| Plan Review Stops For Permit 22100216 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-01 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-01 |
Time |
13:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-27 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-27 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-22 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-17 |
Time |
07:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-01-12 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-01-12 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-11 |
Time |
07:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-01 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-16 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-17 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-07 |
Time |
07:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-27 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-27 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-21 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-21 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2023-03-21 16:29:44 | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS LIST A | | | TOTAL LOAD FOR THE DOG GROOMING AHU AS 44,349 BTUS AND | | | A TOTAL LOAD FOR THE OA COND AS 21.484 BTUS. THE | | | MECHANICAL DRAWING SI SPECIFYING A 5-TON AND A 4-TON | | | UNITS. THESE DOCUMENTS SHOULD REFLECT EACH OTHER. | | | PROVIDE A CORRECTED DESIGN FOR THIS DOG GROOMING | | | FACILITY. FEC C403.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-01-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-12 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-12 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2023-01-12 15:11:26 | 3RD REVIEW FMC | | | PERMIT: 22100216 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ADDRESS THE COMMENT BELOW FROM PREVIOUS REVIEW | | | CYCLE: | | | THE LIKE FOR LIKE DOCUMENT DOES NOT SHOW THIS TO BE A | | | LIKE FOR LIKE. A GOOGLE MAPS SEARCH INDICATES THE | | | BUILDINGS IN THAT AREA TO HAVE RTUS. PROVIDE THE | | | MECHANICAL SIZING CALCULATIONS REQUIRED FOR THIS | | | PROJECT ALONG WITH THE OUTDOOR AIR CALCULATIONS FOR THE | | | USE OF THIS TENANT SPACE. FBC 107.3.5 | | | | | | 2) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH | | | OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES | | | THE USE IN THIS TENANT SPACE FROM TABLE 403.3.1.1. DOG | | | GROOMING IS NOT LISTED AS AN OCCUPANCY CLASSIFICATION, | | | BUT PET SHOPS- ANIMAL AREAS IS LISTED. THE OUTDOOR AIR | | | CALCULATION SUBMITTED LISTS 5 PEOPLE IN THE DOG | | | GROOMING AREA, THE TABLE LISTS THE MINIMUM PEOPLE AS | | | 10. THE CALCULATION SHOW HAVE THE CORRECT PEOPLE COUNT | | | THE CALCULATIONS AND DRAWINGS SUBMITTED DOES NOT SHOW | | | THE CORRECT AMOUNT EXHAUST AIR CALCULATIONS. SHOW THE | | | CORRECTED EXHAUST IN THE CALCULATIONS AND SHOW THE | | | EXHAUST DESIGN ON THE DRAWINGS. PROVIDE THE INFORMATION | | | FOR THE EXHAUST FANS. AND THE NEW MECHANICAL UNITS ON | | | AN EQUIPMENT SCHEDULE. SHOW THE LOCATION OF THE | | | CONDENSING UNIT. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-11-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-18 |
Time |
06:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-18 |
Time |
06:20 |
Sent To |
|
|
| Notes |
| 2022-11-18 06:20:20 | 2ND REVIEW FMC | | | PERMIT: 22100216 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PERMIT APPLICATION HAS THE ADDRESS OF 540 | | | NORTHWOOD RD, THE DRAWING HAS THE ADDRESS OF 544 | | | NORTHWOOD RD. SUBMIT DOCUMENTS THAT ARE CONSISTENT. | | | | | | 2) THE LIKE FOR LIKE DOCUMENT DOES NOT SHOW THIS TO BE | | | A LIKE FOR LIKE. A GOOGLE MAPS SEARCH INDICATES THE | | | BUILDINGS IN THAT AREA TO HAVE RTU???S. PROVIDE THE | | | MECHANICAL SIZING CALCULATIONS REQUIRED FOR THIS | | | PROJECT ALONG WITH THE OUTDOOR AIR CALCULATIONS FOR THE | | | USE OF THIS TENANT SPACE. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-17 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-17 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2022-10-17 08:28:22 | 1ST REVIEW FMC | | | PERMIT: 22100216 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE COMPLETED LIKE FOR LIKE CHANGE OUT FORMS | | | FOR THE CHANGE OUTS ON BOTH AHU???S. IT APPEARS THAT | | | THE UNITS ARE LOCATED ON THE ROOF. A LIKE FOR LIKE | | | WOULD MEAN THE NEW UNITS WOULD ALSO BE RTU???S. IF THIS | | | IS NOT A LIKE FOR LIKE CHANGE OUT PROVIDE EQUIPMENT | | | SIZING CALCULATIONS FOR EACH UNIT. | | | | | | 2) SHOW THE OUTSIDE AIR CALCULATIONS FOR EACH TENANT | | | SPACE. FMC 403.3.1.1 | | | | | | 3) DESIGNER OF THIS DRAWING MUST PRINT AND SIGN THEIR | | | NAME. THE DRAWING MUST ALSO INCLUDE THE ADDRESS. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
N |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-22 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-22 |
Time |
10:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2022-11-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-18 |
Time |
06:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-18 |
Time |
06:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-17 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-17 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|