Plan Review Details - Permit 22100178
Plan Review Stops For Permit 22100178
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-05-03 Cont ID  
Sent By rmcphers Date 2023-05-03 Time 09:25 Rev Time 0.00
Received By rmcphers Date 2023-05-03 Time 09:20 Sent To  
Notes
2023-05-03 09:22:51POOL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A HAND RAIL ATTACHMENT DETAIL - FBC
 454.1.2.5.5
  
 2) DRAWINGS SP120, 1.51, 1.52, 1.53, 1.54, DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-14 Cont ID  
Sent By rmcphers Date 2022-12-14 Time 16:32 Rev Time 0.00
Received By rmcphers Date 2022-12-14 Time 16:32 Sent To  
Notes
2022-12-14 16:37:50POOL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A HAND RAIL DETAIL - FBC 454.1.2.5.5
  
 2) DRAWING SP.001 SHOWS DESIGN PER 2017 FBC - DRAWING
 1.51 SHOWS DESIGN PER 2014 FBC - PLEASE SHOW THE
 CORRECT CODE DESIGN.
  
 3) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2022-11-07 Cont ID  
Sent By   Date 2022-11-07 Time 14:18 Rev Time 0.00
Received By aoliver Date   Time   Sent To  
Notes
2022-11-07 13:51:12 
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-01 Cont ID  
Sent By rperdomo Date 2023-05-01 Time 08:20 Rev Time 0.00
Received By rperdomo Date 2023-05-01 Time 08:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By rperdomo Date 2022-11-07 Time 14:02 Rev Time 0.00
Received By rperdomo Date 2022-11-07 Time 14:05 Sent To  
Notes
2022-11-07 14:01:26FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 - FOLLOW REQUIREMENTS OF NEC 2017 ARTICLE 680.
 - ONE LINE DIAGRAM SHOWINGS GROUNDING (BONDING),
 EQUIPMENT GROUNDING, AND EQUIPOTENTIAL BONDING.
  
 RUBEN P. PERDOMO
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-07-06 Cont ID  
Sent By ccole Date 2023-07-06 Time 11:05 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 17:42 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-04-21 Cont ID  
Sent By ccole Date 2023-04-21 Time 15:30 Rev Time 0.00
Received By ccole Date 2023-04-21 Time 15:30 Sent To  
Notes
2023-04-21 15:31:302ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100178
 4/21/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS
 AND NOTE GAS CAN BE SUBMITTED AS A REVISION TO THE
 MASTER PLAN UNDER PERMIT 18100540. IF THIS OPTION IS
 CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS
 AND PERFORM THE REVIEW UNDER THE REVISION SUBMITTAL.
  
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEETS P.700: THE RISER BRANCH THAT
 CORRELATES TO KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON
 THE DRAWING. PLEASE PROVIDE A COMPLETE GAS RISER
 DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING
 INVOLVED WITH SUPPLYING THE GAS HEATER AND OTHER
 APPLIANCES- SECTIONS 401.3 & 401.4 FBC FG. REFER TO FBC
 CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 THE RISER IS INCOMPLETE BECAUSE IT DOES NOT INCLUDE THE
 LOW PRESSURE PIPING SYSTEM FROM THE REGULATORS TO THE
 POOL HEATERS. A COMPLETE RISER PER COMMENT #1 ABOVE IS
 REQUIRED.
  
 5) FAILED. P.509: SHOW THE GAS VENT PIPING RUN AND
 TERMINATION LOCATION FROM THE EQUIPMENT ROOM BY
 GRIDLINES 10 & K- SEC. 410.3 FBC FG.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET
 P.105C WHICH WAS NOT UPLOADED FOR REVIEW.
  
 6) FAILED. P.509: PLEASE SUBMIT SHEET P.804 THAT
 CONTAINS THE GAS MONITORING AND DETECTING DETAILS
 CALLED OUT ON THE PLAN- SEC. 107.2.1 WPB.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET
 P.804 WHICH WAS NOT UPLOADED FOR REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By ccole Date 2022-11-08 Time 16:48 Rev Time 0.00
Received By ccole Date 2022-11-04 Time 16:16 Sent To  
Notes
2022-11-08 16:50:521ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100178
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE PERMIT APPLICATION IS
 FOR THE HOTEL POOL WHICH HAS A GAS-FIRED POOL HEATER,
 HOWEVER SINCE SHEET P.509 & P.700 SHOWS MULTIPLE POOL
 HEATERS FOR THE INDOOR POOL AND SPAS THE APPLICANTS
 SHOULD CONSIDER SUBMITTING A SEPARATE PERMIT
 APPLICATION FOR GAS THAT INCLUDES ALL THE GAS WORK
 RELATING TO THE POOLS AND SPAS. IF A SEPARATE PERMIT IS
 CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS
 AND PERFORM THE REVIEW UNDER THE SEPARATE PERMIT.
 PLEASE REVIEW THE COMMENTS AND CONTACT ME IF YOU HAVE
 QUESTIONS..
  
