rev Time 0.00
Received By rmcphers Date 2023-04-17 Time 13:08 Sent To  
Notes
2023-04-17 13:10:09SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING SP200 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED
 IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-21 Cont ID  
Sent By rmcphers Date 2023-03-21 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2023-03-21 Time 09:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-10 Cont ID  
Sent By ccole Date 2023-01-10 Time 14:53 Rev Time 0.00
Received By ccole Date 2023-01-10 Time 14:48 Sent To  
Notes
2023-01-10 15:03:451ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 2210245
 1/10/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET : THE VIBROPLACMENT PHASING PLAN REQUIRES THE
 DIGITAL SIGNATURE AND SEAL OF THE ARCHITECT FOR
 APPROVAL- SEC. FL. STATUTE 481.221 AND SEC. 61G1-16.005
 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-01 Cont ID  
Sent By rmcphers Date 2022-12-01 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2022-12-01 Time 14:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 13:46 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 13:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2023-05-08 Cont ID  
Sent By eschneid Date 2023-05-08 Time 11:55 Rev Time 3.00
Received By eschneid Date 2023-05-04 Time 09:48 Sent To  
Notes
2023-05-08 11:55:57PASS
  
 THE VIBRO PERMIT STATES THAT THIS PERMIT IS FOR
 BUILDING A ONLY; HOWEVER, THE PERMIT ENCOMPASSES THE
 ENTIRE NORTHWOOD COMMONS DEVELOPMENT BOUNDARY, WHICH
 INCLUDES BOTH BUILDINGS B AND C, AS A PHASED
 DEVELOPMENT. THE CURRENT REVIEW WILL ONLY APPROVE THE
 PORTION OF BUILDING A CONTAINED WITHIN PHASE 1 OF THE
 PHASING PLAN.
  
 PHASE 1 BUILDING A (WILL BE APPROVED WITH THIS PERMIT
 WHEN COMMENTS ARE ADDRESSED) INCLUDES THE FOLLOWING
 ASSOCIATED PERMITS; HOWEVER, SINCE THE ADDRESS OF THIS
 (MASTER) PERMIT NUMBER IS WITHIN PHASE 2, NO WORK ON
 2484 PINEWOOD MAY OCCUR BASED ON THE ISSUANCE OF PERMIT
 22100245.
  
 2505 BROADWAY - 22120838
 604 25TH STREET - 22120840
 2501 BROADWAY - 22120836
 2401 BROADWAY - 22120834
 610 25TH STREET - 22120837
 609 24TH STREET - 22120841
 2425 BROADWAY - 22120835
  
 THIS PERMIT WILL ONLY PERMIT THE VIBRO WORK FOR PHASE
 1. VIBRO WORK WITHIN PHASES 2, 3, 4, PINEWOOD AVENUE
 AND NORTHWOOD ROAD WILL REQUIRE A REVISION TO THE
 PERMIT BEFORE COMMENCING. ZONING HAS ANNOTATED THE
 PLANS TO EXCLUDE WORK WITHIN PHASE 2, PINEWOOD AVENUE
 AND NORTHWOOD ROAD AS PART OF THIS PERMIT APPROVAL. THE
 PERMIT REVISIONS SHALL INCLUDE NEW PLAN SHEETS SO THAT
 STAFF CAN APPROVED A CLEAN SET OF PLANS FOR THE LATTER
 PHASES.
  
 UPON APPROVAL OF A RIGHT-OF-WAY PERMIT THAT ALLOWS WORK
 WITHIN PINEWOOD AVENUE AND/OR NORTHWOOD ROAD, THE
 SPECIFIC PHASE LINE CAN BE EXTENDED TO ENCOMPASS THE
 SPECIFIC RIGHT-OF-WAY AREA THROUGH THE APPROVAL OF A
 PERMIT REVISION (IE ADDED TO A FUTURE PHASE). THE
 RIGHT-OF-WAY PERMIT FOR WORK WITHIN 24TH STREET AND THE
 PARALLEL ALLEYS HAS BEEN APPROVED BY THE ENGINEERING
 DEPARTMENT AND MAY COMMENCE WITH THE PHASE 1 APPROVAL.
  
