Plan Review Details - Permit 22100218
Plan Review Stops For Permit 22100218
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2022-12-01 Cont ID  
Sent By mpeterso Date 2022-12-01 Time 16:28 Rev Time 0.00
Received By mpeterso Date 2022-12-01 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-27 Cont ID  
Sent By medwards Date 2023-03-27 Time 15:53 Rev Time 0.00
Received By medwards Date 2023-03-27 Time 15:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-21 Cont ID  
Sent By medwards Date 2023-03-21 Time 15:59 Rev Time 0.00
Received By medwards Date 2023-03-17 Time 07:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 09:35 Rev Time 0.00
Received By medwards Date 2023-01-10 Time 16:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-01 Cont ID  
Sent By mpeterso Date 2022-12-01 Time 16:28 Rev Time 0.00
Received By mpeterso Date 2022-11-16 Time 09:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-17 Cont ID  
Sent By medwards Date 2022-10-17 Time 08:52 Rev Time 0.00
Received By medwards Date 2022-10-07 Time 07:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2023-03-27 Cont ID  
Sent By medwards Date 2023-03-27 Time 15:52 Rev Time 0.00
Received By medwards Date 2023-03-27 Time 15:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-03-21 Cont ID  
Sent By medwards Date 2023-03-21 Time 15:59 Rev Time 0.00
Received By medwards Date 2023-03-21 Time 15:50 Sent To  
Notes
2023-03-21 15:58:56STILL WAITING ON THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THESE AHUS.
  
 STILL WAITING ON THE OUTDOOR AIR CALCULATIONS FOR THIS
 TENANT SPACE. THE OUTDOOR AIR CALCULATIONS DOES NOT
 LIST THE OCCUPANT CLASSIFICATION FROM FMC TABLE
 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 09:29 Rev Time 0.00
Received By medwards Date 2023-01-11 Time 09:29 Sent To  
Notes
2023-01-11 09:35:17PLEASE ADDRESS ALL COMMENTS BELOW FROM 2ND REVIEW
 CYCLE:
  
 2ND REVIEW FMC
 PERMIT: 22100218
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION HAS THE ADDRESS OF 544
 NORTHWOOD RD, THE DRAWING HAS THE ADDRESS OF 540
 NORTHWOOD RD. SUBMIT DOCUMENTS THAT ARE CONSISTENT.
  
 2) THE LIKE FOR LIKE DOCUMENT DOES NOT SHOW THIS TO BE
 A LIKE FOR LIKE. A GOOGLE MAPS SEARCH INDICATES THE
 BUILDINGS IN THAT AREA TO HAVE RTU???S. PROVIDE THE
 MECHANICAL SIZING CALCULATIONS REQUIRED FOR THIS
 PROJECT ALONG WITH THE OUTDOOR AIR CALCULATIONS FOR THE
 USE OF THIS TENANT SPACE. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-18 Cont ID  
Sent By medwards Date 2022-11-18 Time 06:13 Rev Time 0.00
Received By medwards Date 2022-11-18 Time 06:12 Sent To  
Notes
2022-11-18 06:13:122ND REVIEW FMC
 PERMIT: 22100218
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION HAS THE ADDRESS OF 544
 NORTHWOOD RD, THE DRAWING HAS THE ADDRESS OF 540
 NORTHWOOD RD. SUBMIT DOCUMENTS THAT ARE CONSISTENT.
  
 2) THE LIKE FOR LIKE DOCUMENT DOES NOT SHOW THIS TO BE
 A LIKE FOR LIKE. A GOOGLE MAPS SEARCH INDICATES THE
 BUILDINGS IN THAT AREA TO HAVE RTU???S. PROVIDE THE
 MECHANICAL SIZING CALCULATIONS REQUIRED FOR THIS
 PROJECT ALONG WITH THE OUTDOOR AIR CALCULATIONS FOR THE
 USE OF THIS TENANT SPACE. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By medwards Date 2022-10-17 Time 08:51 Rev Time 0.00
Received By medwards Date 2022-10-17 Time 08:51 Sent To  
Notes
2022-10-17 08:51:471ST REVIEW FMC
 PERMIT: 22100218
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PERMIT APPLICATION NUMBERS 22100216 AND 22100218
 HAVE THE SAME DRAWING. SUBMIT DRAWINGS THAT PERTAIN TO
 THE WORK BEING PERFORMED UNDER THE PERMIT SUBMITTED FOR
 EACH ADDRESS.
  
 2) PROVIDE THE COMPLETED LIKE FOR LIKE CHANGE OUT FORMS
 FOR THE CHANGE OUTS ON BOTH AHU???S. IT APPEARS THAT
 THE UNITS ARE LOCATED ON THE ROOF. A LIKE FOR LIKE
 WOULD MEAN THE NEW UNITS WOULD ALSO BE RTU???S. IF THIS
 IS NOT A LIKE FOR LIKE CHANGE OUT PROVIDE EQUIPMENT
 SIZING CALCULATIONS FOR EACH UNIT.
  
 3) SHOW THE OUTSIDE AIR CALCULATIONS FOR EACH TENANT
 SPACE. FMC 403.3.1.1
  
 4) DESIGNER OF THIS DRAWING MUST PRINT AND SIGN THEIR
 NAME. THE DRAWING MUST ALSO INCLUDE THE ADDRESS. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-11-18 Cont ID  
Sent By medwards Date 2022-11-18 Time 06:13 Rev Time 0.00
Received By medwards Date 2022-11-18 Time 06:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By medwards Date 2022-10-17 Time 08:51 Rev Time 0.00
Received By medwards Date 2022-10-17 Time 08:51 Sent To  
Notes
***NONE***