Plan Review Details - Permit 22100200
Plan Review Stops For Permit 22100200
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-01-13 Cont ID  
Sent By rmcphers Date 2023-01-13 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2023-01-13 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-04 Cont ID  
Sent By rmcphers Date 2023-01-04 Time 09:08 Rev Time 0.00
Received By rmcphers Date 2023-01-04 Time 08:58 Sent To  
Notes
2023-01-04 09:05:33CONCRETE RESTORATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) REVISED DRAWINGS SHOW POSSIBLE CONCRETE
 REINFORCEMENT REPAIR -
  
 THRESHOLD BUILDING
 CONCRETE RESTORATION
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE
 "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 1) ANY REPAIRS TO THRESHOLD BUILDINGS ARE REQUIRED TO
 COMPLY WITH FS 553.79. THRESHOLD BLDG. REQUIRED
 STATEMENT: W.P.B. AMENDMENT 110.8.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 FLORIDA STATUTES.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
  
 2) PLEASE PROVIDE SOME TYPE OF MAP SHOWING THE LOCATION
 OF CONCRETE REPAIRS.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-15 Cont ID  
Sent By rmcphers Date 2022-12-15 Time 10:27 Rev Time 0.00
Received By rmcphers Date 2022-12-15 Time 10:27 Sent To  
Notes
2022-12-15 10:27:59STUCCO REPAIR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By rmcphers Date 2022-12-13 Time 15:24 Rev Time 0.00
Received By rmcphers Date 2022-12-13 Time 15:24 Sent To  
Notes
2022-12-13 15:26:25STUCCO REPAIR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-01-18 Cont ID  
Sent By pleduc Date 2023-01-18 Time   Rev Time 0.00
Received By pleduc Date 2023-01-18 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-15 Cont ID  
Sent By pleduc Date 2022-12-15 Time   Rev Time 0.00
Received By pleduc Date 2022-12-15 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-11-02 Cont ID  
Sent By pleduc Date 2022-11-02 Time   Rev Time 0.00
Received By pleduc Date 2022-11-02 Time 16:00 Sent To  
Notes
2022-11-02 16:09:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF EXTERIOR WORK ON A HIGH
 RISE BUILDING; HOWEVER, THE IS NO INDICATION OF
 PROTECTION FROM FALLING DEBRIS AROUND THE BUILDING(S)
 AND/OR PROTECTION OF EXIT TRAVEL PATHS.
  
 WITHIN THE SCOPE OF WORK THERE ARE INDICATIONS OF
 SCAFFOLDING, BOOM LIFTS, ETC...
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 FOR THE OFFICIAL RECORD, PLEASE REVIEW AND PROVIDE A
 LIFE SAFETY SHEET THAT INCLUDES PEDESTRIAN PROTECTION
 AROUND THE BUILDING AND SPECIFICALLY THE EXIT TRAVEL
 PATHS OR BLOCKED EXITS FROM THE BUILDING AND PROPOSED
 ALTERNATE ROUTING.
  
 SHOULD NO PROTECTION BE REQUIRED PLEASE PROVIDE A
 DETAILED NARRATIVE AND/OR PLAN SHEETS EXPLAINING WHY
 PROTECTION IS NOT REQUIRED.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-19 Cont ID  
Sent By aoliver Date 2023-01-19 Time 08:54 Rev Time 0.00
Received By aoliver Date 2023-01-12 Time 10:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-04 Cont ID  
Sent By rmcphers Date 2023-01-04 Time 09:08 Rev Time 0.00
Received By rmcphers Date 2022-12-22 Time 14:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-16 Cont ID  
Sent By aoliver Date 2022-12-16 Time 12:19 Rev Time 0.00
Received By aoliver Date 2022-12-14 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-13 Cont ID  
Sent By rmcphers Date 2022-12-13 Time 15:28 Rev Time 0.00
Received By rmcphers Date 2022-11-01 Time 10:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-01-13 Cont ID  
Sent By rmcphers Date 2023-01-13 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2023-01-13 Time 08:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-04 Cont ID  
Sent By rmcphers Date 2023-01-04 Time 09:08 Rev Time 0.00
Received By rmcphers Date 2023-01-04 Time 09:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-15 Cont ID  
Sent By rmcphers Date 2022-12-15 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2022-12-15 Time 10:28 Sent To  
Notes
2022-12-15 10:28:23SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By rmcphers Date 2022-12-13 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2022-12-13 Time 15:26 Sent To  
Notes
2022-12-13 15:27:21SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  