 FOR FUTURE PHASES, THE APPROVED RIGHT-OF-WAY PERMIT,
 INCLUDING THE SITE PLANS, MUST BE UPLOADED PRIOR TO A
 PHASE LINE BEING SHOWN OVER A RIGHT-OF-WAY.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status F Date 2023-04-04 Cont ID  
Sent By eschneid Date 2023-04-04 Time 12:16 Rev Time 2.00
Received By eschneid Date 2023-03-30 Time 16:18 Sent To  
Notes
2023-04-04 12:32:02FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 THE VIBRO PERMIT STATES THAT THIS PERMIT IS FOR
 BUILDING A ONLY; HOWEVER, THE PERMIT ENCOMPASSES THE
 ENTIRE NORTHWOOD COMMONS DEVELOPMENT BOUNDARY, WHICH
 INCLUDES BOTH BUILDINGS B AND C, AS A PHASED
 DEVELOPMENT. THE CURRENT REVIEW WILL ONLY APPROVE THE
 PORTION OF BUILDING A CONTAINED WITHIN PHASE 1 OF THE
 PHASING PLAN.
  
 PHASE 1 BUILDING A (WILL BE APPROVED WITH THIS PERMIT
 WHEN COMMENTS ARE ADDRESSED) INCLUDES THE FOLLOWING
 ASSOCIATED PERMITS; HOWEVER, SINCE THE ADDRESS OF THIS
 PERMIT NUMBER IS NOT WITHIN PHASE 2, NO WORK ON 2484
 PINEWOOD MAY OCCUR BASED ON THE ISSUANCE OF PERMIT
 22100245.
  
 2505 BROADWAY - 22120838
 604 25TH STREET - 22120840
 2501 BROADWAY - 22120836
 2401 BROADWAY - 22120834
 610 25TH STREET - 22120837
 609 24TH STREET - 22120841
 2425 BROADWAY - 22120835
  
 THIS PERMIT WILL ONLY PERMIT THE VIBRO WORK FOR PHASE
 1. VIBRO WORK WITHIN PHASES 2, 3, 4, PINEWOOD AVENUE
 AND NORTHWOOD ROAD WILL REQUIRE A REVISION TO THE
 PERMIT BEFORE COMMENCING.
  
 UPON APPROVAL OF A RIGHT-OF-WAY PERMIT THAT ALLOWS WORK
 WITHIN A SPECIFIC PORTION OF A CITY RIGHT-OF-WAY, THE
 SPECIFIC PHASE LINE CAN BE EXTENDED TO ENCOMPASS THE
 SPECIFIC RIGHT-OF-WAY AREA THROUGH THE APPROVAL OF A
 PERMIT REVISION (IE ADDED TO A FUTURE PHASE).
 CURRENTLY, CITY ENGINEERING HAS NOT ISSUED THE
 RIGHT-OF-WAY PERMIT TO USE THE RIGHTS-OF-WAY WITHIN THE
 PROJECT BOUNDARIES VIBRO RELATED WORK. VINCE NOEL HAS
 STATED THAT WORK WITHIN THE RIGHTS-OF-WAY WITHIN PHASE
 1 HAS BEEN APPROVED BY THE ENGINEERING DIVISION,
 SUBJECT TO PAYMENT OF THE RIGHT-OF-WAY FEES; THEREFORE,
 NO REVISION IS REQUIRED FOR THE RIGHTS-OF-WAY WITHIN
 PHASE 1. NO WORK MAY OCCUR WITHIN THESE RIGHTS-OF-WAY
 (24TH ST AND ADJACENT ALLEYS) UNTIL THE RIGHT-OF-WAY
 PERMIT HAS BEEN ISSUED.
  
 FOR FUTURE PHASES, THE APPROVED RIGHT-OF-WAY PERMIT,
 INCLUDING THE SITE PLANS, MUST BE UPLOADED PRIOR TO A
 PHASE LINE BEING SHOWED OVER A RIGHT-OF-WAY.
  
 UPON APPROVAL, THE PHASE 1 VIBRO PERMIT WILL MEET THE
 CONSTRUCTION PERMIT REQUIREMENT FOR THE ENTIRE
 NORTHWOOD SQUARE DEVELOPMENT AND THUS PERMITS THE
 ISSUANCE OF A DEMOLITION PERMIT FOR THE BUILDINGS
 WITHIN THE BOUNDARIES OF THE NORTHWOOD SQUARE
 DEVELOPMENT.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO THE
 ISSUANCE OF THE PHASE 1 APPROVAL:
  
