Plan Review Details - Permit 22100223
Plan Review Stops For Permit 22100223
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By rmcphers Date 2022-11-17 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2022-11-17 Time 14:15 Sent To  
Notes
2022-11-17 15:06:42PORCH
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 2) FOR ALLOWABLE SET BACKS - SEE FBC TABLE 705.2 - -
 FBC 705.2 PROJECTIONS.
  
 3) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 DESIGNER - FBC WPB 107.1
  
 4) SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 PROJECTDOX (ELECTRONIC PLAN REVIEW).
  
 5) JOB COST APPEARS TO BE LOW - PLEASE REVISE THE
 BUILDING PERMIT APPLICATION TO SHOW THE CORRECT JOB
 COST - ALL MATERIAL AND ALL LABOR COST AS IF IT WAS NOT
 YET CONSTRUCTED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-11-03 Cont ID  
Sent By jleahy Date 2022-11-03 Time 16:34 Rev Time 0.00
Received By jleahy Date 2022-11-03 Time 16:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-31 Cont ID  
Sent By pleduc Date 2022-10-31 Time   Rev Time 0.00
Received By pleduc Date 2022-10-31 Time 10:34 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-12-02 Cont ID  
Sent By amhamilt Date 2022-12-02 Time 12:23 Rev Time 0.00
Received By amhamilt Date 2022-12-02 Time 12:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-05 Cont ID  
Sent By aoliver Date 2022-12-05 Time 10:24 Rev Time 0.00
Received By aoliver Date 2022-10-28 Time 09:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rwbrown Date 2022-11-01 Time 07:39 Rev Time 0.00
Received By rwbrown Date 2022-11-01 Time 07:39 Sent To  
Notes
2022-11-01 08:07:501ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - IN REVIEW OF THE CODE CASE
 PICTURES, YOU HAVE NOT DETAILED THE WATER HEATER
 (BOTTOM FED) AND YOU ARE ONLY SHOWING ONE OF THE TWO
 WASHING MACHINES,
  
 2. 2020 FPC 607.1.1 - PLEASE SHOW COMPLIANCE WITH THE
 LIMITING FOR HOT WATER DELIVERY. THE THERMOSTAT ON THE
 WATER CANNOT SERVE AS THE LIMITING MEANS FOR HOT OR
 TEMPERED WATER. A MIXING DEVICE IS REQUIRED FOR THIS
 SECTION. THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST
 BE INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC
 613.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By rwbrown Date 2022-11-17 Time 05:30 Rev Time 0.00
Received By rwbrown Date 2022-11-17 Time 05:27 Sent To  
Notes
2022-11-17 05:30:46SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-02 Cont ID  
Sent By amhamilt Date 2022-12-02 Time 12:23 Rev Time 0.00
Received By amhamilt Date 2022-12-02 Time 12:23 Sent To  
Notes
2022-12-02 12:38:41THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PROPOSED CONCRETE PAD/COVERING DOES NOT APPEAR TO MEET
 SETBACKS. CONCRETE MUST BE AT LEAST 2FT FROM PROPERTY
 LINE, ANY ROOFED STRUCTURE SUPPORTED BY COLUMNS WOULD
 NEED TO BE AT LEAST 5FT FROM PROPERTY LINE. POTENTIAL
 FOR CANVAS OR OTHER NON-COLUMN SUPPORTED AWNING TO BE
 LOCATED AS CLOSE AS 2FT.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  