 1) SHEETS SP.120, SP.700, P.509, P.700: THE RISER
 BRANCH THAT CORRELATES TO KEYNOTE 1 ON SHEET P.700 DOES
 NOT APPEAR TO BE SHOWN ON THE DRAWING. PLEASE PROVIDE A
 COMPLETE GAS RISER DRAWING THAT INCLUDES ALL NEW AND
 EXISTING GAS PIPING SUPPLYING THE NEW POOL HEATER AND
 APPLIANCES- SECTIONS 401.3 & 401.4 FBC FG. REFER TO FBC
 CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 2) SP.120, SP.700, P.509, P.700: SUBMIT MANUFACTURER' S
 SPECIFICATIONS FOR THE POOL HEATER- SEC.617.1 FBC FG.
  
 3) SP.120, SP.700, P.509, P.700: INDICATE HOW
 COMBUSTION AIR WILL BE PROVIDED TO THE HEATER AND SHOW
 CALCULATIONS FOR INDOOR AIR IF APPLICABLE- SEC. 304.1
 FBC FG.
  
 4) SP.120, SP.700, P.509, P.700: PROVIDE A VENTING PLAN
 FOR THE HEATER- SEC. 503.1 FBC FG.
  
 5) P.509: PLEASE INDICATE WHICH FLOOR LEVELS THE
 EQUIPMENT ROOMS ARE ON- SEC. 107.2.1 WPB.
  
 6) P.509: SHOW THE GAS VENT PIPING RUN AND TERMINATION
 LOCATION FROM THE EQUIPMENT ROOM BY GRIDLINES 10 & K-
 SEC. 410.3 FBC FG.
  
 7) P.509: PLEASE SUBMIT SHEET P.804 THAT CONTAINS THE
 GAS MONITORING AND DETECTING DETAILS CALLED OUT ON THE
 PLAN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-03 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-03 Cont ID  
Sent By rmcphers Date 2023-05-03 Time 09:25 Rev Time 0.00
Received By rmcphers Date 2023-04-18 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-14 Cont ID  
Sent By rmcphers Date 2022-12-14 Time 16:39 Rev Time 0.00
Received By rmcphers Date 2022-10-28 Time 12:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-07-20 Cont ID  
Sent By hmoser Date 2023-07-20 Time 10:15 Rev Time 0.00
Received By hmoser Date 2023-07-20 Time 10:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-20 Cont ID  
Sent By medwards Date 2023-05-02 Time 06:04 Rev Time 0.00
Received By hmoser Date 2023-05-02 Time 06:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-06 Cont ID  
Sent By ccole Date 2023-07-06 Time 11:05 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 17:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-21 Cont ID  
Sent By ccole Date 2023-04-21 Time 15:00 Rev Time 0.00
Received By ccole Date 2023-04-21 Time 15:00 Sent To  
Notes
2023-04-21 15:01:472ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22100178
 4/21/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS
 #1 & #11 ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET SP.003 & SP.620: REFER TO SEC.
 454.1.1.1 FBC B AND PROVIDE THE FOLLOWING INFORMATION
 ON THE PLAN.
 A) THE POOL IS FOR USE BY TRANSIENT OR NON-TRANSIENT
 OCCUPANTS OF THE FACILITY.
 B) CLARIFY HOW THE BATHING LOAD WAS CALCULATED.
  
 SHEETS SP.001: PLEASE CORRECT THE CALCULATIONS SO THEY
 CLEARLY INDICATE (TRANSIENT UNITS- 5 BATHERS PER
 TRANSIENT UNIT), AND (NON-TRANSIENT UNITS- 7 BATHERS
 PER TRANSIENT UNIT)- SEC. 454.1.1.1 FBC B. CORRECT THE
 MIAMI LOCATION TO WEST PALM BEACH.
  
 11) FAILED. P.509: PLEASE REMOVE THE NOTE REQUIRING
 SEPARATE PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND
 PROVIDE EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 &
 608.16 FBC P.
  
 SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
 PLEASE PROVIDE THE REQUESTED COMPLIANCE INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By ccole Date 2022-11-08 Time 16:12 Rev Time 0.00
Received By ccole Date 2022-11-04 Time 15:27 Sent To  
Notes
2022-11-08 16:14:411ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100178
 11/8/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. BASED ON THE PERMIT
 APPLICATION PLEASE NOTE THE FOLLOWING COMMENTS ARE FOR
 THE HOTEL POOL ONLY WITH THE EXCEPTION OF COMMENT #1
 WHICH INCLUDES THE SPA.
  
 1) SHEETS SP.001 & A1.108: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE POOL AND SPA IN ACCORDANCE WITH
 TABLE 403.6 FBC P, AND TABLE 454.1.6.1, AND SEC.
 454.1.8.1 FBC B. THE FLOOR PLAN APPEARS TO SHOW THE
 BATHROOMS ADJACENT TO THE POOL DECK WILL ALSO BE USED
 BY OCCUPANTS OF THE OUTDOOR BAR. PLEASE SEE THE
 EXCEPTION UNDER SEC. 454.1.6.1.1. AND IF APPLICABLE
 THEN THE FIXTURE REQUIREMENT FOR THE BUILDING SHALL BE
 DETERMINED AND IF IT EXCEEDS THE REQUIREMENT IN TABLE
 454.1.6.1 THEN THE BUILDING REQUIREMENT SHALL REGULATE
 THE FIXTURE COUNT, OTHERWISE THE FIXTURE COUNT SHALL BE
 BASED ON THE REQUIREMENT FOR THE POOL. UNDER NO
 CIRCUMSTANCES SHALL THE FIXTURE COUNTS BE CUMULATIVE.
 PLEASE ALSO SHOW COMPLIANCE WITH THE FOLLOWING CODE
 SECTIONS-
 A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES
 THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE
 POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE
 TIMES THE AREA OF THE POOL SURFACE.
 B) SECS. 454.1.6.1.1 & 454.1.6.1.3: CONFIRM WITH
 DETAILS AND/OR NOTES THAT EACH BATHROOM CONTAINS A
 DIAPER CHANGING STATION AND A FLOOR DRAIN.
 C) SEC. 454.1.6.1.2: THE RESTROOMS ARE DO NOT APPEAR TO
 BE VISIBLE FROM ALL PORTIONS OF THE DECK. SHOW THE
 LOCATIONS OF DIRECTIONAL SIGNS FOR THE BATHROOM.
  
 2) SHEETS SP.100 & SP.120: THE PLANS SHOW ONLY TWO
 4-INCH GUTTER DRAINS. PLEASE SHOW THE LOCATIONS AND
 DIAMETERS OF ALL GUTTER DRAINS, AND NOTE THE SPACINGS
 BETWEEN DRAINS SHALL NOT EXCEED 10 FT. FOR 2-INCH
 DRAINS OR 15 FT. FOR 2-1/2 INCH UNLESS HYDRAULICALLY
 JUSTIFIED BY THE ENGINEER- SEC. 454.1.6.5.3.1 FBC B.
 A) PLEASE SHOW ALL GUTTER LOCATIONS ALONG THE PERIMETER
 OF THE POOL- SEC. 454.1.6.5.3.1 FBC B.
 B) SP.110 DETAIL 8: THE GUTTER DOES NOT APPEAR TO BE
 EITHER AN OPEN OR RECESSED TYPE AS REQUIRED BY SEC.
 454.1.6.5.3.1.2 FBC B. PLEASE PROVIDE MORE INFORMATION
 ABOUT THE DESIGN.
  
 3) SP.120: PLEASE PROVIDE TDH CALCULATIONS FOR PUMP
 SIZING- SEC. 454.1.6.5.4 FBC B.
  
 4) SP.120: PLEASE SHOW THE FLOOR INLET SPACINGS BETWEEN
 ADJACENT INLETS AND ADJACENT WALLS- SEC. 454.1.6.5.9.2
 FBC B.
  
 5) SP.130 & SP.730: PROVIDE A BACKFLOW PREVENTER FOR
 THE WATER SUPPLY LINE TO THE COLLECTOR TANK, AND
 INCLUDE AN EQUIPMENT SCHEDULE- SEC. 608.3 FBC P & SEC.
 454.1.6.3 FBC B.
  