 1) UPDATED REPEAT COMMENT: THE ARCHITECTURAL SITE PLAN
 AND THE FOUNDATION/GROUND LEVEL FRAMING PLAN SHEETS
 PROVIDED WITH THIS PERMIT DO NOT MATCH THE LATEST SITE
 PLAN FOR BUILDING A CURRENTLY UNDER REVIEW AS PART OF
 THE FORMAL SITE PLAN. NEITHER OF THESE PLANS WERE
 UPDATED TO ADDRESS THE STAFF COMMENTS DATED JANUARY 6,
 2023. THE STRUCTURAL COLUMNS SHOWN ON THESE PLANS DO
 NOT MATCH THE LOCATIONS THAT ARE SHOWN ON THE SITE PLAN
 AND IN THE CASE OF THE FOUNDATION/GROUND LEVEL FRAMING
 PLAN, INTERIOR AND EXTERIOR WALL LOCATIONS DO NOT MATCH
 THE LATEST SITE PLAN. ALL PLANS NEED TO SHOW ACCURATE,
 CONSISTENT CONDITIONS. NOTE: THESE PLANS ALSO DO NOT
 MATCH THE SUBMITTED FOUNDATION PERMIT PLANS.
  
 2) REPEAT COMMENT: ONCE CORRECTED, THE RESUBMITTED
 FOUNDATION/GROUND LEVEL FRAMING PLAN NEEDS TO INCLUDE
 THE SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
 FUTURE PHASES THAT WILL REQUIRE PERMIT REVISIONS TO
 PERMIT 22100245 PRIOR TO WORK COMMENCING.
  
 PHASE 2 BUILDING A
  
 2484 PINEWOOD - 22100245 (FUTURE REVISION)
  
 PHASE 3 BUILDING B (FUTURE REVISION) WHEN SUBMITTED -
 PROVIDE THE SETBACK DIMENSION FOR BUILDING B FROM 23RD
 STREET SO THAT STAFF CAN VERIFY THAT IT MATCHES THE
 SITE PLAN CURRENTLY UNDER REVIEW AS PART OF THE FORMAL
 SITE PLAN
  
 550 NORTHWOOD ROAD - 22120842
  
 NOTE: THE HISTORIC BUILDING WALL THAT IS TO REMAIN MUST
 BE SHOWN ON THIS REVISION, INCLUDING HOW IT WILL BE
 PROTECTED DURING THE VIBRO WORK FOR BUILDING B.
  
 PHASE 4 BUILDING C (FUTURE REVISION) WHEN SUBMITTED -
 PROVIDE ALL THE BUILDING DIMENSIONS FOR BUILDING C SO
 THAT STAFF CAN VERIFY THAT IT MATCHES THE SITE PLAN
 CURRENTLY UNDER REVIEW AS PART OF THE FORMAL SITE PLAN
  
 2446 BROADWAY - 22120833
 2400 BROADWAY - 22120832
  
 **** 701 23RD STREET - 22120839 HAD A SEPARATE VIBRO
 PERMIT SUBMITTED, BUT DOES NOT HAVE ANY FUTURE BUILDING
 CONSTRUCTION. THIS PERMIT SHOULD MOST LIKELY BE VOIDED
 AS IT DOES NOT SEEM TO APPLY.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-06 Cont ID  
Sent By eschneid Date 2023-01-06 Time 13:58 Rev Time 2.00
Received By eschneid Date 2023-01-05 Time 17:11 Sent To  
Notes
2023-01-06 13:04:10FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 THE VIBRO PERMIT STATES THAT THIS PERMIT IS FOR
 BUILDING A ONLY; HOWEVER, THE PERMIT ENCOMPASSES THE
 ENTIRE NORTHWOOD COMMONS DEVELOPMENT BOUNDARY, WHICH
 INCLUDES BOTH BUILDINGS B AND C, AS A PHASED
 DEVELOPMENT. THE CURRENT REVIEW INCLUDES THE BUILDING A
 FOUNDATION/GROUND LEVEL FRAMING PLAN, THE ARCHITECTURAL
 SITE PLAN COVERING THE ENTIRE PROPERTY, AND THE PHASING
 PLAN COVERING THE 3 BUILDINGS.
  
 1) THE PHASING PLAN NEEDS TO BE DRAWN FOLLOWING THE
 PROPERTY LINES (IE. EXCLUDING THE RIGHTS-OF-WAYS) TO
 CLEARLY SHOW WHERE THE WORK WILL BE PERFORMED ON
 PRIVATE PROPERTY (THE NOTE ON THE PLAN IS NOT
 SUFFICIENT). UPON APPROVAL OF A RIGHT-OF-WAY PERMIT
 THAT PERMITS WORK WITHIN A SPECIFIC PORTION OF A CITY
 RIGHT-OF-WAY, THE SPECIFIC PHASE LINE CAN BE EXTENDED
 TO ENCOMPASS THE SPECIFIC RIGHT-OF-WAY AREA THROUGH THE
 APPROVAL OF A PERMIT REVISION. CURRENTLY, CITY
 ENGINEERING HAS NOT ISSUED A RIGHT-OF-WAY PERMIT TO USE
 THE RIGHTS-OF-WAY WITHIN THE PROJECT BOUNDARIES. THE
 APPROVED RIGHT-OF-WAY PERMIT, INCLUDING THE SITE PLANS,
 MUST BE UPLOADED PRIOR TO A PHASE LINE BEING SHOWED
 OVER A RIGHT-OF-WAY.
  