 6) SP.700: PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE MAIN DRAIN GRATE AND SUMP SHOWING COMPLIANCE
 WITH SEC. 454.1.6.5.10.2 AND ANSI/APSP 16. PLEASE
 PROVIDE A NOTE AND/OR DETAIL ON THE PLAN INDICATING THE
 MAXIMUM VELOCITY OF WATER PASSING THROUGH THE OPENINGS
 DOES NOT EXCEED 11/2 FEET PER SECOND AT 100 PERCENT OF
 THE DESIGN RECIRCULATION FLOW. PLEASE NOTE THE SPECS
 MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE WITH SEC.
 107.3.4.1 WPB.
  
 7) SP.120 & SP.700: THE PIPING PLANS SHOW POOL
 WASTEWATER DRAINING INTO THE SANITARY SYSTEM WHICH IS
 PROHIBITED- SEC. 90-126 (5) WPB CODE OF ORDINANCES. THE
 DRAWINGS ALSO SHOW THE COLLECTOR TANK OVERFLOW DRAINING
 INTO THE STORM. PLEASE REVIEW THE FOLLOWING INFORMATION
 AND REVISE THE PLAN ACCORDINGLY.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 8) SP.120, SP.700, SP.730 & P.509: THE EMERGENCY SHOWER
 AND EYEWASH STATIONS SHALL CONFORM TO ISEA Z358.1.
 SUBMIT MANUFACTURER' S SPECIFICATIONS TO VERIFY
 COMPLIANCE.
 A) PLEASE NOTE IF HOT WATER IS SUPPLIED TO THE UNIT IT,
 THE TEMPERATURE OF THE WATER SUPPLY SHALL ONLY BE
 CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P. PLEASE NOTE
 THE SPECS MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE
 WITH SEC. 107.3.4.1 WPB.
  
 9) SP.100 & SP.120: SUBMIT MANUFACTURER' S
 SPECIFICATIONS FOR THE POOL LIFT SHOWING COMPLIANCE
 WITH SECS. 1009.1- 1009.2.9 FBC ACC. PLEASE NOTE THE
 SPECS MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE WITH
 SEC. 107.3.4.1 WPB.
  
 10) SP.100: PLEASE CLARIFY IF THE SLOPED ENTRY FOR THE
 POOL IS INTENDED TO MEET COMPLIANCE WITH SECS. 242.2 &
 1009.3 FBC ACC BECAUSE THE CURRENT PLAN SHOWS
 NON-COMPLIANCE WITH SECS. 1009.3.2 & 1009.3 FBC ACC-
 1009.3.2 SUBMERGED DEPTH.
 SLOPED ENTRIES SHALL EXTEND TO A DEPTH OF 24 INCHES
 MINIMUM AND 30 INCHES (760 MM) MAXIMUM BELOW THE
 STATIONARY WATER LEVEL. WHERE LANDINGS ARE REQUIRED BY
 405.7, AT LEAST ONE LANDING SHALL BE LOCATED 24 INCHES
 MINIMUM AND 30 INCHES MAXIMUM BELOW THE STATIONARY
 WATER LEVEL.
 1009 1009.3.3 HANDRAILS.
 AT LEAST TWO HANDRAILS COMPLYING WITH 505 SHALL BE
 PROVIDED ON THE SLOPED ENTRY. THE CLEAR WIDTH BETWEEN
 REQUIRED HANDRAILS SHALL BE 33 INCHES MINIMUM AND 38
 INCHES MAXIMUM.
  
 11) P.509: PLEASE REMOVE THE NOTE REQUIRING SEPARATE
 PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & 608.16
 FBC P. SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
  
 12) SP.700: PROVIDE A POOL EQUIPMENT SUBMITTAL PACKAGE
 THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS LISTED IN
 THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND
 RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT-
 SEC. 107.2.1 WPB. PLREASE NOTE ALL SUBMITTALS CAN BE
 DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC.
 10.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-03 Cont ID  
Sent By rmcphers Date 2023-05-03 Time 09:24 Rev Time 0.00
Received By rmcphers Date 2023-05-03 Time 09:23 Sent To  
Notes
2023-05-03 09:24:36SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP120, 1.51, 1.52, 1.53, 1.54, DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By rmcphers Date 2022-12-14 Time 16:37 Rev Time 0.00
Received By rmcphers Date 2022-12-14 Time 16:37 Sent To  
Notes
2022-12-14 16:39:40SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By ckimmer Date 2022-11-21 Time 15:18 Rev Time 0.00
Received By ckimmerl Date 2022-11-21 Time 15:17 Sent To  
Notes
***NONE***