 2) BASED ON THE REQUIREMENT FOR A PERMIT FOR EACH
 INDIVIDUAL PARCEL, THE PHASE LINE BETWEEN PHASE 1 AND 2
 NEEDS TO FOLLOW PARCEL LINES SO THAT THE ENTIRE PARCEL
 IS COVERED BY ONE PHASE.
  
 3) THIS PERMIT WILL ONLY PERMIT THE VIBRO WORK FOR
 PHASE 1. PHASES 2, 3 AND 4 WILL REQUIRE A REVISION TO
 THE PERMIT BEFORE COMMENCING.
  
 4) NO WORK MAY OCCUR WITHIN THE RIGHTS-OF-WAY IN PHASE
 1 UNTIL THE CITY UTILITIES ARE NO LONGER ACTIVE. THE
 PERMIT REVISION TO MOVE THE PHASE 1 LINE TO INCLUDE THE
 RIGHTS-OF-WAY INCLUDED ON AN APPROVED RIGHT-OF-WAY
 PERMIT MUST ALSO BE ACCOMPANIED BY VERIFICATION FROM
 THE CITY'S ENGINEERING DIVISION THAT THE UTILITIES
 WITHIN THE SPECIFIC RIGHT-OF-WAY ARE NO LONGER ACTIVE.
 THE APPROVAL MUST BE PROVIDED WITH THE PERMIT REVISION
 SUBMITTAL TO CHANGE THE PHASE LINE.
  
 5) THE SOUTH PORTION OF PHASE 1 IS SHOWN IN THE
 EXISTING PINEWOOD AVENUE RIGHT-OF-WAY. SINCE WORK MAY
 NOT OCCUR IN THE PINEWOOD AVENUE RIGHT-OF-WAY UNTIL THE
 EXISTING CITY UTILITIES ARE NO LONGER ACTIVE, THIS AREA
 MUST BE EXCLUDED FROM PHASE 1. PINEWOOD AVENUE HAS
 MAJOR CITY UTILITIES.
  
 6) THE ARCHITECTURAL SITE PLAN PROVIDED WITH THIS
 PERMIT DOES NOT MATCH THE SITE PLAN FOR BUILDING A
 CURRENTLY UNDER REVIEW AS PART OF THE FORMAL SITE PLAN.
  
 A. THE DIMENSION FOR THE 5,510 SF RETAIL SPACE ALONG
 THE WEST SIDE OF NEW PINEWOOD IS INCORRECT.
 B. THE DIMENSION FOR LOBBY #3 ALONG BROADWAY IS
 INCORRECT.
  
 7) THE FOUNDATION/GROUND LEVEL FRAMING PLAN SHEETS DO
 NOT MATCH THE ARCHITECTURAL SITE PLAN PROVIDED WITH
 THIS PERMIT OR THE ARCHITECTURAL SITE PLAN CURRENTLY
 UNDER REVIEW AS PART OF THE FORMAL SITE PLAN. THE
 ACCURATE PLANS MUST BE INCLUDED WITH THIS PERMIT.
  
 8) ONCE CORRECTED, THE RESUBMITTED FOUNDATION/GROUND
 LEVEL FRAMING PLAN NEEDS TO INCLUDE THE SETBACK
 DIMENSIONS TO THE PROPERTY LINES.
  
 SINCE THERE ARE CURRENTLY MULTIPLE PROPERTIES WITHIN
 THE LIMITS OF WORK, THERE HAS BEEN A PERMIT SUBMITTED
 FOR EACH PARCEL. THE CURRENT PHASE LAYOUT FOR THE
 VARIOUS BUILDINGS INCLUDES THE FOLLOWING PERMITS.
  
 PHASE 1 BUILDING A (WILL BE APPROVED WITH THIS PERMIT
 WHEN COMMENTS ARE ADDRESSED)
  
 2505 BROADWAY - 22120838
 604 25TH STREET - 22120840
 2501 BROADWAY - 22120836
 2401 BROADWAY - 22120834
  
 PHASE 2 BUILDING A
  
 2501 PINEWOOD - 22100245 (FUTURE REVISION)
  
 SPLIT BETWEEN PHASE 1 AND 2. THE ENTIRE PROPERTY MUST
 BE ASSIGNED TO JUST ONE PHASE. (ANY OF THESE SHOWN IN
 PHASE 1 WILL BE APPROVED WITH THIS PERMIT WHEN COMMENTS
 ARE ADDRESSED)
  
 610 25TH STREET - 22120837
 609 24TH STREET - 22120841
 2425 BROADWAY - 22120835
  
 PHASE 3 BUILDING B (FUTURE REVISION) WHEN SUBMITTED -
 PROVIDE THE SETBACK DIMENSION FOR BUILDING B FROM 23RD
 STREET SO THAT STAFF CAN VERIFY THAT IT MATCHES THE
 SITE PLAN CURRENTLY UNDER REVIEW AS PART OF THE FORMAL
 SITE PLAN
  
 550 NORTHWOOD ROAD - 22120842
  
 NOTE: THE HISTORIC BUILDING WALL THAT IS TO REMAIN MUST
 BE SHOWN ON THIS REVISION, INCLUDING HOW IT WILL BE
 PROTECTED DURING THE VIBRO WORK FOR BUILDING B.
  
 PHASE 4 BUILDING C (FUTURE REVISION) WHEN SUBMITTED -
 PROVIDE ALL THE BUILDING DIMENSIONS FOR BUILDING C SO
 THAT STAFF CAN VERIFY THAT IT MATCHES THE SITE PLAN
 CURRENTLY UNDER REVIEW AS PART OF THE FORMAL SITE PLAN
  
 2446 BROADWAY - 22120833
 2400 BROADWAY - 22120832
  
 **** 701 23RD STREET - 22120839 HAD A SEPARATE VIBRO
 PERMIT SUBMITTED, BUT DOES NOT HAVE ANY FUTURE BUILDING
 CONSTRUCTION. THIS PERMIT SHOULD MOST LIKELY BE VOIDED
 AS IT DOES NOT SEEM TO APPLY.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-11-30 Cont ID  
Sent By eschneid Date 2022-11-30 Time 10:14 Rev Time 0.25
Received By eschneid Date 2022-11-30 Time 10:13 Sent To  
Notes
2022-11-30 10:32:25FAILED
  
 1) THE SITE IS CURRENTLY BISECTED BY PINEWOOD AVENUE,
 NORTHWOOD ROAD, 24TH STREET AND TWO ALLEYS. WHILE THERE
 IS AN APPLICATION TO ABANDON THESE RIGHTS-OF-WAY AND
 REPLAT THE AREA, NONE OF THESE HAVE BEEN APPROVED BY
 CITY COMMISSION. ADDITONALLY, THE BMUD REGULATIONS DO
 NOT PERMIT THE DEMOLITION OF THE EXISTING STRUCTURES
 UNTIL BUIDING PERMITS FOR THE NEW STRUCTURES HAVE BEEN
 APPROVED.
  
 2) THE RIGHTS-OF-WAY INCLUDE CITY UTILITES WHICH MUST
 BE RELOCATED AND/OR ABANDONED PRIOR TO ANY WORK BEING
 DONE IN THE RIGHST-OF-WAY TO AVOUD INTERUPTION OF CITY
 SERVICES.
  
 3) ONLY THE PARCELS (NOT RIGHTS-OF-WAY) THAT ARE VACANT
 MAY HAVE THE WORK STARTED ON THEM AND THE AREAS OF WOK
 WOULD NEED TO BE CLEARLY DELINEATED ON THE PLAN.
  
 4) CONTRARY TO THE RESPONSE LETTER, THE FORMAL SITE
 PLAN HAS NOT BEEN APPROVED FOR THE PROJECT. THE
 PLANNING BOARD GRANTED VARIANCES AND APPROVAL OF THE
 PROJECT BASED ON THE SUBMITTED DEVELOPMENT PLAN. THE
 FINAL SITE PLAN IS STILL PENDING.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446.
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-11-21 Cont ID  
Sent By afowlkes Date 2022-11-21 Time 11:56 Rev Time 0.00
Received By asangele Date 2022-11-21 Time 11:56 Sent To  
Notes
2022-11-21 11:57:54FAILED
 11/21/2022
  
 PLEASE PROVIDE A SURVEY WITH APPLICATION WITH LABELED
 SETBACKS.
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]